94 CHAPTER 4 '1946 Guide NRc = Sl YL 12 iii (67) Coefficients from these curves must be multiplied by --^=i==, the velocity of approach factor, in accordance with Equation 46, to obtain the value of K to use in the various equations. The expansion factor for nozzles, designated by ip, is obtained from a rational formula, as already noted. = 1 \ Pi) ( k yi-to/fr)*- 1/k\( 1-P4 \ \k-ij\i- ft/p, A i - P` to/p.)2/*) (68) This formula is plotted for k = 1.40 (air and other diatomic gases) and k = 1.30. (steam, carbon dioxide, natural gas) in Figs. 21 and 22, respect ively. . Fluid Flow.|;_________________________________________________________ \' 95 pressure, which is the sum'of the static and kinetic pressures, while' the tube directed crosswise receives only the static pressure; the difference between the two, as read on the separate tubes or on the U-tube is, of ' course, the kinetic pressure. The velocity is expressed as _.F= V2iAT ' (69) Application of Equation 57 serves to make the. formula general, assuming that water is used in the manometer connecting the two tubes. Using tins equation, and mutiplying by 60 to convert feet per second to feet per minute, Fm = 1096.5 ^*25 , (70) in which Vm is the rate of flow in feet per minute. Fig.' 21. Relation of Expansion Factor, 9, for Nozzles to Diameter Ratio and Pressure Loss for Air and Other Diatomic Gases FLOW MEASUREMENT BY PITOT TUBE There remains one other head type meter useful in ventilating work, the Pitpt tube, named for the Frenchman who discovered the principle. The Pitot tube is essentially a bent tube with its open end pointed upstream, combined with another tube with its end pointed crosswise to the flow or downstream,, or connected to openings crosswise to the flow. Used with flowing liquid, the liquid will rise in each tube, but higher in the one pointed upstream. Used with a flowing gas, and the two tubes connected by a U-tube containing.water,.the liquid level in the U-tube will be displaced, with the lower level on the side connected, to the tube pointed upstream.- The tube'directed upstream receives the impact Fig. 22. Relation of Expansion Factor, 9, for Nozzles to Diameter Ratio and Pressure Loss for Steam, Carbon Dioxide and Natural Gas It is often difficult to obtain the exact static pressure. In the usual construction of Pitot tubes, the static pressure openings are downstream from the impact pressure opening, and turbulence induced by the nose may affect the static pressure reading. If the static pressure openings point downstream in any degree, a suction effect is' produced to falsify the reading. In instruments having the static pressure opening pointed downstream, the coefficient may be as low as 0.86. Consequently, for , accurate work, Pitot tubes should be calibrated, and the pertinent coefficient should be applied to-Equation 69. In a sense,, this coefficient is advantageous, since it results in a higher differential reading, which, in turn, enables more accurate readings at low flows. In.using Pitot tubes, it is generally necessary to make a traverse of the pipe or duct to. determine the course of the velocity pattern. In a .pipe, for instance, one of the profiles, shown in Fig. 5 would be obtained. Near a valve or fitting, however, the profile might be quite distorted, a ^