Document MMYgXY0yXaVqY5gORGQ8ee9Zz

THE PROPER HANDLING OF AROCLORS AND THEIR MIXTURES IN THE ELECTRICAL INDUSTRY Monsanto U. Monsanto Chemical Co. Organic Div. Sales Dept. 800 N. Twelfth Blvd. St. Louis, Mo. 0237230 P. G. BEN I GNUS MAY 1, 1956 TOWOLDMON0027460 WATER_PCB-00011929 INDEX Introduction Chapter 1 Chapter 2 Chapter 3 Chapter 4 Chapter 5 Chapter 6 Chapter 7 Chapter B Chapter 9 The Proper Handling of the Aroolors and Their Mixtures in the Blectrlcal Industry. Procedure Tor Unloading Tunkcars of Aroolors and Their Mixtures. A. Description of the Cars. B. Procedure for Unloading the Cars. C. Drum Packaging Storage Tanks A. General Description of Storage Tanks. B, Detailed Description of Storage Tunks. Gasketing and Pump Packing. Sampling. Laboratory Analysis and Procedure for Treating Aroolors and Their Mixtures. Test Procedures. Typical Properties. Earth Treatment of Aroclors and Their Mixtures in the Electrical Industry Prior to Use. Dermatology and Toxicology. Attachments: Drawing No. 31-20848, Dome Detail. Drawing No. 31-20847, The Tank Car. Drawing No. 9C-8170-5, The Horizontal Storage Tank. Drawing No. D-13362, The Vertical Storage Tank. Drawing No. 9C-8243, The Breather. Drawing No. 9C-8278, The Varec Gauge. Drawing No. 9C-8178, The Unloading Platform. 0237231 | TOWOLDMON0027461 WATER_PCB-00011930 THE PROPER HANDLING OP AROCLORS* AND THEIR MIXTURES IN ME ELECTRICAL INDUSTRY INTRODUCTION Monsanto's Aroclors*, especially the chlorinated biphenyls Including typeB 1242, 1248, 1254 and 1260, used alone or in combination with chlorinated benzenes, are commonly used die lectrics materials of the Askarel^ class. Askarel is a generic name referring to liquid dielectrics derlvftdkSrefi halogenated aromatic hydrocarbons possessing excellent chemical and dieleotrie stability and fire-reBlstance over the temperature ranges and operating conditions required of transformers and capacitors in the electrical industry. The properties of AroolorB and their mixtures, used as dleleotrlcs are described in detail in Chhpter 7 entitled, "Typical Properties". These dielectrics are manufactured under very carefully controlled conditions in order to meet the strlot and exacting electrical requirements and properties. The electrical industry's use of these fluids has been largely in accordance with the General Electric Company's patents and developments. Aroclors - Monsanto's chlorinated blphenylB and chlorinated polyphenyls. Registered D.S. Patent Office. *?. M. Clark, "Electrical Insulation", Chem. Eng. News 25, 2977 (1947). ------- ------------ 1 02 37232 TOWOLDMON0027462 WATER_PCB-00011931 Resulting from the wide use of these materials In the Industry, trade nameB have been established to Identify them by different manufacturers of electrical equipment. LIbted alphabetically the trade names Include, "Chlorextol," Allis Chalmers; "Diaclor," Sangamo Electrio; "Dykanol," Cornell Dubilier; "Elemex," Line Materials; "Hyvol," Aerovox; "Inerteen," Westlnghouse Electric; "Noflamol," Wagner Electric; and "Pyranol," General Electric Company. The purpose of this bulletin Is to assist the Industry With 'theoproper and safe handling of these dleleotrlo materials In their operations. 0E37233 2 TOWOLDMON0027463 WATER_PCB-00011932 CHAPTER 1 PROCEDURE FOR UNLOADING TANKCARS 07 AROCLORS AND AROCLOR MIXTURES A, Description of the Cara Aroolor and mixturea of Aroolora with chlorinated benzenes are shipped by Monsanto In two types of Insulated tankcars both of which are either aluminum lined or zlnc-tla metallized. One type of ear has heating oolls Inside of the tank and these are In direct contact with the product. The other, a more widely uaed type or car, is a double-shell tank with heating oolla between the Inner and outer shells. The steam coll connections are at the bottom of the car. Both types of tankoars are tested for 60 pounds pressure and their steam oolls are tested for 200 pounds gauge pressure. The cars are top-unloaded by displacement with dry air containing 10 mg. HgO/cu. ft. maximum. There are two or three connections on the tankcar dome depending on the type of oar. Where three connections exist, one Is a two Inch diameter unloading line Which extends to the bottom of the oar, the second is a one Inch diameter air Inlet connection and the third Is a two Inch diameter pressure safety vent, whloh Is a thin lead disc adjusted to release any pressure In exoesB of 60 pounds gaage. This safety vent Is hooded for protection against dust, dirt or accidental bumping. Where only two connections exist on the dome, one Is the two lnoh diameter unloading line and the other is the safety 3. 0237234 J TOWOLDMON0027464 WATER_PCB-00011933 vent. On these ears. It Is necessary to remove the safety vent and Introduce the displacement air through that connection. Drawing No, 31-20848 shows In detail the dome of a tankoar with three connections. "A" Is the two Inch unloading line Whloh extends to a small sump at the bottom of the car. "B" Is the one Inch air Inlet oonneotlon. "C" Is the hooded safety vent. Hie car dome cover with fitted bolts Is shown In the center. It Is fitted with a Oarlock 901 asbestos gasket or an a&lumlnum envelope Goetze gasket. This drawing also shows a bottom opening In the oar. TfclB oan be opened only from the InBlde of the car and Its purpose Is for cleaning operations. It has no use at all In unloading the car. Drawing No. 31-20847 shows the over-all dimensions of the 8,000 gallon Aroclor tankcar. B. Procedure for Unloading the Cars The car should be spotted at an unloading dock similar to the one shown by Drawing No. 90-8178. The car must be level and the brakes Bet properly. "STOP-Tankoar Connected" signs should be placed fore and aft the car to warn switching crews. If It Is raining or snowing or the humidity Is extremely high, it Is not advisable to open the car. In case the oar must be sampled and opened during bad weather, a canvas oanopy must be placed over the dome of the car. It Is preferable to unload the oars under roof or Inside the factory. Unless It Is absolutely necessary because of following described situations 4 023*2" | TOWOLDMON0027465 WATER_PCB-00011934 the dome cover should not be opened until ready for sampling. The dome oover Is sealed with a standard railroad wire and seal, and Monsanto should be notified if this seal is foundbbroken upon receipt of the oar. The first step In unloading is to Inspect the dome and clean around the dome oover to remove all loose dirt, water or snow. Wiping rags and a brush should be used to clean before the dome cover and connections are opened. Then, the screwed hood over the alr-lnlet valve should be removed and this valve opened fully and left open while heating the car. A Weston or metal encased thermometer should be In serted through this alr-lnlet valve opening and the temperature of the Interior of the car determined. If the car temperature Is below the caution temperature shown In the following Table 1, It will be necessary to take the special step of Inserting a "hair-pin" heating coll through the dome of the car to preclude rupturing the tankcar seams during the heating period. Product ASTM Pour Point C, Temperature00C. Below which Caution Must Be Deed in Heating Aroolor 1260 Aroolor 1254 Aroolor 1248 +30 +10 -7 + 40 +20 +5 Aroolor 1242 Pyranol 1467 Pyranol 1470 - 19 - 10 Pre-heating is not required* Pre-heating Is not required* Pyranol 1481 Pre-heating Is not required* Exoept if the material has cooled be&ow -10C. and crystals of scavenger have separated. Then, the material should be heated to 70C. (158P.) until complete solu tion has been accomplished. ' 0237236 | TOWOLDMON0027466 WATER_PCB-00011935 If the done of the car Is to be ppened for the pre-heating operation. It is necessary that It be covered with a olean oanvas. Extreme care oust be taken to avoid getting dirt or moisture into the oar. It la due to the relatively high viscosity of some of the Aroclors at low temperatures that It becomes necessary to form a column of molten material from top to bottom of the car. In the center, to prevent hydraulic pressure build-up which mayrupture the tank shell If there Is too rapid localized heating when employing the main steam oolls. When such pre-heating Is required, a satisfactory vent hole can be made by Inserting a "halr-pln" coil (1/f Inch diameter brass, galvanized, or stainless Bteel pipe) Into the open dome of the oar and Introducing steam through the ooll until there Is a oolumn of fluid Aroolor from top to bottom. After the vent hole Is melted through the material to the bottom of the oar, the "hair-pin" coll should be removed and the dome cover replaced and bolted. Steam Is then Introduced Into the main colls. It is recommended that the steam pressure be limited to 100 pounds gauge pressure, particularly In the case where the oolls are In direct contact with the Aroolor. The steam ooll outlet should be trapped or throttled with a valve. It will require eight to twenty hours to bring the material to pumping temperature - depending upon weather 6 0Z372JT | TOWOLDMON0027467 WATER_PCB-00011936 conditions, it is essential that the air inlet valve be open during the heating period in order to vent the tank. Some ealoulatlons have been made to indicate the heat requirements for an Aroclor oar. Data for an 8,000 gallon oar of Aroelor 125*1 ares Specific Gravity = 1.5 Specific Heat = 0.26 BTU/lb./'F. Heat requirement for heating Aroolor from 30C. (86F.) to llO^C. (230F.) 1b: 8000 x 1.5 x 8.33 x 0.26 x (230-86) 3,77*,000 BTU. For heating from 30C. (86F.) to only 75C. (167'F.), the heat required Is 2,110,000 BTU. A nine horse power boiler operating at 80 pslg produces 263 lbs./hr. of steam with no reused condensate. Returning condensate at 200F. will increase the steam output to 296 lbB./ hr. at 80 pslg. In the first ease, heating to 110'C., the over-all heat transfer oo-effleient is assumed to be too low to utilize the 100% capacity of the boiler. A value of 15OO for UA with an average ^ T of 144F. indicates that the useable steam is 2P2,000 BTU/hr. or 226 lbs./hr. steam at 80 pslg. In the second oase the ^ T is lower and the entire output Of the boiler la useable. Table II sums up the approximate time calculated to heat Aroelor 125*. 0237238 | TOWOLDMON0027468 WATER_PCB-00011937 I n i] TABLE II Mine HP Boiler c Lbs. Steam/Hr 30-110*C. 30-75C p1; 100 cap.(no reused condensate) 263 75# cap.(no reused condensate) -- -- 9 Hrs 18 hrs.(86^cap) 12 Hrs 11 lOOJf cap.(condensate 8 200*P.) 296 -- 8 Hrs 75% cap.(oondensate 9 200P.j -- 18 hrs.(76oap] 11 Hrs 1. Calculations on a five horse power boiler give heating times of the c following order: {; Five HP Boiler (r; Lbs.Steamer. 100$ cap.(no reused condensate) 1*6 30-110'C. 28 hrs. 30-75c 16 hrs r 100% cap.(condensate 9 200*F.) 16* 25 hrs. 1* hrs Aroelor oars ean be heated by steam (80-100 pslg) to the proper handling temperatures in a reasonable time by using a boiler source capable of producing 200,000 to 300,000 BTB/hr. The times given here are approximate and will act as a guide until experience shows the exact time for this operation. 0237Z3` TOWOLDMON0027469 WATER PCB-00011938 The proper handling temperature for the various fluids Is given In the following Table III, which Indicates cor responding viscosity valueB: TABLE III Product Handling and Pumping Temperature C Approximate Viscosity, S.l Aroclor 1260 Aroclor 1254 Aroclor 1248 Aroclor 1242 Pyranol 1481 Pyranol 1467 Pyranol 1470 95 - 130 75 - 110 50 - 85 35 - 75 30 - 75 20 - 55* 15 - 45* 100 - 43 100 - 42 100 - 40 100 - 40 100 - 40 100 - 40 100 - 40 *lf any of the scavenger Is out of solution, then the material must be heated at 70C. (158 F.) until It has dissolved. Selection of pumping temperatures for any dielectric not shown on this list or Mhlch may be developed In the future should be based on a viscosity of about 100 Saybolt universal Seconds for average pumping and about 40 S.U.S, for fast pumping. When the material has been heated to pumping temperature, a one-half inch diameter pipe "oross" arrangement containing a pressure gauge/ air Inlet, pressure relief valve to relieve at 30 PSIO, and vent connections, should be connected to the dome air Inlet pipe. Then the unloading line should be connected. 