812
CHAPTER 51
heat output rating is 75 percent of the approved heat input to the burners for fan-type units, and 70 percent for gravity-type
Space Heaters
Space heaters are defined as heating units that tAlra the air for combustion from the space being heated. They may be broadly classified as room heaters and unit heaters.
Room heater* are used for heating either single rooms or-con-
necting rooms with good circulation between them, and, ex
cept for wall-type heaters, they are scimportable. Unventedtype room heaters should not be used, nnWa space is'properly
ventilated to prevent excess moisture and to provide sufficient combustion air to prevent formation of carbon monoxide. All
types of room heaters can be automatically controlled, al though they are generally controlled manually. When
equipped for automatic control, they must have an automatic pilot as part of the control equipment. Room heaters may be classified as follows:
Circulator*, .vented and (invented, that heat the room
mainly by convection, although some have radiants over the burner, with windows in the front to allow some heat by
radiation. Some circulators are available with voted combus
tion chamber*, so that they take combustion air from outdoors,
near the flue gas terminal.
...
Radiant heater*, usually (invented, although some vented
types are available, have a refractory' directly above the burners which is heated to incandescence, and gives off.-an
appreciable part of its heat in the form of radiant energy.
Wallheaters are usually a typeof radiant heater constructed
with sufficient insulation (either solid or circulating air) tp prevent overheating of the casing, and are built into a wall
with the front flush with the wall surface. Their heat input
1965 Guide And Ddtti'Book
-rating is limited to a marimnm of 25,000 Btuh. . Unit heater* are used extensively for heating large such as stores, garages, and factories. These heaters of a burner, heat exchanger, fan for distributing the air, draft hood, automatic pilot, and controls for burners and fan. They are usually mounted in an elevated position from which the heated air is directed downward by louvers. Some unit heaters are suspended from the ceiling, and others are free-standing floor unite of the heat tower type. Unit heaters are for use with or without ducts, depending on specific A.GJL approval. When connected to ducte,.they must have sufficient blower capacity to deliver an adequate air quantity' against the duct resistance. Heat output is required to be at least 75 percent of heat input to the burners. Duct furnace* are usually of the unit heater type without the fan, and are used for hrating air in existing duct systems where blowers are provided for moving the air through the system. Duct furnaces are tested for operation at much higher static pressures than are obtained in unit beaters.
COMMERCIAL AND INDUSTRIAL
There are many basic types of industrial gas burners, but only those commonly used for heating service will be covered here. These burners may be either of the atmospheric or power type.
Atmospheric Burners . .
Burners of the atmospheric type are most frequently .made
up of a multiple of tubes or burners, each with a Venturi, gas
orifice, and burner heads. These burners are of inshot or. up
shot design.
: ''' '
Inshot burners are placed horizontally, melting them par-
ticulariy adaptable to firing Scotch-type boilers. Upshot
burners are arranged vertically, malting them more
in firebox type boilers.
Power Burners
Burners of the power'type employ a fan to . supply
control combustion air. These burners be of either natural
draft or forced draft type.
,...
In natural draft installations, a chimney is required to draw
the products of combustion through the boiler or-furnace;
the burner fan supplies only enough power to move the air
through the burner. Many natural draft power burners have a
configuration wimilar to that of an inshot atmospheric burner
to which a fan and windbox have been added: More complex
Automatic Fuel-Burning Equipment
Table 2...Capacity of Gas Piping--Cu Ft Per Hr (At pretan drop of 0.3 in. water. Specific gravity 0.60)
length at Pipe O
40
80
150 . 200
froa Pipe Site (IPS) laches
X X IX 1H 2 2X 3
520
1,050
1,600
3,050
4,800 8,500
92 190 350
730 1,100 2,100 3,300 5,900 .
73 152 285
590 890 1,650 2,700 4,700
63 130 245
500 760 1,450 2,300 4,100
115 215 105 195
180 43 90 170
440 670 1,270 2,000 8,600
400
610
1,160
1,850
3,250
370 560 1,050 1,700 3,000
350 530 990 1,600 2,800
40
84 160 79 150
320 490 930 1,500 2.600 305 460 870 1,400 2,500
72 130
275 410 780 1,250 2,200
31 64 120 250 380 710 1,130 2,000
28 59 110 225 350 650 1.050 1,850 28 55 100 210 320 610 980 1,700
From Americas Standard Installation el Oat ApjUaeeet anA Oat Piping, ASA 221JO-1859.
