Document MbOabqzbweYLKZNYz76jmL5a

PLAINTIFF'S EXHIBIT Inter Office Personnel end OrpenUetlon staff March 23, 19B3 Mr. R. C. Scott Safety Engineer Van Dyke Plant cc R. D. Byron J. J. Vhelan Subject! Bulk ABbeatoa Material Re-Teat - Insulation Material frost Van Dyke Plant Powerhouse As a result of discrepancies between asbestos testing results fron our Industrial Hygiene Laboratory and the Michigan Department of Public Health (MDPH), the two bulk samples of insulation material received on 26 February 19B3 were forwarded to an outside laboratory for further analysis. Samples were sent to EnvironmentalResearch Group, Inc. of Ann Arbor and analysed by polarised light microscopy (PLM). PLM is the same technique used by MDPH. The attached analytical report indicates the subject samples did indeed contain asbestos. Specifically, 14 peroent ohrysotile and 22 to 23 percent amosite forms of asbestos were found which is relatively consistent with MDPH results. Conse quently, the insulation material must be regarded as containing asbestos and all aspects of OSHA Asbestos Regulation 29CFR 1910.1001 oust be complied with. Ve are investigating possible causes of our initial false negative report. We believe it to be related to a possible masking effect in the color changes when both amosite and chryeotile forms of asbestos are present in the sample. StepB have been taken to assure that this does not ooour with future samples. Our initial report of 10 March 19B3 should be disregarded. If you have further questions, please call on 33-76935* dw Attachment D. S. Carruthers, Industrial Hygienist Industrial Hygiene & Toxicology Department Employee Health Services 8006 0078 SCF-FORD-3294 PRODUCED BY FORD ANALYTICAL REPORT ENVIRONMENTAL RESEARCH GROUP, INC. IIV N FIRST ANN ARSON. KJCHICAf. 48104 (313) 662-3104 PROJECT REPORT DATE 9457 03-16-83 L.L J ENT f u REPORT 52 UP* 4bl 11 BAIlPl.ES REC'.'D: 03-14-83 REFER TECHNICAL QUESTIONS TO: KATHRYN Hv BERRY, CIH CLIENT: FORD MOTOR COMPANY CENTRAL LAB INDUSTRIAL HYGIENE 15000 CENTURY DR. DEARCORN. MI 48121 ATTENTION: DAVE CARRUTHERS APPROVED. KuJ f RESIDUAL SAMPLES WILL BE HELD FO*#R* TWO WEEKS CLIENT I D. ERG SAMPLE NO. MATRIX DSC 163/ 03/096269 BULK SAMPLE PARAMETER RESULTS ASBESTOS. BULK ANALYSIS iHi n> CHRYSOTILE AMOSIT CROC)OOLITE OTHER ASBESTOS FIBER CLASS. MINERAL WO.i.. OTHER COMPONENT HOMOGENIZED PRIOR TO ANALYSIS FRIABILITY COMMENTS APPEARANCE FIBRCJS WHITE COLOR 14 25 ND (1) ND (1) ND (1) MORTAR YES MODERATE HOMOGENEOUS MATERIAL UNITS X X 7. 7. X CLIENT 1.0 ERG SAMPLE NO MATRIX DSC lt-.J 03/096240 BULK SAMPLE PARAMETER RESULTS UNITS ASBESTOS. BULK ANALYSIS (Pi M> CHRYSOTILE AMOSITS CROC IDOL1TE OTHER ASCESIOs FIBER GLASS. MINERAL WOui OTHER COMPONENT HOMOGENIZED Phi OR TOAUAi.VSIS FRIABILITY 14 22 ND (1) ND (1> ND (1) MORTAR YES ^ MODERATE PAGE 1 SEE LAS. PAGE FOR EXPLANATION OF SYMBOLS /. xx xx CONTINUED PQ8006 0079 PRODUCED BY FORD ANALYTICAL REPORT ENVIRONMENTAL RESEARCH GROUP, INC. ERG PROJECT NO. 9457 - FORD MOTOR COMPANY 03-16-83 COMMENTS' APPEARANCE - HOMOGENEOUS MATERIAL FIBROUS WHITE COLOR t' 8006 0080 FW - Ml f Jfc.l.0 hti UKT FOH RtSUl.T NA - HOT AH Pi K Alii E TO Tt .T REGUESTED ND - IJOUbfr U-.CTED, OtTECT 1 >)N LIMIT IN <J SO * UAMPlE D/.f'iA.',L 0 SR - SEC AT VACHi 0 REPORT iCR RESULT < - POSITIVE RL'Sui T BUT AT UNGUANTIFIABlE CDNCEWIRATICN BELOU INDICATED LEVEL TmAU.\ \GU F.IR YOUR BUSINESS ! PACE J IAJT PACE A m "o0 PRODUCED BY FORD