9 0237240 | TOWOLDMON0027470 WATER_PCB-00011939 (At this point a sample Is taken as described In Chapter 4,) Dry* air Is then Introduced Into the tankcar and pressure built up to 15 pounds gauge. The two Inch valve cook on the stand pipe Is opened and the discharge pipe observed to be sure the liquid Is being uftloaded, To protect the seams In the tankcar, the pressure oust not exceed 30 pounds. The car will begin to unload at about 12 pounds pressure. When the car Is empty, the air pressure will drop off rapidly and air will blow out of the vent on the receiving tank. The air flow may be stopped at this point and the tankcar pres sure released through the vent valve on the .Across" arrange ment. After Inspecting the car to be sure that It haB been completely unloaded, all connections and dome cover should be closed tightly. It Is essential that the empty tankcar be sealed Immediately after the oar Is unloaded In order to keep the oar filled with dry air during return shipment. As a final *It is essential that the displacement air used for unloading be dried thoroughly by Borne dehumldlfylng unit suoh as soda lime, activated alumina or similar dehydrating agent drying unit. It may be necessary to recharge the dehumldlfylng unit each time that a car Is unloaded. Por unloading a tankcar of ArocJor within three hours, 15 standard oublc feet a minute of air at 15 pounds per square inoh gauge pressure '-arta -10P, dew point should be supplied. If the dry air unit Is to be used only for unloading tankcars, a small single tower dryer unit containing a self-contained reactivating heater Is suggested. Two manufacturers of air dryers of this type are: C. M. Kemp Mfg. Co., 405 E. Oliver Street, Baltimore 2, Maryland and Pittsburgh Lectrodryer Corporation, Poot of 32nd Street, Pittsburgh, Pennsylvania. 10 TOWOLDMON0027471 WATEFLPCB-00011940 step, it Is desired that a standard railroad wire seal be in serted through the slotted bolts of the car fittings. Steam should be released from the car colls and all oondensate re moved from the ooils by blowing with air with the steam trap by passed. All connections must be replaced as received. Adequate care should be taken in preparing and sealing the car for return shipment. Unloading with dry air as described la the preferred and recommended procedure because it is done with the car dome closed which avoids contamination. If the oar is unloaded by pumping out of the top, which required opening the dome, it is most desirable that the car be Bet inside of a building. If this cannot be done, then, a canopy or roof should be provided over the oar dome, and the unloading should be done when the weather is clear. A centrifugal pump with minimum capacity of 40 gpm. is suggested. It will be necessary to prime the pump and only clean Askarel should be used to do this. Another method for priming the pump Is to use a Penberthy steam Jet, No. 22A available from Penberthy Injector Co., 1242 Holden Ave., Detroit 2, Michigan. If a flexible unloading line lsxsed, it Bhould be a flexible metallic hose. Rubber hose must not be used. 11 02372*2 I TOWOLDMON0027472 WATER_PCB-00011941 C, Drum Packaging ' Drum packaging la made with new and carefully inspected 55-gallon drums. These steel drums are lined with a specially selected baked phenolic coating. An example is NESCO No. 3 lining offered by the National Enameling and Stamping Company, Long Island, New York. Contents of the drums should not be heated by dlreot application of flame or strip heaters. Radiant heat from steam colls or hot air in a heated room is to be pre ferred. The screw plug in the drum head is fitted with a metal cap as a safe guard against tampering. 0237243 IS TOWOLDMON0027473 WATER_PCB-00011942 CHAPTER 2 STORAGE TANKS A. General Description The storage tanks should be a minimum of 10,000 gallons and preferably 12,000 to 15,000 gallons capacity to accommodate the normal 8,000 gallon tankoars. It Is preferable to looate the tanks above ground where they are easily accessible for any changes or repairs. Under ground location presents difficulty In this respect. Especially In cold climates. It Is preferable to locate the tanks Inside of a building. The tanks should be located conveniently with reference to the tankcar unloading facilities and the area where the dielectric Is used. Although Aroclors are non-oorroslve to metals, corrosion or rusting of Iron and steel equipment (by oxidation) may occur resulting In contamination of the products. The resis tance of Aroclors to materials of construction is given In Monsanto Technical Bulletlon O-P-115, entitled, "The Aroclors," Page 6. Stainless steel tanks are very satisfactory but relatively expensive. Stainless steel pipe is relatively difficult to fabricate and It Is dlffloult to make tight leak-proof connec tions . Storage tanks may be of steel construction If properly metallised with zlnc-tln or aluminum on the Interior surfaces 13 . TOWOLDMON0027474 WATER_PCB-00011943 coming In contact with the Aroclors. The metallizing should be done according to the following procedure: 1. Clean an area of the surface by sand blasting, or a similar method, to give a perfectly clean and roughened surface. The area cleaned should not be greater than oan be completely metallized within a few hours after oleanlng. 2. If zlno-tln metallizing Is used, a coating of zinc 0.005 Inches thick should be sprayed on to the cleaned surfaoe. This Is followed Immediately by a ooatlng of tin 0,007 inches thick. 3. Aluminum metallized surfacing should be about 0.01 Inch thick. The detailed procedure for metallizing and cleaning is outlined as follows: a) Sand blaBt. b) Coat with Iron, 0.005 IncheB thick, (The purpose of this coating Is to provide a rougher and better bond for the finish coat of aluminum or the zlnc-tln combination.) o) Apply the selected finish coat, d) Pill the tank with tap water and warm It with steam, (if an open steam line Is used, do not allow the steam to Impinge directly onto the metallized surfaoe of the tank.) e) Drain the tank, f) Pill with oold water and<*>8In. g) Wipe dry with clean diaper cloth or other fabric relatively free of lint, h) Heat the tank to at least 100C. (212F.) to expell moist air. It would be beneficial to heat the tank, allow It to cool and pull dry air through it using a dehumldlfylng breather in the air line, heat again etc. until the tank Is full of comparatively dry air. 1) Spray about 100 gallons of new, electrloal grade Aroclor (not high 14 OZW'* j TOWOLDMON0027475 WATER_PCB-00011944 In vlsooslty) or eleotrloal grad trlehlorobenzene onto the Inner walls of the tank, washing the walls thoroughly (avoid breathing any fumes). J) Attach the circulating pump, the lines used, and the filter press fitted with dry paper and oiroulate the fluid through the system and the tank. Install new dry filter paper Beveral times In the press during this dry ing and cleaning operation. Slsoard the dielectric fluid used for cleaning, k) Partially fill the tank with new Aroclor dielectric and analyze It electrically and ohemlcally to de termine whether It meets specifications. If all tests are met, then fill the tank with the dlelectrlo. The tanks should be Insulated using, preferably^- glass foam beads as supplied by Dow-Cornlng or Libby-OwenB-Ford. Ihe suggested thickness of the glass Insulation Is one Inch mini mum to two inches maximum. The glass Insulation may be covered with tar material commonly used for weatherproofing. Another type of Insulation which may be used Instead of the glass Is 85$ Magnesia-Wool which should be covered also with the weather proofing tar. The advantage of the glass Insulation Is that It Is not moisture sensitive as 1b the case with Magnesia-Wool. If the Btorage tank is located outdoors, it 1b best that the Insulation be covered with riveted or bolted tin sheeting painted with aluminum paint. This type of metal surfaoe weathers well and Is cleaned easily. All piping must be gal vanized and screwed fittings must be back brazed to assure 15 023724b TOWOLDMON0027476 WATER_PCB-00011945 tightness. All handling pipe lines oust be traced with steam lines and Insulation applied over the two lines in order to keep the handling lines and the material up to the desired pumping temperature. Usually a one-fourth Inch copper steam line running parallel with the handling line will suffice. Under very severe conditions of low temperatures, it would be desirable to wind the steam line around the handling line about two turns to the foot. The tanks must be provided with ample pressurized heating coll butface to supply sufficient heat to the material to bring It to the proper temperature for pumping and handling as Indi cated In Table III, Heating colls should be either metallized Bteel, or preferably steel colls which have been galvanized after fabrication. It Is recommended that the steam pressure on all heating colls should not exceed 100 pounds per square Inch gauge; lower pressures may be used where practicable. It Is essential that all steam colls be completely free from even minute leaks since this will Introduce water Into the product. The steam colls may be Introduced as "halr-pln" colls through a manhole at the side and bottom of the tank, or as la most often done. Inserted through the manhole at the top of the tankr.and then located near the bottom. External heating colls located In the Jacket of the tank may be used but this construction Is more expensive and less efficient than the Internal colls. 16 ' 023724 7 TOWOLDMON0027477 WATER PCB-00011946 The storage tanks may be fitted with a stirrer, either through the top, side, or bottom of the tank and the propeller blade should be located near the bottom of the tank. However, Insertion of a stirrer through the side offers possible source of a leak and since these materials are homogeneous. It Is not essential to provide suoh agitation for the purpose of mixing. Adequate circulation can also be accomplished by using a centrifugal type pump. Gear pumps or other equipment where wear or chipping of metal parts may Introduce contamination should not be used. The pumps must be of the type designed to handle hot oil. All wetted pump parts should be either stainless steel or bronze. The centrifugal pumps must be provided with a deep stuffing box and proper packing used, as described In Chapter 3. As examples of pumpB found com pletely satisfactory for this Bervlce, reference Is made to Worthington Worthlte pumps. Blackmer pumps, and Dayton Dowd Type C pumpe for handling hot oil. Also, a very satisfactory arrangement for mixing or circulating and pumping the fluid from the storage tank Is to use a vertloal sump pump such as a Taber pump. All storage tanks must be amply provided with a dehumldlfylng breather such as soda lime, activated Alumina, etc., units. This Is essential to prevent moist air from coming In oontaot with the dielectric. A moisture oontent above 35 ppm 17 ozm*8 TOWOLDMON0027478 WATER_PCB-00011947 adversely affects the electrical resistivity of these pro ducts. Provision should be made to preolude possible leakage 00 the drier material baok Into the storage tank and the drier should be Inspected periodically to make Bure that It is open and not plugged. B. Detailed Description Drawing Ho. 9C-8170 shows the detailed construction of a horizontal 15,000 gallon storage tank for Aroclor and Its mixtures Whloh has been found completely satisfactory. The various nozzles on this tank are used as follows, con sidering them In order from left to right on-the drawing: 3" nozzle 24" nozzle 3" nozzle 36" manhole 3" nozzle 24" nozzle Inlet for reclroulatlon Por future agitator If required (not used) For soda lime or calcium ohlorlde breather connection For Inspection, etc. lhe float gauge Is located In the center of this manhole. Not used. For future agitator If required (not used) 3" nozzle 3" nozzle 18" X 26" Oval Nozzle Not used Filling Inlet connection For sump pump 3" nozzle For thermometer well (see detail) The two 24" nozzles were originally Installed for Installa tion of agitators, if required. However, It has been found 18 . 