4
17,500 12,0009,700 8,300
7,400 6,800 6,200 5,800
5,400 5,100 4,500 4,100
3,800 3,500
813
length of ripe Ft
10 20
60 60 70 80 90 125
175
gas-air miring patterns are possible, and combustion capabil-
ites are thereby improved.
The fan size and speed on power burners have been grad
ually increased and the combustion process modified so that
the fan not only moves air through-the burner, but also forces
it through the boiler. Only a vent is required to release the
flue gas products at a height above a nuisance level and
combust'TM1 occurs under pressure. These burners are classified
as forced draft burners. In a forced draft power burner, gas in
put is .usually controlled-by throttling valves or equivalent
pioona external to the burner. The gas is introduced into a con
trolled air stream designed to produce thorough gas-air mixing
but still capable of maintaining a stable flame front. In a ring
burner, the'gas is introduced into the combustion air stream
through a gas filled-ring just ahead of the combustion zone.
In a premix burner, gas .nH primary air are mixed together,
and the mixture is then introduced into secondary air in the
combustion zone. The power burner affords superior control of combustion,
particularly in restricted furnaces
under forced draft
conditions. Commercial and industrial gas burners .can : frequently
operate from higher gas pressures than are employed . for
domestic equipment. It is necessary to determine both maxi
mum
minimum gas pressures to be applied to the con
trols of these burners. If'the maximum gas pressure exceeds
the 14 to 18 in. standard for domestic equipment, appropriate
consideration must be taken in the selection of burner control
equipment.
Infrared Heaters
Infrared heaters, vented or (invented, are used extensively for Wring factories, foundries, sports arenas, loading docks, garagp and other ingtalhdanns where convection heating is difficult to apply. There are two general types of gas-fired infrared heaters:
1. Surface combustion radiant heaters which have a ported re fractory or metallic screen burner face through which a selfsufficient mixture of gas and air flows. The gasman* mixture burns on'the surface of theburner face hiring it to incandescence and
releasing beat by radiation. These units operate at surface tem peratures of about 1600 F, are generally (invented, and have rated inputs up to 50.000 Btu per hour per unit.
2. Internally-fired beaten which consist of heat exchanger with the *xp<d surface radiating.heat,at a surface temperature of approximately 800 F. The erposed surface can be equipped with reflecting louvers or a single large reflector to direct the radiated energy. Units of type are available with rated inputs up to 125,000 Btu per hour and are usually vented.
Infrared heaters of the types described above ore usually mounted in elevated positions and radiate heat downward. For further information, see Chapter 14 of the 1964 Guide And Data Book.
Sizing of Gas Piping
Piping for ga appliances should be of adequate size, and so instjillftd as to provide a' supply of gas sufficient to meet the maximum demand without undue loss of pressure between the point of supply (the meter) and the appliance. The size of gas pipe required depends upon the following:
L Maximum gna imunmptifln to be provided. 2. Length of pipe and number of fittings. 3. Allowable loss in pressure from the outlet of the meter to the appliance. 4. Specific gravity of the gas.
To obtain the cubic feet per hour of gas required by the appliance,' divide the Btu input rate at which .the appliance will be adjusted by the average Btu heating value per cubic foot of the gas.
Capacities of different sizes and lengths of pipe, in cubic feet per hour, with a pressure drop of 0.3 in. of water column for a gas of 0.60 specific gravity, are shown in Table 2. In adopt ing a 0.3 in. pressure drop, due allowance for an ordinary number of fittings was made.
To convert the values given in Table 2 to capacities for an other gas of different specific gravity, multiply the tabular values by the multipliers shown in Table 3.
Pipe capacities for gas flow up to 100,000 ch for various lengths of pipe are given in fig. 11 which is based on a specific gravity of 0.60. The capacity at a given pressure loss for a
4$