550 CHAPTER 22 1955 Guide temperatures. Piping should be insulated to the same thickness and stand ards as for steam at the same temperature. Valves for high temperature water should be made with cast steel bodies Table 8. Head Loss in Fittings' (For turbulent flow) Feet of Same Size Pipe Having Equal Loss9 Fittings 10 8 6 5 4 3 21. 2 11 l 1 1 Globe Valve.................. 340 270 200 170 135 105 83 70 55 45 36 28 21 Gate Valve.................... 7 5.75 4.5 3.5 3 2.2 1.7 1.5 1.2 1 0.8 0.6 0.5 90 Welding Elbow.... 11 8.5 6.5 5.5 4.5 3.5 2.6 2.2 1.8 1.5 1.2 0.9 0.7 45 Welding Elbow.... 7 6 4.5 3.6 3 2.4 1.7 1.5 1.2 1. 0.8 0.6 0.5 2234 Welding Elbow.. 5 4 3 2.5 2 1.6 1.3 1.1 0.9 0.7 0.6 0.5 0.3 Lateral1*........................... 26 20 16 13 11 8 6.5 5.5 4 3.5 2.8 2.2 1.6 Lateral9........................... 17 14 10 8.5 7 5 4 3.5 2.8 2.5 1.8 1.5 1.1 Welding Tee'................ 13 10 8 7 5.5 4 3.2 2.6 2. 1.7 1.4 1.2 0.8 Concentric to Reducers \ 10 8 6 5 4 3 From 2 m m 1 Vi 'A 10 8 6 5 4 3 m 2 m m i \ \ 1 2.5 3 2.8 3.5 \ \ 1.2 2 2.2 2.2 C )NTRAC TING 10 3.5 \ \ 0.5 1.3 1.8 1.7 12 7.5 1.5 \ \ 0.5 1.2 1.4 1.5 12 9.5 4.5 1.5 \ \ 0.6 1.2 1.4 1.5 10 7 5 1.8 \ \ 0 0.8 1 1 7.5 6 3.8 0.7 \ \ 0 0.7 0.8 0.75 6 5 2.5 0.8 \ \ 0 0.6|o.6 0.6 5 3.8 2.8 9 \ \ 0 0.5 0.5 0.5 4 3 2 0.3 \ \ 0 0 0.3 ElI LA itGEMG 3 2.5 1.25 0.5 \ 0 0.3 % 2.5 2 1.3 0.5 0 1c Vo 2 1.8] 1 - 5 0.8_J\ * Compiled from data published by Tube Turns, Inc., a Division of the National Cyliod Used by permission. b Water deflected through branch. 9 Water flowing straight through fitting. d For eccentric reducers, the values read for ooncentric reducers must be increased by 33J%9 Equivalent length of pipe having a Fanning friction coefficient of 0.006. and stainless steel trim since these have proved far more satisfactory than bronze valves. Wedge-type gate valves are recommended for isolating an for use within the boiler house. For general use throughout the system, globe valves are preferred. Hot Water Heating Systems 551 Valves combining flow control and regulation are preferable for high temperature water where heat balancing is necessary, since a small quan tity of this water contains a large quantity of heat. As high temperature water is more penetrating than low temperature water, leakage due partly to capillary action should not be ignored' because even a small amount of. leakage evaporates immediately. This slight leakage becomes noticeable only on the outside of the gland and spindle of the valve where thin de posits of salts are left after evaporation. Control The control of temperature is usually obtained by conventional means although it is common practice to place control valves on the outlet line of Table 9. Properties, of Water (212 F to 400 F) Temperature F Pressure* psia Density Lb/CuFt Specific Heat Btu/(lb)(F) Total Heat Above 32 F Btu/Lb* Btu/CuFt 212 14.70 59.88 1.0055 180.00 10.760 220 17.19 59.66 1.0068 188.06 11.222 230 20.78 59.37 1.0087 198.15 11.764 240 24.97 59.17 1.0104 208.26 12.327 250 29.82 58.84 1.0126 218.39 12.856 260 35.43 58.62 1.0148 228.55 13.403 270 41.85 58.25 1.0174 238.74 13.912 280 49.20 58.04 1.0200 248.95 14.555 290 57.55 57.65 1.0230 259.20 14.942 300 67.01 57.41 1.0260 269.48 15.476 310 77.68 57.00 320 89.65 56.65 330 103.03 56.31 340 117.99 55.95 350 134.62 55.65 1.0296 1.0332 1.0368 1.0404 1.0440 279.80 290.17 300.59 311.05 321.55 15.955 16.444 16.931 17.407 17.899 360 153.01 55.19 370 173.33 54.78 380 195.70 54.36 390 220.19 53.96 400 247.25 53.62 1.0486 1.0532 1.0578 1.0624 1.0670 332.10 342.71 353.39 364.14 374.96 18.333 18.778 19.213 19.644 20.106 * Reprinted by permission from Thermodynamic Properties of Steam, by J. H. Keenan and F. G. Keyes published by John Wiley and Sons, Inc., 1938 edition. the heat absorbing equipment where the temperatures are lower. In larger distribution systems means of controlling differential pressures be tween the flow and return mains are advisable. With space and process heating, temperatures can be controlled within close limits by the use of two- and three-way mixing valves modulating or by-passing some of the high temperature water. Such controls are essential at heat exchangers or converters. Boilers or Hot Water Generators Almost any high pressure boiler can be used for high temperature water systems, but certain types as, for example, the water tube boiler, are more advantageous than others. Boiler selection is important and such proberns as frictional head loss, available water space, flue outlet, type of firing,