0237249 TOWOLDMON0027479 WATER_PCB-00011948 unnecessary to use agitators In the storage tanks, and these nozzles oould be omitted. It has been found that circulation of the fluid by the sump pump, and Into the noszls at the opposite end of the tank, for several hours gives satisfactory blending of the tank contents. For pumping the dielectric from the storage tank, a "Taber Tump Co. all bronze 2-1/8" X 2" vertical Bump pump with monel shaft has been found to be cults satslfactory for the applica tion. The liquid level gauge used in the storage must be gastight. The storage tanks are equipped with Vapor Recovery Systems Co.'s "Varec," gas-tight, automatic tank gauge as shown by Drawing No. 90-8278. The storage tanks should be provided with an operating plat form suitable to the customer's conditions of operation. The dehumldlfylng units used as breathers on the storage tanks can be constructed as shown by Drawing NO. 9C-8248. The upper portion of the chamber Is oharged with anhydrous soda lime or another drying agent. Periodic Inspection of the drying agent will show the formation of a cake of damp material on top about 1 to 1-1/2 Inches deep. This cake should be removed and freBh material recharged. Any suitable con struction similar to that shown on Drawing No. 90-8248 may be used for the breather units. Drawing No. D-13362 shows design detail of a 15,000 gallon 19 ' 0237250 | TOWOLDMON0027480 WATER_PCB-00011949 vertical storage tank. The vertical type tank Mould seem especially desirable When Insufficient space is available to accommodate the horizontal type tank. 20 oz*1**' TOWOLDMON0027481 WATER_PCB-00011950 CHAPTER 3 OASKETINQ AND POMP PACKING Aroolors and their mixtures soften and swell natural rubber and many of the synthetic "rubber" materials. Such material not recommended for use. Include Hycar P, Koroseal, Perbunan, Neoprene, etc. These materials are known sources of contami nation. Suggested types of packing and gasketing materials lnolude: 1. For Welded Flanged Pipe Connections: Oarlock Packing Co., No. 901 or No, 7021, 1/8 Inch asbestos fiber sheet. A ring of thin aluminum drawn tightly at the flange connections may be used satisfactorily also. 2. For Pumps: Oarlock No. 234, No. 431, and Cheveron No. 7050-C are satisfactory packings. Likewise, Durametalllc1s spiral asbestos fiber may be used, Johns-Manvllle and others have comparable packing materials. 3. For Valves: Oarlock No. 117 braided packing or Its equivalent Is suggested. 4. Other Resistant Materials: It is Indicated that duPont's Teflon, poly tetrafluoroethylene Is not attacked by hot (130C.) Aroclor and Is to be reoomrnended as a gasket material. Dow-Cornlng'B Silastic, Sllloone l80. Is very resistant to Aroclor and Is suggested for gasket purposes. 5. In some cases cork impregnated tinder pressure with Chrysler's Cycloweld 55-9 or Armstrong Cork Co.'s 1162-J and oured at 170C. may be used as a gasket material. These are baked phenolic type ooatlngs. 6. Pipe Thread Compounds: When neoessary to use pipe thread compounds, the following should be satisfac tory If care Is taken to prevent the pipe oompound from getting on the inside of the pipe. (a) Plastic Lead Seal--manufactured by Dura metalllc Corp. (b) Ordinary white lead 21 0 TOWOLDMON0027482 WATER_PCB-00011951 Usually It Is not neoessary to use pipe thread com pounds since all sorewed pipe fittings should be sealed by back brazing. 7. All new lines and fittings Bhould be cleaned thoroughly by steaming (for two hours) and dried with air or heat. 0237253 TOWOLDMON0027483 WATER_PCB-00011952 CHAPTER 4 SAMPLING METHODS 1.) The ASTM Standard Method for sampling electrical Insulating oils 1b described In ASTM Designation: D923-49. This describes glass and metal thlefs for sampling drums, cans, and tankcars. A specially designed thief or bomb for sampling tankcars Is described, also. A very good Instrument of this type Is the stainless-steel Baoon Bomb Thief with which samples of the liquid can be drawn from any level of the tankcar. The ASTM procedure describes sample containers, their cleaning and storage. Under general precautions,.the ASTM mentions that, "Samples of the fluid shall not be taken until the oil Is at least as warm as the surrounding air, because cold oil may condense enough moisture from a humid atmosphere to affect seriously Its Insulation properties, (in the case of tankcar lots, on some occasions there may be no choice, as It may be neoessary to procure samples from a tankcar when the temperature Is not above the surrounding air. On such occasions, the temperature of oil and air, also the humidity If possible, should be noted In the report of test results.) It Is unde sirable to do any sampling when the relative humidity of the atmosphere exceeds 75 percent, and samples shall never be taken In the rain." 23 0237254 TOWOLDMON0027484 WATER_PCB-00011953 At the plants of several eleotrloal manufacturers using Aroelor dleleotrlcs, the practice Is to swltoh the tankcars dlreotly Into the plant building or under roof before sampling and unloading. These precautions In handling are taken to avoid any contamination of the fluids which are manufactured under very strict specifications. For example, the specification for lonlzable ohlorldes allows no more than 0.10 parts per million. Moisture may not exceed 30 to 35 parts per million. Tankcars are cleaned and prepared under close inspection before they are filled. When filled, and analysis Bhows the material In the car to be satisfactory, the oar is then sealed with a standard railroad wire and seal Inserted through the slots of the dome fittings. Likewise, after the tankcars have been unloaded In the Industry, It Is requested that the domefittings should be sealed with a railroad wire and seal. 2.) Monsanto Methods used for sampling tankcars differ somewhat from the ASTM procedure. The modified techniques are used because of thftlr greater simplicity and they have been entirely satisfactory as employed over many years. A sample Is never taken When It la raining or snowing or when there Is any ehanoe of contaminated atmosphere moving In the direction of the oar. However, In oase of an emergency, during inolement weather, a canopy Is placed over the car dome before sampling. 24 02**'* TOWOLDMON0027485 WATER_PCB-00011954 [ r li A satisfactory sample bottle is a five pint, round amber glass, paoker type container fitted with a 33 millimeter Bake- llte sorew oap with an aluminum or tin oup liner. Bottles of this description oan be purohased from the Northwestern Bottle Company, 3144 North Broadway, St. Iiouls, Missouri aooordlng to their No. A-7253. Only new bottles and oaps are used. When a shipment of bottles Is reoelved, the bottles are capped Immediately and stored In their receiving oartons. prior to use, the exterior of the bottles Is wiped with a dean cloth. The simplest sampling devloe used is a clean stainless Bteel or aluminum dipper. However, this Is not a generally preferred devloe because It permits sampling the oar from the near surfaoe, only. The sampling devloe commonly used consists of a Btalnless steel tube, seven feet long with one end bent into a hook, to serve as a handle and on the other end there Is a stainless steel buoket with a perforated bottom. This bucket Is about 3-1/4 Inches Inside diameter and 6 inches deep to hold the i five pint bottle. This bottle Is held firmly by a stainless steel oollar made to slide along the shaft of the sampling devloe. This oollar has a damp attachment for fixing it tightly Into place where desired around the neck of the bottle. When a oar Is to be sampled, a new sample bottle Is damped firmly In the buoket. All dirt Is brushed and wiped away from the oar dome area using a dean rag. _25- 0237*56 TOWOLDMON0027486 WATER_PCB-00011955 me car dome la opened and the cap Is then removed from the sample bottle. The sampling device la Inserted Into the oar so that the neck of the bottle Is at least twelve to eighteen inches below the surfaoe of the fluid. The Bample taken Is dis carded sb Its purpose Is to rinse the bottle. A portion of the sample Is used to rinse the Interior of the bottle oap. This procedure Is repeated until a minimum of three rinses has been made; eaoh time the sample"taken Is not put back into the oar. These rinses should be discarded. Then the sample Is taken and the oap of the bottle Is screwed down tightly. When the sample has been obtained, the car dome lsrreplaced. Immediately. The exterior of the sample bottle Is wiped with a clean cloth and when returned to the laboratory It Is further clean ed with a cloth dampened with pure trlohlorobenzene. If the sample Is to be shipped, the cap Is taped with Scotch Tape, The sampling devloe Is also oleaned with pure trichloro benzene and Is stored In a dust free, air oondltloned>room. ' 3.) Drum Sampling. A glass thief, thoroughly cleaned with pure trlohlorobenzene and dried Is used to sample drums. 26 0237257 TOWOLDMON0027487 WATER_PCB-00011956 CHAPTER 5 LABORATORY ANALYSIS AND PROCEDURE FOR TREATING AROCLORS AND THEIR MIXTURES WITH EARTH A sample of the Aroolor or Aroelor mixture taken from the tankcar, or drums, as described In Chapter 4, Is analyzed In the laboratory to determine Its quality In aceordanoe with the property values given in Chapter 7. For eapaoltor use, usually the Important properties tested are resistivity, power factor, chlorides, and moisture. For transformer use dielectric strength, resistivity, moisture, and ohlorldes are the Important properties. If the sample Is out of line with the shipping specifica tions, It Is Indicated that the sample has become contaminated. In this case, another sample Is to be taken and the properties redetermined. If still out of speciflcatlons, the sample should be given treatment with earth. Treatment of the dielectric with conditioned Attapulgus earth will bring the electrical properties to the maximum attainable values. While there Is complete agreement on the benefits derived from treating with conditioned earth, there Is difference of opinion on details of the method, arising from factors such as the following. Ho doubt, there are differences In the absorbent power of various types of dlatomaoeous earth with respect to removing moisture. Impurities and additives such as stabilizers or scavengers from the dlelectrlo 27 0237258 TOWOLDMON0027488 WATER_PCB-00011957 materials. The size of the earth particles, temperature and conditions of activation of the earth, the concentrations used and the temperature, the degree of agitation and time interval at which the dielectric Is given earth treatment are all possible variables which are still being studied m various laboratories. The method used by Monsanto for treating the fluid with activated earth In the laboratory lss The absorbent Is minus 200 mesh Attapulgus* earth ac tivated Just prior to use by heating In shallow trays for four hours at 400OC. (752P.) or for at least twelve hours at 250OC. (482f.). At least one quart of the dielectric sample Is placed Into a clean two liter Pyrex beaker or three necked flask. The beaker or flask should be cleaned Just prior to use In a manner similar to the procedure described In Chapter 6, Method No. 11,751 "Procedure for Cleaning of Electrodes, o.E. Cell and Accessories". The flask or beaker Is fitted with a glass or stainless steel agitator. Heat la applied using either a hot plate or a Qlaa-Col mantle and Is controlled by a thermostat such as a Penwal thermo switch with a stainless steel sheath. About 0.1 to 0.2$ of the activated earth, based on the weight)Of'the liquid Is added. Attapulgus Division, Minerals & Chemicals Corp. of America, 210 West Washington Square, Philadelphia 5, Pennsylvania TOWOLDMON0027489 WATER_PCB-00011958 The mope viscous dielectrics such as Aroclors 1248 and 1254 are heated at about 70 to 80C. (158 - 176F.) and the less v1boou8 materials suoh as Aroelor 1242 and Pyranols 1481, 1467, and 1470 are heated at about 50 to 60 c. (122 to l4op.). After heating and stirring the sample for about four hours. It Is filtered using a clean Pyrex glass suotlon flask and a buohner funnel fitted with a Whatman No. 1 or No. 3 filter paper. This apparatus and the bottle Into which the treated sample of dielectric Is transferred should have been cleaned In a manner similar to the cleaning procedure de scribed In Chapter 6. The earth treated and "up-graded" sample Is then ready for final analysis of Its electrical properties. 