Document MQM5ndmQVMBqVdb5zqEn1d3V
Westinghouse Electric Corp. Sharon, Pa.
Purchasing Dept. Spec. 7336 M (Not for publication)
INERTEEN
1. This specification covers nonflammable insulating liquid used
in specific designs of transformers where the fire hazard of in
sulating oil is to be eliminated. It is designated as Inerteen
7336-9* The material is a mixture of 60 per cent chlorinated di
phenyl, and 40 per cent trichlorbenzene, by weight, with 0.20 per
cent phenoxypropene oxide added.
2. No change shall be made in the quality of successive shipments
of material furnished under this specification without first obtain
ing the approval of the purchaser.
CHEMICAL AND PHYSICAL PROPERTIES AND TESTS
3. PHENOXYPROPENE OXIDE CONTENT: The Inerteen shall contain 0.18
to 0.22 per cent by weight of phenoxypropene oxide.
4. NEUTRALIZATION NUMBER: The neutralization number shall be less
than 0.014 mg. of KOH when determined in accordance with ASTM D-974.
5. FREE CHLORIDES: The material shall not contain more than 0.10 ppm
of free chlorides when determined in accordance with ASTM D-901.
6. CONDITION; The material shall be clear.
7. SPECIFIC GRAVITY: The specific gravity at 15*5 C/15 C (60 F/60F)
shall not be less than 1.560 nor more than 1.568 when determined
in accordance with ASTM D-901.
8. VISCOSITY: The viscosity at 37*8 C (100 F) shall be 54 seconds,
plus or minus 2 seconds, when determined by Saybolt Universal Vis
cosimeter in accordance with ASTM D-88.
9. COLOR: The color shall be not greater than 150 A.P.H. when tested
in accordance with ASTM D-901.
10. FIRE POINT: The material shall have no fire point when tested
according to ASTM D-92 to its boiling point.
11. CHEMICAL STABILITY: There shall be no generation of free chlor
ides when a specimen is refluxed with distilled water for six hours in
the presence of air.
12. POUR POINT: The pour point shall be lower than minus 32 C (-25.6F)
when determined in accordance with ASTM D-97.
13. DIELECTRIC STRENGTH: The dielectric strength at point of ship
ment shall not be less than 35,000 volts and not less than 30,000 volts
at destination when tested in accordance with ASTM D-877.
14. ELECTRICAL RESISTIVITY: The electrical resistivity at 100 C (212F)
when tested at 500 volts D-c shall not be less than 100 x 109 ohms/cm3.
15. CORROSION: After heating with the bright aluminum for six hours
at 200-220 C (392-428 F), the aluminum shall not be corroded either on
visual inspection or weight determination, and the Inerteen shall con
form to the following:
Color, Max
400 A.P.H.
Acidity, Max
0.014
DSW 550778
Free Chlorides, ppm. Max 5.0
,,Condition
Clear
16. REFRACTIVE INDEX: The refractive index at 25 C (77 F) shall not
be less than 1.6137 nor more than 1.6157 when tested according
to ASTM D-901.
Continued
STLCOPCB4089195
page 2 Westlnghouse Electric Co.
Tentative Spec. 7336- M
17. TEST METHODS: The test for phenoxypropene oxide shall be made
in accordance with Weatinghouse Eleotric Corporation Material Test
Specification 80166, which shall be considered.a part of this spec.
PACKING AND MARKING
id. PACKING: Shipping containers dial1 conform to the requirements
of Weatinghouse Electric Corp. Purchas. Dept. Spec. 6824 2.
19. ' MARKING: (19.1) Containers other than tank cars shall be
marked in accordance with the requirements of Westlnghouse Electric
Corporation Purchas. Dept. Spec. 6824-2.
_ (19.2) Each tank car shall have a packing slip bearing the following
information: Purchase Order Number; P D Spec 7336-9-M; Batch Number;
Number of Gallons; Name of Manufacturer.
INSPECTION
.
.
20. Inspection: The manufacturer shall furnish the Purchasing Agent
of the Westlnghouse Electric Corporation a test report of the tests
made in accordance with Sections 3 to 17 inclusive of this specifica
tion on each shipment of Inerteen.
21. SAMPLES: (21.1) For Inerteen shipped to any Westlnghouse plant
except Sharon, Pennsylvania, the manufacturer shall furnish a one
quart sample from each shipment to the purchaser by parcel post. *
(21.2) For shipment of Inerteen to the Sharon, Pennsylvania Works in
lieu of samples the manufacturer shall furnish a certified test report
of the tests made in accordance with Sections 3 to 16 inclusive of
this specification cn each tank oar or shipment of drums.
COPIED JBT:dth 6/24/53 6/1/53
JZ-stc.
DSW 550779 STLCOPCB4089196