29 0237260 TOWOLDMON0027490 WATER_PCB-00011959 CHAPTER 6 TEST PROCEDURES A. general Information The Monsanto test methods described here with the special equipment used are some of the control tests employed to main tain the quAllty of Aroolors for dielectric use. They are suggested as a guide for test work needed to Indicate the quality of the dielectrics used In the manufacture of electrical goods. The most significant electrloal tests made on Aroclors for capacitors are: 1. Dleleotrlc constant. 2. Power Factor. 3. Resistivity. For transformer use the most significant tests of Aroolor mixtures are: 1. Dleleotrlc Strength. 2i Resistivity. In both cases a significant chemical test Is corrosion chlorides. The following terms are defined: Dleleotrlc Constant: The dielectric constant (sometimes called specific Induc tive capacity) of any substance Is equal to the ratio of the capacitance of a oondenser when that substance Is used as the 30 . 0237261 TOWOLDMON0027491 WATER_PCB-00011960 dielectric to the oapacltance when there la a vacuum between the oonduotors (for all practical purposes alr -at ordinarypressures may be used Instead of a vacuum). Dielectric Strength; Dleleotrle Strength Is the rupturing strength of an Insulating material when subjected to voltage stress under specific conditions and expressed In kilovolts. Breakdown varies with the shape of the electrodes and does not increase directly In proportion to the thlokness of the dielectric. Power Factor; The power faotor of a dielectric Is the ratio of the ener gy loss In the dielectric to the "apparent power" In the di electric . Resistivity: Resistivity Is eleotrloal resistance offered to the pas sage of a steady current. The volume resistivity In ohmscentlmeter of an oil 1b the ratio of the d-c potential gradient In volts per centimeter paralleling the current flow within the sample, to the current density In amperes per square centimeter at a given Instant of time and under prescribed conditions. Volume resistivity Is expressed In ohm-om. The analytical procedures described In detail include: 1. METHOD NO. 11,751, "PROCEDURE FOR CLEANINO OP ELECTRODES, O.E. CELS AND ACCESSORIES." 2. METHOD NO. 11,608, "DIELECTRIC CONSTANT AND POWER FACTOR." 31 0237262 TOWOLDMON0027492 WATER_PCB-00011961 3. METHOD NO. 11,605. "DIELECTRIC STRENOTH." 4. METHOD NO. 11,607, "RESISTIVITY." 5. METHOD NO. 10,126, "CORROSION AND CHEMICAL STABILITY." 6. METHOD NO. 10,118, "INOROANIC CHLORIDES." 7. METHOD NO. 10,087, "ACID NUMBER." 8. METHOD (MODIFIED) NO. 10,620, "MOISTURE (WATER)." Detailed Instruction and Testing Methods. 1. METHOD NO. 11,751, "PROCEDURE FOR CLEANING OF ELEC TRODES, G.E. Cell and Accessories. a. The Electrode Cleaning Procedure: 1) Place the electrodes In hot electrical grade Trichlorobenzene for ten minutes. 2) Wash with unheated TCB. 3) Rinse twice with methanol and twice with tap water. 4) Place the electrodes in hot 10% Tri Sodium Phosphate solution. Soak and heat for ten minutes. 5) Wash thoroughly withttap water. CAUTION: After Step 5-- DO NOT TOUCH THE ELECTRODES WITH HANDS! 6) Wash with distilled water twice. 7) Dry in drying oven for at least two hours at 120C. b. The G.E. Cell Cleaning: 1) Reolean the cell before use, when more than 8 hours have elapsed since the previous cleaning. 2) Follow the procedure for the electrodes starting at Step 4. 32 . TOWOLDMON0027493 WATER_PCB-00011962 0. Cleaning of the Accessories: 1) Apply the same cleaning procedure as given for the Electrodes (Steps 1 to 7) to prepare the glass spacer and beaker for next test. 2) Clean the thermometer In the same manner as the electrodes, except for Step 7. 3) Plaoe the wet thermometer (after Step 6) directly in position in the temperature Heating Unit (Modified Fisher Isotemp Oven) and allow to dry. METHOD NO. 11,608. "DIELECTRIC CONSTANT AND POWER FACTOR." 1, Apparatus A. Oscilloscope: Heathkit Model 0-6, B. Constant Temperature Heating Unit: Fisher Isotemp oven. Model 13-245A, modified to include inter wall connectors. C. A. C. Generator: General Radio type 1302-A. D. Amplifier and Null Detector: General Radio type 1231-B with type 1261-A power supply. E. Capacitance Bridge: General Radio Co. Capacitance Bridge type 716-C. F. Test Cells: G.E. type, concentric cylinder eleotrodes Catalog #1,559,6(53, G. Class B driver transformer: This is used for 60 cycle measurements to excite the bridge directly from the domestic power line. It has 50 volts output with a 4800 ohm resistor in service. H. Tuned Circuit Filters: General Radio Type 1231-P2 (400 and 1000 cycle) and 1231-P3 (60 cycle). These filters aid in obtaining a more accurate frequency for the measurements by removing harmonics, noise, hum, etc. 33 *6, | TOWOLDMON0027494 WATER_PCB-00011963 II Adjustment of Controls on Electrical Apparatus A. On Panel No. 1 (Top Panel, Amplifier and Null Detector) a. Turn the 4-way (main power) switch on the upper right hand side to the #3 position to determine the Dielectric Constant at 1000 cycles. Turn this switch to the #2 position for measurements bo oyolis. b. Allow the equipment to warm up 10 minutes. c. Turn "GAIN CONTROL" to 6. d. Depress "INPUT 0.03V." button. B. On Panel No. 2 (Oscilloscope) a. Turn "INTEN." to about the 12 o'clock position. CAUTION: Do not allow a high Intensity spot to remain stationary on the screen for any length of time. b. Using "HOR. POSITION" and "VERT. POSITION" controls center the Image on the screen. c. Adjust "FOCUS" for sharp line. d. Turn "FREQ. SELECTOR" to LOOKC. e. Turn "FREQ. VERNIER" to 80. f. Turn "VERTICAL GAIN" to 5. g. Turn "VERTICAL INPUT" tt> "10 VOLT MAX.". h. Turn "HORIZONTAL GAIN" to about 20. 1. Turn "SYNCHRONIZING" to + 20. J. Turn "SYN." to "EXT. SYN." k. Turn "GEN." to "SWEEP GEN." 3^ 0237265 TOWOLDMON0027495 WATER_PCB-00011964 C. On Panel No. 3 (Capacitance Bridge) a. Turn "RANGE SELECTOR" switch to "100 C" for 60 cycle measurements and to "1 Kc" for 1000 cycle measurements. b. Turn "METHOD SWITCH" to direct. c. Turn "DISSIPATION FACTOR" selector switch to "0". D. On Panel No. 4 (oscillator) a. Disregard this panel for measurements at 60 cycles. b. On 1000 cycle measurements, depress the No. 10 "MULTIPLY BY" button. 8. Set "FREQUENCY DIAL" to 100. d. Turn "OUTPUT" dial so that pointer is at the end of the arrow. e. Depress the "UNBAL. 5000 OHMS" button. When all of the above adjustments are made, the electrical apparatus is ready for measurement of Dielectric Constant and Power Faotor. III. Determination of Constants for the Apparatus 1. Carefully assemble the cell which has been cleaned and dried within the last 8 hours. Refer to Method No. 11,751 for the procedure to use In cleaning the cells. 2. Place the cell assembly in the Fisher oven which has been adjusted to 25C. 3. Connect the back wire inside the oven to the lead on the inner cylinder of the cell and the front wire to the lead on the outer cylinder of the cell. 35 023*M' | TOWOLDMON0027496 WATER_PCB-00011965 4. Connect the cable from the capacitance bridge to the terminals on top of the oven so that the inner wire of the cable goes to the back terminal ana the outside mesh casing of the cable "('the ground) goes to the front terminal. 5. Remove the thermometer from the top of the oven before going on with the test. fEi8~Ts"Tmportant. .6 Make all adjustments on the electrical apparatus as directed in Part I of this method. 7. Balance the bridge by rotating the "CAPACITANCE" and "DISSIPATION FACTOR" dials on Panel No. 3 until the wide vertical band on the oscilliscope is adjusted to a minimum width. .8 Record the sum of the readings on the "CAPACITANCE" dial and vernier and call this value A. 9. Remove the beaker containing the cell from the oven and fill it with C.P. benzene to a level O.737 Inches (ca.3/4 inch) above the top of the concentric cylinders of the cell. .10 Adjust the temperature of the benzene to 25C. while stirring with a thermometer. .11 Replace the cell in the oven (at 25C.) and make the same electrical connections as in Steps 3 and 4. DO NOT Interchange connections. 12'. Balance the bridge again as in Step 7. 13. Record the sum of the readings on the "CAPACITANCE" dial and vernier and call this value B. 14. Calculate the cell constant by the following equation: Cell Constant, K B - A (this is usually 2.27 a 1,0 around 70 mmfd.) 15. Remove the cell from the oven and balance the bridge as in Step 7 with the "CAPACITANCE" and "DISSIPATION" "FACTOR" dials. 3& 073??f,7 TOWOLDMONOQ27497 WATER_PCB-00011966 16. Record the sum of the readings on the "CAPACITANCE" dial and vernier>and call this value F. (capacitance of connecting cable.) " 17. Calculate the CELL LEAD CAPACITANCE by the following equation; CELL LEAD CAPACITANCE, 0 A - P - K (this is ~ usually around 3 mmfd.) WHERE: A = CAPACITANCE OP ENTIRE SYSTEM IN AIR (SYSTEM CONSTANT) 0 CAPACITANCE OP THE CELL LEADS (CELL LEAD CONSTANT) F CAPACITANCE OP CABLE AND WIRES WHICH CONNECT THE CELL AND CELL LEADS TO THE BRIDGE. (CONNECTOR CONSTANT) K . CAPACITANCE OF THE CELL ALONE (THE CELL CONSTANT) Tabulate the system Constant (a), the Cell Lead Con stant (g), the Connector Constant (f), and the Cell Constant (K) on a piece of stiff paper and post them near the instrument where they can be easilyvreferred to for comparison and calculations. These constants must be checked at least once every three months and in all cases where the Dielectric Constant and/or Power Factor are out of specification. Measurement of Dielectric Constant and Power Factor on Aroc lora,, ^yrano'ls, Inerteens, and Trl-Tetrachlorobenzene Blends. A. Test Run on Cell to Determine whether it is Clean and properly Aligned. ' '' ' 1. Carefully assemble a cell which haB been cleaned and dried within the past 8 hours. 36a 02372b8 TOWOLDMON0027498 WATER_PCB-00011967 NOTE: Refer to method No. 11,751 for procedure to use in cleaning cells. 2. Adjust the oven control to hold at a temperature of 100C. for all materials except Tri-Tetra Blends. If a Tri-Tetra blend is to be tested, adjust the oven to hold a temperature of 250. 3. Place the empty cell assembly in the oven and connect the back wire inside the oven to the lead on the inner cylinder of the cell, and connect the other (.front) wire to the lead on the outer cylinder. 4. Connect the cables from the capacitance bridge to the terminals on top of the oven so that the inner wire of the cable goes to the back terminal ancT the outside metal casing (ground)goeB to the front terminal. 5. Allow 15 minutes for the cell to reach temperature equilibrium inside the oven. 6. Remove the thermometer from the top of the oven before taking any measurements on the bridge. This is Important. 7. Make all the adjustments on the electrical apparatus as directed in Part I of this method. 8. Balance the bridge by rotating the "CAPACITANCE" and "DISSIPATION FACTOR" dials on Panel No. 3 until the wide vertical band on the osollloscope screen is adjusted to a minimum width. 9. Record the sum of the readings on the "CAPACITANCE" dial and vernier and compare this value with the SYSTEM CONSTANT determined in Part II of this method. IMPORTANT: If the value obtained in Step 9 does not agree with the System Constant A (Part II) within 5 uuf, the cell must be re-cleaned, re-dried, re-assembled, and the test run for the System Constant must be repeated. NOTE: Although the above test run must be made prior to each analysis, the value obtained in Step 9 is not to be used in calculations but is to be used only as a~5heok on the cleanliness and alignment of the cell. 37 0237769 TOWOLDMON0027499 WATER_PCB-00011968 B Procedure for Testing Materials 10. Remove the cell from the oven and fill the beaker with the material to be tested to a level 0.737 Inches (ca 3/4 Inch) above the cylinders of the cell. 11. Adjust the temperature of the sample to 100C. (use hot plate) for all materials except Trl-Tetra blends. For Trl-Tetra blends, adjust the tempera ture of the sample to 25C. using an Ice-water bath If neceBBary. NOTE; Stir sample continuously with a thermometer while adjusting the temperature. 12. Place the cell and sample In the oven and make the same connections from the cell to the bridge as In Steps 3 and 4. DO NOT Interchange connections. 13. Allow fifteen minutes for the oell to reach tempera ture equilibrium Inside the oven. 14. Remove thermometer from the oven before taking a measurement. This Is important. 15. Make the adjustment of controls on the electrical apparatus as directed In Part I of this method. 16. Balance the bridge by rotating the "CAPACITANCE" and "DISSIPATION FACTOR" dials on Panel No. 3 until the wide vertical band on the oscilloscope soreen 1b adjusted to a minimum width. 17. Reoord the sum of the readings on the "CAPACITANCE" dial and vernier, and call this value X. 18. Record the sum of the readings on the "DISSIPATION FACTOR" dial and switch, call this value D. Calculations: Dielectric Constant X-F-Q ------- K------- Where: X = Capacitance reading from Step 17. F m Connector Constant (Determined in Part II) 0 -Cell Lead Constant (Determined in Part II) K m Cell Constant (Determined In Part II) 38 11 02* TOWOLDMON0027500 WATER_PCB-00011969 When assembling this booklet, a mistake was noted in the num bering of the pages. No page of contents is missing. Only number 39 wee skipped. We are pleased to insert number 39 as a blank page for your conveni ence for notes, if you care to make any. TOWOLDMON0027501 WATER_PCB-00011970 % Power Factor f x D ~*b Where: f - Test Frequency (60 cycles or 1000 cycles) f0 Frequency of "Range Selector" on Panel No. 3 D Dissipation Factor reading from Step 18. NOTE: When D (dissipation factor) Is less than 0.1, the dissipation and power factors differ by less than 0.0005. Therefore, for our measurements, power factors and dissipation factors are equal. Precision: (Reference: General Radio Manual for Model 716-0 Capaoitance Bridge) a. Capacitance readings are precise to j 2 mmfd. x mul tiplier reading (i 0,2$G of full scale for each range) when the dissipation factor is less than 0.01. b. Dissipation Factor (Power Factor) readings are preoise to 0.0005 or + 2$6 of the dial reading which ever Is larger, for values less than 0.1 for D (Dissipation Factor). 3. METHOD NO. 11,605, "DIELECTRIC STRENGTH." a. Apparatus and General Information The electrical equipment necessary to provide high voltage to permit the determination of dielectric strength of liquid dielectric at commercial power frequencies is basically quite simple. The equipment assembled in the laboratory consists of a high voltage transformer of good design and with a ourrent eapaoity of 2.43 KVA and with equip ment for control Of the voltage and a means of measuring the voltage and to provide safety for the operator. 40 0237272 TOWOLDMON0027502 WATER_PCB-00011971 It is enclosed in a steel gray crackle finished cabinet measuring 42* high, 22" wide, 17" deep and set on truck casters for easy mobility. Protective equipment incorporated in this apparatus prevents the application of high voltage unless all safeguards are complied with. The door on rear of cabinet must be closed. The cover over the oil must be all the way down and the voltage control must be at 0 position. Failure to comply with these requirements will prevent any action when the red button is depressed. The teBt cue; Transformers, Voltmeters, and Accessorlee The askarel testing cup type No. 224809 supplied by General Electric Company is mounted on the top rear of the oabinet. It is protected by a heavy plastic cover, hinged at the rear for accessibility to the receptlcal. It is equipped with safety oontactor so placed that the circuit energizing the high voltage contactor cannot be completed unless the protective cover is completely lowered and in place. It is impossible for the operator or anyone else to touch the testing cup when high voltage is applied. TOWOLDMON0027503 WATER_PCB-00011972 The High Voltage Transformer manufactured by the Kelly-Koett Manufacturing Co. is of the closed core, oil Immersed, shell type design. Hated @ 81,000 volt @ 40 mlllaapers. It was recovered from a used X-ray machine, purchased quite Inexpensively. An auto transformer from the same X-ray machine is connected so as to limit the out-put voltage of the high voltage secondary to 50,000 volts. The primary of the auto transformer is connected to the secondary of a 2-1/2 KVA powerstat variable auto transformer supplied by the Superior Electric Company. Power to the powerstat Is controlled by a 4 con tact 30 amp. solenoid circuit breaker. The voltmeter mounted on top near front edge is connected across the powerstat secondary and is calibrated to read directly in Kilovolts in the range of 0 - 50 K.V. The overload circuit breaker consists of a small relay connected between one side of the high voltage transformer secondary center tap and 42 OZ3727'> TOWOLDMON0027504 WATER_PCB-00011973 ground. It is adjusted to break contact on a current drain of about 50 milliatnpers. The circuit for the coil of the solenoid circuit breaker is wired through the contacts of this relay. Safety and Operating Controls 1) Door interlock switch located on rear door. 2) Test cup cover interlock switch. 3) Powerstat switch mounted on rear of unit arranged so that high voltage contactor cannot be closed unless powerstat is at zero position. 4) Main power switch on front panel 5) Powerstat voltage control on front panel. 6) High voltage contactor push button on front panel (red). 7) Signal lamps mounted on top around voltmeter. Purpose and operation described in method of use. Procedure 1) Ascertain that the temperature of the material under test is 25 ( 0.5)C, NOTE; Testing at other temperature is likely to give variable results which may be misleading. 2) Shake the sample container so as to thoroughly mix the askarel before filling the test cup. NOTE; This operation is especially important with used Aroclor as the impurities may settle to the bottom and the test may be misleading. 3) Rinse the testing cup three times with small portions of the sample to be tested. 43 TOWOLDMON0027505 WATEFLPCB-00011974 4) Immediately after final rlnBe, fill the cup to a height of not leas than 20 mm. (0.787 in.) above the top of the electrodes. 5) Rock the cup a few times in order that any entrapped air may escape. Close cover over oil test cup. 6) Allow to stand 3 minutes. CAUTION: THIS IS IMPORTANT. 7) Turn main toggle switch on front panel to "ON" (or up) position. Both green and amber pilot lights on the top at either side of the voltmeter will now glow. NOTE: The green signal light is connected across the 115 volt in-put and denotes that line voltage has been applied to operating control circuit. Amber light is connected in series with sensitive switch located under high voltage contactors and connected to its armature. It indicates that high voltage contactor is In its rest position and away from oontaotB energizing auto transformer. 8) Turn voltage control (large knob on front) to extreme counter-clockwise position. 9) Depress red button on front. This energizeB high voltage transformer and circuit breaker and is indicated by amber light going out and the red light directly over voltmeter will llghT; 10) Vlatch the voltmeter and, while holding the button "IN", turn the voltage control at such speed that will cause voltage as Indicated on< voltmeter to 'rise at a fate of 3 K.V. per second. 11) Note and Record the voltmeter reading at breakdown. 44 U^3 ?27b TOWOLDMON0027506 WATER_PCB-00011975 12) Repeat the test until two successive break downs occur on each of two fillings of the test cup which do not differ by more than 10#. Report the average value of these two readings (Step 12) as the Dielectric Strength. If the limit of the instrument is reached before breakdown, report the Dielectric Strength as 50 K.V. at 25C. Cleaning of the test cup; After the test is completed, drain the oup. Plush the cup with benzene. Then fill with Aroolor 1248 and let Btand, until the next analysis. NOTE: An exception, when samples of oil from the plant are brought in for test, the cup must be thoroughly cleaned with benzene and carbon tetrachloride before and after running the test. The electrodes; The testing cup has two electrodes. Both electrodes are movable and have twenty threads to the inch with index notches on both the electrodes and the lock nuts. To set the Qap; Arrange one of the electrodes and the look nuts with the index marks in line. Move the other elec trode until it comes in firm contact with the first electrode and look it. 45 02 372 7 7 TOWOLDMON0027507 WATER PCB-00011976 Now unscrew the electrode with the Index marks In line (Step 1) two complete turns and lock It. This will leave a gap of 0.1 Inch between faoes of the electrodes. Cleaning of the electrodes and the test cup free of carbon coating: The following ASTM method of oleanlng Bhall be followed when It Is apparent from visual Inspec tion that the electrode discs of the cup are coated with carbon. Wipe clean with dry calendered tissue paper the electrodes and the test cup, CAPTION: It Is Important to avoid touching the electrodes with the finger or with portion of the tissue paper which has been In contact with handB. Rinse the electrodes and cup with dry lead-free gaso line, StodQaBS Solvent (or dry, waterwhite Kerosene) until they are entirely clean. Care should be taken not to touch the electrodes or the Inside of the cup after cleaning so as to avoid possible contamination. 46 023?278 | TOWOLDMON0027508 WATER_PCB-00011977 4. METHOD NO. 11,607, "RESISTIVITY. a. Apparatus: General Radio Company Megohm Bridge Type 544-B. This Is a combination of Wheatstone bridge and vacuum tube voltmeter for indicating null. The direct measurement of resistance up to 1,000,000 megohms is made possible by the use of a vacuum tube detector whloh absorbs negligible amount of power. The voltage applied to the unknown resistor is held approximately constant, regardless of the value of the unknown resistance. This condition is necessary to measure resistance properly. The accuracy of the instrument in the range en countered in the measurement of Aroclor resis tivity, 100 to 1000 megohm is 4 6%. The instrument is equipped with a 115 volt AC power supply which supplies all operating voltages for the bridge Indicating circuits and in addition supplies 500 V DC for application to the material under test. The instrument is completely enclosed in a waxed finish shielded oak cabinet measuring 8-1/2" wide, 22-1/2" long and 8" high. Approximate weight--26 pounds. 47 ' 07377 7b TOWOLDMON0027509 WATEFLPCB-00011978 Test Electrodes! Two concentric nickel cylinders with feet, obtained from General Electric Company. The Inner electrode has outside diameter of 2.8" and a height of 3.25" with area of 184 sq. om. The outer electrode has an Inside diameter of 3" and a height of 3.25" with area of 198 sq. cm. The distance between electrodes is, therefore, 0.1" or 0.254 cm. By theory, electrode constant (K) area/length is 191/0.254 or 752 where average area is 191 sq. cm. Also K 36 x 10" x C (farads with air as dielectric) or 11.29 x C (mmfd. with air as dielectric). Qlass Plate; Pyrex about 3-1/2" diameter with concentric grooves to assist in spacing electrodes. Obtained from General Electric Company. Heating Pnlt: Assembled in the laboratory and is the same unit described in Dielectric Constant Apparatus (see Method Mo. 11,608; Equipment). Procedure; 1) Assemble the test cell. Place the recently cleaned (within the last 8 hours--see Method No. 11,751, Step 9) electrodes in an 800 ml. beaker. 48 0231*80 | TOWOLDMON0027510 WATER_PCB-00011979 2) Measure the capacitance of the test cell (Cc) according to Method No. 11,608 (Dielectric Constant and Power Factor measurements.) 3) Fill the cell assembly until the liquid level is 3/4 inch above the top of the electrodes. 4) Heat the assembly on the hot plate to 100 ( 0.5)C. 5) Place the assembly Inside of the testing oven. 6) Attach top lead (+) on the megohm bridge to inner electrode. 7) Attach other lead to outer electrode. 8) Throw the three switches at the top of the megohm bridge to "ON" position. 9) Allow 10 minutes for assembly to reach temperature equilibrium inside the oven. DAMPER: Make sure control knob is in "CHECK" position. Otherwise, painful shock will result if leads are touched. 10) Bring the galvanometer pointer to zero by turn ing the "ZERO ADJUST" knob in the direction in which the pointer of the galvanometer should move. 11) Turn the control knob to "CHARGE" position for 30 seconds. 12) Turn the control knob to "OPERATE" position and return the galvanometer pointer to zero by ad justment of the "MULTIPLY BY" switch and the megohm dial. 13) Read after 30 seconds. Calculation: Resistivity* - Megohm dial reading (Step 12) x "Multiply By" reading (Step 11) x capacitance of cell (Step 2) in mmfd. x 11.29 x 0.001. 49 TOWOLDMON0027511 WATER_PCB-00011980 Report the result In units of 109 ohm-cm. Values of resistivity are qualified by designation of temperature and voltage. These are for this test, 100C and 500 volts DC. NOTE: It Is Important that the product under test, eleotrodes, and beaker be at uniform temperature for this determination. Temperature variations In different parts of the sample will cause the galva nometer zero to ohange constantly and give misleading resultB, CAPTION: Inasmuch as measurements must be made at a potential of 500 volts DC a shock hazard exists In the handling of this apparatus. With the control knob In the charge and operate position full voltage of the bridge (500 volts) is applied to the positive and low terminals and through the test leads to the electrodes. Do not attempt to handle the electrodes of the test leads unless the oontrol knob is In the "CHECK" position. Possible penalty for failure to observe this precaution -- Painful Shock. 5...METHOD NO. 10,126 "CORROSION AND CHEMICAL STABILITY." a. Apparatus: G.B. Corrosion Apparatus consists of the following: 1) A Corrosion Flask - It Is a 300-ral. Pyrex flask 50 OZ37282 TOWOLDMON0027512 WATER_PCB-00011981 with a ground glass 24/40 Joint equipped with a 12-inch straight tube as an air cooled con denser. The air-oondenser is painted on the outside with aluminum. 2) The Corrosion Apparatus; A transits box 32" long x 8" wide x 5" deep. The top of the box represents a split transite board with 5 holes cut to fit the flasks. The box is heated by two 500-watt, 15 volt O.E. Strip heaters with off-set terminals at one end (23.5" overall length). The heating length of the heating element is covered by a copper strip 19-1/2" long x 4" wide x 1/4" thick. The temperature is controlled by an automatic thermostat with temperature setting indicator. Procedure; 1) Roll a rectangular (2" x 4") piece of aluminum foil so that it will pass through a ground glass 24/40 Joint of the corrosion test flask. CAPTION: Be careful that after rolling the specimen does not touch Itself at any point. 2) Wash the aluminum foil (Step l) scrupulously with acetone, distilled water, acetone, benzene, and chloride-free ether. 3) Then place the foil on a clean watch-glass and dry in an oven at 110C. for 30 min. After cleaning handle the specimen with tongs or forceps only. 4) Weigh accurately on an analytical balance the specimen (Step 3) at room temperature. 5) Drop the weighed aluminum foil into the chloridefree corrosion flask of the "G.E. Corrosion Appa ratus." Rinse out flask with sample and rinse end of condenser with sample. 51 023T28I TOWOLDMON0027513 WATER_PCB-00011982 6) Add 200 ml. of the product under test to the aluminum foil (Step 4 and 5). 7) Set the corrosion flask In the corrosion test appa ratus. 8) Attach a 12-lnch straight-tube air-cooled condenser, the outside of which Is painted with aluminum. 9) Cover the exposed part of the flask with aluminum foil. 10) Heat the flask for 6 ( O.l) hours at 210 M 5) C. The temperature of the liquid In the test flask Is mea sured Indirectly using a thermometer Inserted through a cork stopper and Into similar liquid contained In an iden tical flask seated adjacent to the test flask on the heating chamber. 11) At the end of the heating period, detach condenser from the flask before removing It from the hot plate. 12) Remove the flask from the hot plate and cover all of the flaBk with aluminum foil (when the flask Is not on the hot plate.) 13) Without removing the aluminum foil covering of the flask, analyze the product (Step 6) remaining In the corrosion apparatus for: a) Appearance. Color, and Condition. b) Inorganic (Free) Chlorldes--Apply Method No. 10,118 e) Acidity (Acid Number) - Follow Method No. 10,087 14) With a pair of clean, straight nlchrome tongs, remove the aluminum foil specimen (Step 5), wash thoroughly, dry and weight accurately on an analytical balance In the same manner as before (Steps 2, 3 and 4). Report the corrosion as Iobs or gain In weight to the nearest 0.0001 g. end the Chemical Stability, as Indicated by the ana lysis of the products "After Corrosion Test". In the same way as reported for the original (as received) material. 51 A ozsrte* TOWOLDMON0027514 WATER_PCB-00011983 6. METHOD NO. 10,118, "INORGANIC CHLORIDES a. Preparation of Standards: 1) Make a primary standard of 100.0 ppm by weighing 0.1648 g. C.P. NaCl Into a chloride-free 1 liter volumetric flask. Dilute to the mark and mix thoroughly. Make a 10.0 ppm standard by diluting 100 ml. of the primary standard to 1 liter, and mixing well. For every 0.1 ppm standard, dilute to 10 ml. of the 10 ppm standard to one liter and mix well. A 0.1 ppm beam Is considered the very faintest beam perceptible to the eye between 15-45 seconds after adding the AgN0~ solution. If the beam Intensity is not vislble^at all, or If easily visible (too strong), discard the solutions and make new standards. 2) Weigh 20,0 g. C.P. AgN03 into a chloride free dark bottle. Add 20 ml. C.P. HNO- (chloride-free). Dilute to 200 ml. with water. 3) All solutions should be freshly prepared every two weeks and stored in glass-stoppered Pyrex bottles. b. Light Source: Employ the 2 battery Penlite flashlight, having a 3-4 mm. light aperture. New batteries must be used fre quently in order to perceive beams properly. c. Procedure: 1) Thoroughly rinse two separatory funnels with chloride-free water three or four times. Then take an aliquot from each funnel In a test tube which has been rinsed with chloride-free water. Test these aliquots for Tyndall beams by adding 3-5 drops of AgNOo and allowing 45 sec. for full beam to evolve. Absolutely no dust or chloride beam should be present, (if beam is present, rinse all equipment with 1:1 HNO3 and repeat Step 1). 2) When funnels are beam-free, drain out all the water exoept 50 ml. in one and 25 ml. in the other. Heat the water in both funnels to boiling. (Hold stopper while heating as steam may cause stopper to fail.) 52 02372`> TOWOLDMON0027515 WATER_PCB-00011984 3) Transfer 50 ml. of the sample from the sample bottle at a temperature of 95-100C. into the separatory funnel containing the 50 ml. of boiling water. (As a precautionary measure, pour some of the sample from the sample bottle into a waste beaker before adding the 50 ml. to the funnel.) 4) Stopper the funnel and Bhake vigorously for at least 1 minute, venting frequently through the stopcock. (Care must be exercised at all times to touch neither 'the lower part of the funnel stem not the ground part of the Btopcock.) 5) Allow the layerB to separate and drain off the sample into the second funnel containing the 25 ml. of boiling water. (As before, drain off a few ml. of the sample into a waste beaker before draining the sample into the second separatory funnel.) It may be necessary to heat the sample when transferring the sample to the second funnel; e.g., Aroclor 1260. 6) Repeat step 4 and allow the layers to separate. Then drain off the sample into a waste beaker. 7) Combine both water extracts in one funnel and shake thoroughly. 8) Take approximately a 10 ml. aliquot of the water extract out through the bottom of the funnel into a 3/4" x 6" test tube. Again, first allow a few ml. to drain out before taking the aliquot. (The test tube used should be rinsed with chloride-free water several times before using.) 9) Add approximately an equal portion of chloridefree ether. (The ether is tested by shaking a portion of it with chloride-free water and testing for Tyndall beam at the end of 45 sec. If beam is present, wash ether several times with chloridefree water until washings show no beam after adding 3-5 drops AgNOj). 10) Shake the ether-water mixture until the emulsion in the sample disappears and the water layer is completely beam free before adding AgNOo. If emulsion is difficult to break, add sample dropwise through the ether and then shake. 53 0/3726b I TOWOLDMON0027516 WATER_PCB-00011985 11) Add 3-5 drops of 10}8 AgNOg solution and test for chloride beam for 45 sec. exactly. If no beam Is present at the end of 45 seconds, report as ^p.l ppm. The very faintest of beams Is considered 0.1 ppm. If beam is stronger It will be necessary to compare with standards of 0.15, 0.20 up to 1.0 ppm, adding the 3-5 drops of AgNOg and comparing at the end of 45 sec, The method Is precise to the nearest 0.1 ppm. Report results to the nearest 0.1 ppm. METHOD NO. 10,087, "ACID NUMBER." a. Reagents: 1) Nitration grade benzol. 2) Anhydrous methanol, 3) A saturated solution of phenol red (phenol sulfonphthaleln) in methanol (approx. 0.156). 4) A 0.01 N solution of KOH in methanol. b. Procedure: 1) Place 100 ml. of benzol, 100 ml. of methanol and 0,5 ml. (pipette) of phenol red Indicator into one of two clean dry 500 ml. Erlenmeyer flasks. 2) Neutralize carefully with the 0.01 N KOH (to be first definite pink color.) 3) Pour the mixture back and forth between the two flaskB several times. If the solution Is still neutral, divide it equally between the two flasks, if not, repeat steps 2 and 3. 4) Weigh (1 0.05 g.) into one of the flasks a 75.0 s' 5.0 g. sample and titrate with the 0.01 N, KOH until the sample matcnes the blank. 0.. Calculations: Acid No. (mg. KOH/gram sample) - ml. 0.01 N KOH x '0.56 Sample Weight' 54 0237287 | TOWOLDMON0027517 WATER_PCB-00011986 Report the results to the nearest 0.001 If they are below 0.1, otherwise to the nearest 0.01. The method Is precise to 4- 0.002 for acid numbers below 0.01 and to + 0.01 In the range of 0.1 to 0.01. NOTE 1: To convert mg. KOH/gram to mg. NaOH/gram, multiply by 0.715. 8. METHOD (MODIFIED NO. 10,620, "MOISTURE (WATER)". a.Introductory Comment: The Karl Fischer Reagent titration method used In the analytical laboratory Involves use of an analytical ba lance to weigh accurately about one drop of water used In preparing the standard. Since an analytical balance may not be available, the method has been modified and sues a purchased standard water solution as described below. Also, in the laboratory a "Dead Stop" potentlometrlc method for determining the end point Is often used. However, as this equipment may not be available, the procedure described below uses the visual Indicator change for determining the end point. b.Apparatus and Reagents: 1) Karl Fischer Burett, Automatic Pyrex No. 5750, 25 ml. capacity. Ace Glass Company, Vineland, New Jersey. 2) Water Standard In Methanol. No. SO-W-2 (l ml. : 1 mg. Hp0) Fisher Scientific Company, 2800 Jeffer son Aver, St. Louis, Missouri. 3) Karl Fischer Reagent Solution No. SO-K-2, Fisher Scientific Company. c.Standardization of Karl Fischer Reagent Into a 500 ml. clean, dry Erlenmeyer flasK, place about 100 ml. "Anhydrous" methoanol (commerlcally available, 99.95#). Add Karl Fischer reagent to this blank until the first color change from lemon yellow. It is not necessary to read the burette at this point. Carefully pipette 50 ml. of standard water solution Into the blanked methanol. Refill the Karl Fischer burette.Titrate the solution with gentle swirling to mix, until the same color is obtained as was obtained for the blank. Now read the burette. 55 0137Z88 TOWOLDMONOQ27518 WATER_PCB-00011987 Moisture value of K.F, reagent In terms of grams - H20 per ml. (Moisture value of stand- (Ml. Standard H20 solution) .ard water solution In gm. per ml. stated on label.) ml. Karl Fischer Reagent d. Solvent Mixture: Since the solubility of the different askarels varies, the following solvent mixtures are suggested: Material Anhydrous Benzene Anhydrous Methanol Pyranol 1478 Fyranol 1488 1467 Pyranol 1481 Pyranol 1495 All Aroclors 0 ml. 100 ml. 100 ml. 100 ml. 110 ml. 300 ml. 200 ml. 200 ml. 200 ml. 190 ml. e. Procedure, "Visual End Point." 1) Place 100-300 ml. of dry BOlvent mixture (c) in a dry 500 ml. ground glass stoppered Erlenmeyer flask, 2) Titrate the solvent with K.F. reagent to the vis ual endpoint, l.e., the first change from the yellow to reddish orange that persists for 30 seconds. Refill the burette. 3) Using a beam balance, weigh to the nearest 0.1 gram by difference, a sample containing 0.03 to 0.06 grams KgO Into the flask. 4) Stopper and shake until the sample Is in solution. 5) Titrate the solution with K.F. reagent to the endpoint described In Step 2. Record the volume of K.F. reagent used. Calculation: % h2 " Ml, of K.F. reagent x HpO factor x 100 ' Sample weight References: Mitchell, J. and Smith, D.M., Chemical Analysis, Vol. Aquametry, Interscience Publishers, Inc., New York, (1 948) 56 0^37789 | TOWOLDMON0027519 WATER_PCB-00011988 CHAPTER 7 TYPICAL PROPERTIES The 1200 series members of the Aroclor family are chlor inated biphenyls, and are made by chlorinating biphenyl to approximately the percentage of chlorine, by weight, in dicated by the laBt two digits of the serial number. For example, Aroclor 125** is approximately 54# chlorine on a weight basis. Accordingly, these Aroclors are not single or simple compounds, They are a mixture of isomeric com pounds oomposed predominately of the chemical compound in dicated below as being their approximate equivalent: Aroolor 1242 Aroclor 1248 Aroolor 1254 Aroclor 1260 Triohlorobiphenyl Tetraohlorobiphenyl Pentachlorobiphenyl Hexaehloroblphenyl For transformer use and some capacitor use where lower viscosity is required for better low temperature operation than offered by the above Aroclors, these products are mixed with pour point depressants, particularly trichlorobenzene resulting in various general Electric Company Pyranols described briefly as follows: Transformer Pyranol 1467* 60# of Aroclor 1260 40# of Elec. Grade Trlchlorobenzene 0.125# of Tin Tetraphenyl Transformer Pyranol 1470* 45# of Aroclor 1260 55# of Elec. Grade TrichloroTetrachlorobenzene MIX' ture 0.125# of Tin Tetraphenyl *0se of trl-tetrachlorobenzene and tin-tetraphenyl scavenger is subject to G.E. patents and lioense: Royalty arrangements should be checked before using. Questions about license concerning the use of anthraquinone stabilizer for DC capacitors should be referred to Western Electric, 195 Broadway, N.Y.C. 57 0237Z' TOWOLDMON0027520 WATER_PCB-00011989 Capacitor pyranol l48l 75$ of Aroolor 1254 S5$ of Elec. Orade Tri chlorobenzene Detailed properties of all of these products are given as follows: AROCLOR 1242 PROPERTY TYPICAL Vise. @ 37.8C. (ASTM D88) Specifio Gravity @ 25/15.5C. (ASTM D287) Color, APHA Condition Acidity, mg. KOH/g. Pour Pt., C. (ASTM D97) Inorganic Chlorides, ppm. Refractive Index @ 25" C. Distillation Range (ASTM D20) Corrected for stem and barometric pressure Corrosion 82 - 92 seconds Saybolt Oniver. 1.381 - 1.392 100 max. Clear 0.01 max, -1.4 or lower 0,10 max, 1.6245 - 1.6265 10$, 325C. min. 90$ 366C. max. After heating with aluminum for six hours at 210C I 10C, the aluminum must not be cor roded either on visual or weight inspection and the Aroolor 1242 should meet the following specs: Color, APHA 150 max. Acidity,mg.KOH/g. 0.01 max. Inorg.Chlorides,ppm 0.10 max. Condition Clear Water Content, ppm 35 max. Resistivity 100C. 500 volts DC @ 0.1" gap 500 x lO^ ohm-cm., min, Dieleotrio Constant 100C. 4.7 - 4.9 @ 1000 cycles (ASTM D924) Plash Point Cleve. Open Cup* Fire point c.* l60C, rain. None to boiling point Sulfates (ASTM-D117-31)* None Fixed chlorine content (Carius)* 4l,5 - 42.556 Specific Heat @ 25C.* 0.29 Evaporation 1006C for 6 hrs* 0,k$ max. Dielectric Strength (KV) 35 Min. (ASTM D877)* *Not determined unless by special request. 58 0g3fin TOWOLDMON0027521 WATER_PCB-00011990 AROCLOR 1248 PROPERTY Vise. @ 54.4C. (ASTM D-88) Speo. Qrav, @ 65/15.5C. (ASTM D-287) Color, APHA Condition Acidity, mg. ICOH/g. Pour Point C. (ASTM D-97) Refrao. Index @ 20C. List. Range (ASTM D-20) Water Content, ppm. Reals. 100C, 500 v D.C. 9 0,1" gap Dieleotrlo Constant,lOOOc. 1000 cycle Dlelectrlo Strength 25C.* Plash Point, (C.O.C.)* Fixed Chlorine (Carlus)* SpeoIflo Heat @ 25C.* TYPICAL 73-80* sec.Saybolt Onlver. 1.404-1.414 100 max. Clear 0.01 max. -7 I.63O-I.631 343 - 373CC. 35 500 x 109 ohm-cm., min. 4.6 35 KV min. 193C. 47.5 - 48.5* 0.27 Not determined unless by special request. 59 02 372^-' TOWOLDMON0027522 WATER_PCB-00011991 AROCLOR 1254 PROPERTY TYPICAL Vise. @ 98.9C.(ASTM D88) Specific Gravity @ 65/15*5C. (ASTM D207) Color, APHA Condition Acidity, nig.KOH/g. Pour Pt. C.(ASTM D97) Inorganic Chlorides, ppm. Refraotive Index @ 25C. Distillation Range (ASTM D20) Corrected for stem and Barometrio Pressure Corrosion 44 - 48 sec. Saybolt Dniver, 1.495 - 1.505 100 max. Clear 0.01 max. 7-12 0.10 max. 1.6370 - 1.6390 10# 366-- 3?8C. 50# 372 - 3830c. 90# 383 - 396C. After heating with aluminum for 6 hours @ 210C, plus or minus 10C, the aluminum must be cor roded either on visual or weight inspection and the Aroclor 1254 should meet the following specs: Color, APHA 150 max. Acidity,mg.KOH/g. 0.01 max. Free Chlorides,ppm.0,10 max. Condition Clear Water Content, ppm. 35 max. Resistivity 100C.,500 v D.C. 0.1" gap 500 x 10^ ohm-cm., min. Dielectric Constant, 100C 4.15 - 4.35 1000 oyoles Dielectrio Strength 25C* 35 KV., min. Burn Point (ASTM D92)* Higher than 350C. Sulfates (ASTM D-117-31)* None Fixed Chlorine Content (Carius)* 55 I 0.5# Evaporation @ 100C. for 6 hrs<sI 0.4# max. Stability* There shall be no liberation of chlorine or chlorides when the material is heated @ 100C in glass vessels In contact with air for periods of at least one month. Ageing Characteristics* No loss in resistivity over original value on heating in air for 96 hrs. at 100C. Specific Heat @ 25C.* 0.26 Not determined unless by special request. 60 I TOWOLDMON0027523 WATER_PCB-00011992 AROCLOR lg6p PROPERTY TYPICAL Vise. @ 98.9C.(ASTM D88) 72 - 78 Sec. Saybolt Oniv. Specific Gravity @ 90C./15.5C 1.555 - 1.566 (ASTM D207) Color, APHA 150 max. Condition Clear Acidity, mg.KOH/g, 0,01 max. Pour Pt.,C.(ASTM D97) 25 - 34 Inorganic chlorides, ppm. 0.10 max, Refractive Index, 25C. 1.6455 - 1.6470 Distillation Range (ASTM D20) Corrected for stem and barometric pressure. Corrosion After heating with aluminum for 6 hTB, @ 210C. 4 10C. the aluminum must no be cor roded either on visual or weight Inspection and the Aroolor 1260 should meet the following specs: color, apha iso max. Free Chlorides,ppm. 0.10 max. Acidity,mg.KOH/g. 0.01 max. Condition Clear Water content, ppm. 35 max. Resistivity,1006C. 500 volts @ p.l" gap 500 x 109 ohm-om., min. Dielectric Strength 50C.* 30 KV., min. Dielectric Strength 100C.* 30 KV., min. Dleleotrle Constant 100C. 3.6 - 3.8 @ 1000 cycles* Burn Pt. (ASTM D92)* Higher than 350C. Sulfates (ASTM D117-31)* None Fixed chlorine content (Carlus)* 60 4 0.5* Evaporation @ 100C. for 6 hrBi 0,2* max. stability* There shall be no liberation of chlorine or chlorides when . the material Is heated @ 100C. In a glass vessel in oontact with air for periods of at least one month. Specific Heat @ 25C.* 0.23 *Hot determined unless by special request. 61 ozVf^ TOWOLDMON0027524 WATER_PCB-00011993 PYRANOL 1481 PROPERTIES TYPICAL Viscosity @ 37.8C. 70 - 82 seo, Saybolt Unlv. Spec. Gravity 15.5/15.5C 1.525 - 1.535 Color, APHA 150 max. Condition Clear Acidity, mg. KOH/g. 0.01 max. Pour Pt., C. -15 or lower Inorganio ChlorideB, ppm. 0.10 max. Refractive index @ 25C. 1.6205 - 1.6215 Distillation Range Corrected for stem and barometrio pressure. First drop 205C. min. 25# max. Below 270C. 90# 380 - 395C. Corrosion Test Change in Weight 0.0# Color, APHA 200 max. Acidity, after test,mg.KOH/g 0.01 max. Free Chlorides,ppm. 0.10 max. Condition after test Clear Water Content, ppm. 35 max. Resistivity @ 100C 500 volts, DC, 0.1"gap 100 x 10^ ohm-ora,,min. Dielectrio Constant (100C,, 1000 cycles) 4.1 - 4.6 62 TOWOLDMONOQ27525 WATER_PCB-00011994 PYRANOL 1467 PROPERTIES TYPICAL Vise. @ 37.8C.,(ASTM D88) 54 4 2 sec. Saybolt Dniv. Specifio Gravity @ 15.5/15.5C (ASTM D-287) 1.560 - 1.568 Color, APHA 150 max. Condition Clear Aoidity, mg. KOH/g. 0.01 max. Pour Point, C. (ASTM D-97) -32C. or lower Inorganic Chlorides, ppm. 0.10 max. Refractive Index @ 25C. 1.6137 - 1.6147 Distillation Range (ASTM D20) 1st drop - 200C. min. Corrected for stem and Below 270C. - 40# max. barometric pressure 90# - 395 - 415C Corrosion After heating with aluminum for 6 hrs. at 200-220C.,the aluminum must not be oorroded either on visual or weight in spection and the Pyranol should meet the following specs: Color, APHA 200 max. Acidity,mg.KOH/g. 0.01 max. Inorganic Chlorides 5 max. ppm. Condition Clear Water Content, ppm. 30 max. Resistivity, 100C. 500 volts, q 0.1" gap 100 x 10 ohm-cm.,mln. Dielectrio Strength, 25C. 35 KV., min. Dielectric Constant, 100C. 1000 cycles* 3.7 - 4;0 _ Tin Tetraphenyl* Q.125# 4 OjOl# by weight Burn Point, (ASTM D92)* None up"to Boiling Point Fixed Chlorine* 59.1# min. Aro Formed Oases* Less than 1.0# (Oxygen Free Liquid @ 25C.) Total combustible gases including carbon monoxide, hydrogen and volatile hydro carbons. *Not determined unless by special request. 63 TOWOLDMON0027526 WATER_PCB-00011995 PYRANOL 1470 PROPERTIES TYPICAL Vise. @ 37.8C. (ASTM d88) Spec. Gravity @ 15.5/15.56C., (ASTM D287) Color, APHA Condition Aoidity, mg. KOH/g. Pour Pt.,C., (ASTM D97) Inorganlo Chlorides, ppm. Refraotive Index @ 25C. Distillation Range (ASTM D20) Distillation Range (ASTM D20) Corrected for stem and barometric pressure First drop 35* 55* 65* 95* Corrosion 41-45 See. Saybolt Univ, 1.563 - 1.571 130 max. Clear 0.01 max. -44c., or lower 0.10 max. 1.6075 - 1.6085 210C., min. 238 - 256C. 275 - 345C. 380 - 400C. 390 - 4l5C. After heating with aluminum for 6 hrs. @ 200-220C., the aluminum must not be corroded either on visual or weight inspection and the Pyranol should meet the following specs: Color, APHA 200 max. Acidity,mg.KOH/g. 0.01 max. Inorg. Chlorides,ppm 5 max. Condition Clear Water Content, ppm. 30 max. Resistivity, 1000c., 500 v., 0.1" gap 100 x 10^ ohm-cra., min. Dielectric Strength, 25C. 35 KV., min. Dielectric Constant, 100C., 1000 cycles* 3.8 -4.3 Tin Tetraphenyl* 0.125* + 0.01* by weight Burn Point, (ASTM D92)* None up"to Boiling Point Fixed Chlorine* 60.5 4 0.5 Arc Formed Oases* Total`"combustible gases in (Oxygen Free Liquid 9 25C. cluding oarbon monoxide, hydro gen and volatile hydrocarbons. Electrical Stability* After heating for 96 hrs. @ 100C in a closed container, the resistivity should not decrease more than 10* *Not determined unless by special request. 64 0237297 TOWOLDMON0027527 WATER_PCB-00011996 PYRANOL 1488 Vise. @ 37.8C. Spec. Orav. @ 15.5/15.5C. Color, APHA Acidity (Mg KOH/g) Water, ppm. Condition Refrac. Index @ 25C. Free Chloride, ppm. Pour Point, C. Reals. 100C,, 500 v D.C. 1" gap Dielectric Strength (25C.) Corrosions Lobs of Aluminum 54-- 2 Seo. Saybolt Unlv. 1.560 - 1.568 150 max, .014 max. 35 max. Clear 1.6137 - 1.6147 0.10 max. Lower than -32C. 100 x 10^ ohm-cm min. Over 35 KV None Heating with aluminum for 6 hr8. at 200-220C. The Pyranol after heating should meet the following specs: Color, APHA 200 max. Acidity(MgKOH/g) .014 max. Free Chlorides ppm .10 max. Condition Clear Dielectric Constant @ 1000 oyoles @ 100C.* 3.7 - 4.0 Distilling Range (corrected)* 1st drop 200C. min. Below 270C. 40$ max. 9O5? point 295 - 4l5C. Burn Point (ASTM D-92)* None up to boiling point Fixed Chlorines* 59.l min. Aro Formed Oases* Less than 1.0$ total com (Oxygen-free liquid @ 25C.) bustible gases including oarbon monoxide, hydrogen, and volatile hydrocarbons. Not determined unless by special request. 65 023729& TOWOLDMON0027528 WATER_PCB-00011997 CHAPTER 8 EARTH TREATMENT OP AROCLOR IN THE ELECTRICAL INDUSTRY PRIOR TO USE. Arodors and their mixtures supplied to the electrical Industry must conform with most strict requirements sepclfied by the industry as shown in Chapter 7. Since these products are sensitive to contamination from traces of impurities, they require careful handling in the Industry when sampling or storing or using the materials to Impregnate oapaeltors or fill transformers. Common contaminants to be avoided Include moisture, lonlzable Impurities, metallic impurities, such as rust or corrosion products from storage and handling equipment, and contaminants Buoh as oils (mineral oils), lubricating oils or greases common ly used in equipment or other processes in the electrioal Industry. Care must be taken to avoid contamination from contact with Improper gaskets or paoking materials, including natural and synthetic rubber and most plastic exclusive of oertaln Silicones and Teflon. Rosin solder fluxes, etc. may also introduce traces of deleterious Impurities. The dielectrics are also susceptible to the harmful aotion of ultra-violet light and, therefore, exposure to direct sunlight should be avoided. The adverse effect of lonizable impurities is especially pronounced in the low visoosity Aroolors such as Aroclor 1242 66 . TOWOLDMON0027529 WATER_PCB-00011998 or Aroclor mixtures such as Pyranol l48l. In the ease of more viscous fluids, such as Aroolor 1254, the lonlzable Im purities are not so free to move about In the fluid and, con sequently, the more vlsoous fluids can be handled with less oare than required for the thinner fluids. This is especially pertinent In capacitor manufacturing. When using the thinner type Arodors to make capacitors that offer superior low temperature operation, the following types of trace contamination affeotlng the electrical properties of the dielectric have been experienced. Occasional droplets of perspiration from operators, when winding the capaoltor cores, have fallen onto the paper causing contamination In the finished units. Small amounts of Qlyptal resin and simi lar Beallng compounds used to Beal tiny leaks In the vacuum Impregnating equipment or storage tanks have caused contamina tion. Also, small amounts of mineral oil entering the system have caused similar trouble. A small droplet of any of these materials In one or several liters of the thinner type fluids results In noticeable contamination, whereas It may not have as much adverse effect on the more viscous dielectrics. To be certain that the fluids are free from traces of contamination. It Is standard practice to treat them with con ditioned diatomaoeous earth and then to filter Immediately be fore use. Treatment with this earth by removing trace contam inants results In "up-grading" the electrleal values, e.g., 67 . 02^ TOWOLDMON0027530 WATER_PCB-00011999 the volume-resistivity may be brought up considerably beyond the specification minimum or the normal values of the dielectric as received. Likewise, improvement in power factor may be ao compllshed. The earth treatment recommended for use by the electrical manufacturers is qualitatively the same as used in the produc tion of the Aroclors and their preparation for shipment to the electrical industry. Treatment of the Aroclors with earth by the electrical manufacturers is a step required to assure that traces of impurity or contamination that may have been introduced during storage or handling in the electrical indus try have been removed and that maximum electrical values have been attained immediately before the dlelectrlo is introduced into capacitors or transformers. It is Impractical for the manufacturer to furnish these dielectrics to the customer at the maximum attainable electri cal qualities because even with careful packaging, shipping, sampling and handling in the electrical Industry, these fluids may easily pick up traces of oontaminants from opened tankcars, drums, pipe line, pumps, etc. However, as supplied according to the specifications, the fluids are readily "up-graded" by the earth treatment. The type of dlatomaceous earth used is known as Fuller's Earth, supplied by the Floridin Earth Company, Warren, Pennsyl vania, or the Attapulgus Division, Mineral & Chemicals Corp. of America, 210 West Washington Square, Philadelphia 55, Pa., 68 TOWOLDMON0027531 WATER_PCB-00012000 or their equivalent. Usually a minus 200 mesh size, regular volatile. Is used and theqiality should be specified as for use by the electrical Industry. (Code 73122) The earth as received needs to be conditioned and acti vated, after which it should be stored only a minimum length of time (about a day at the most) and in hermetically sealed containers, prior to use. It is desirable that the earth be used immediately after it has been activated. Activation should be done by heating the earth contained in stainless steel shallow trays for four hours at 400c. in a muffle furnace. If a muffle furnace is not available or the capacity by this method may not be great enough, the earth can be activated by heating at least twelve hours in an elec trically heated oven at 250C. Another method used is to pan dry and activate by heating at 100C, and using a strong vacuum, about 6 mm. of mercury. This latter method is used in connection with transformer work and the former methods are usually used for capacitor work. In the place of pan drying, rotary driers may be used but their aotion should not be so severe as to break the earth par ticles to the extent of producing powder which is difficult to handle in the subsequent filtering operations. It is the consensus that the earth should not be heated above 400c. as this may cause collapse of the particles. 69 oz*130* TOWOLDMON0027532 WATER_PCB-00012001 The amount of earth used Is usually 0.1$ to 0.3$ based on the weight of the fluid. Larger amounts of earth can be used if the fluid Is composed of only Aroclor or a mixture of Aroolor and chlorinated benzene or other pour point depressants. However, larger amounts of highly active earth. In the range of 2$ or 3$, would be expected to selectively adsorb scavengers or stabilizers from the fluids containing these additives. This Is especially of conoern in handling the transformer fluids which usually contain scavengers such as tin tetraphenyl. For transformer work It Is suggested that the earth be condi tioned and mildly activated by heating It at 100C, under va cuum, about 6 mm. of mercury. Not more than about 0.1$ of earth baBed on the total weight of the transformer fluid should be used. For treatment with earth, the fluid Is put Into a suitable tank fitted with an agitator, heating coll, and a cover. The proper amount of freshly conditioned earth 1b added and the mixture Is agitated thoroughly and heated for about four hours. The more viscous dielectrics such as Aroclors 1248 and 1254 8re heated at about 70 to 80 C. (158 to 176F.) and the less vlsoous materials such as Aroclor 1242 and Pyranols 1481, 1467, end 1470 are heated at about 50 to 60 C. (122 to l40F.) After about four hours oontact the material Is filtered through a Sparkler or Sweetland or a comparable filter press previously fitted with filter paper liners such as supplied by 70 . 0237303 | TOWOLDMON0027533 WATER_PCB-00012002 Carl Sohlelcher and Sohuel Co., Inc., Keene, N.H. The paper la usually 25 mils thick and must be dried at 100C. to remove moisture, prior to use In the filter press. The filtered dleleotrlo material is then ready for Impregnating capacitors or filling transformers. In some cases, especially for AC capacitor work where the dielectric does not require addition of stabilizers and accordingly there Is no danger of removing such additives by repeated earth treatment, good practice 1b to use continuous earth treating, circulation and filtration with constant read ing of the resistivity of the filtered dielectric. In Chapters 1 and 2 selection of proper materials of construction for the tankcars and storage tanks was discussed. It Is equally Important to select proper materials of con struction for the processing tanks used In the eapaoitor and transformer Industries and also for the lmprgnating chambers used in making capacitors. It Is preferable that this equipment be made of stain less steel or aluminum, or , If It Is of steel construction, the Interior should be either zlno-tln metallized or aluminum lined. While Iron or steel equipment Is not regarded as de sirable for handling the fluids, this type of construction is used In some of the plants. Here the possibilities of rust ing or corrosion cannot be overlooked. If the equipment Is kept free from water and If a film of clean dleleotrlo adheres 71 ' 0Z3"0*' | TOWOLDMON0027534 WATER_PCB-00012003 to the surface of the metal, e.g. when the tanks are empty, then satisfactory operation can be experienced. However, a number of factors must be kept In mind and to cite an example, reference Is made to the Impregnation of capa citors by the chamber method. The moisture content of the paper used In the oapaoltor oores may easily Introduce several gallons of water Into the average Impregnating ohamber. This water Is removed from the capaoltors prior to impregnation -- usually by heating the ohamber to about 130C. under efficient vacuum, 100 microns or less. If the chamber is not made of the preferred materials of construction, slight corrosion may occur and the film of fluid on the interior surfaoe of the tank may be contaminated and In turn Introduce traces of impuritleB Into the treated and clean dielectric subsequently introduced Into the chamber for Impregnating the capacitors. In fact, because of this possibility of contamination. In some operations the oapacltors are conditioned and dried preparatory to impreg nation in a separate oven or chamber and when thoroughly dried they are then transferred into a seoond ohamber used for impreg nation. In the case of relatively large size capaoltors, such as power factor correction units, a manifold pipe system may be used to handle each unit individually rather than by the batchohamber method. The unimpregnated oapacltors are placed Into an oven and vaouum Is applied to the individual units attached to the manifold. 72 oz^30* | TOWOLDMON0027535 WATER_PCB-00012004 When conditioned and dry, the dleleotrlc le Introduced Into the unit through the manifold. Care must be taken that molBt air or oontamlnants do not oollect In the branoh through Which the dleleotrlc Is Introduced. In addition to removing moisture, another purpose of the heat and vacuum conditioning treatment given the capacitor units prior to Impregnation is to remove traces of impurities suoh as residual solvent from the metal cleaning operations and from Bolder flux, eto. The fluid is Introduced hot Into the evacuated capacitor units. The more vlsoous Aroelors, such as 1248 and 1254, are usually impregnated at 85 to 130C. The less viscous and more volatile dieleotrics such as Aroclor 1242 and mix tures of Aroclor with chlorinated benzene may be Introduced best at lower temperatures -- about 50C. optimum, BO^C. max. Table IV Indicates desirable minimum resistivity values of the dleleotrlo materials when earth treated and ready for oapacltor Impregnation and similar values of the material following the process. TABLE IV Dielectric Volume Resistivity Ohm-om at 100Ct and 500 volts pc. Prior So After Impregnation Impregnation Aroclor 1254 2.500 x 1C>9 800 x 10? Aroolor 1242 1.500 x 109 600 x 109 Pyranol 1481 600 x 10^ 400 x 109 73 *3?306 TOWOLDMON0027536 WATER_PCB-00012005 In the ease of new and freshly filled transformers using Aroclor dielectric mixtures, it seems reasonable that the power factor of a sample of the fluid drawn from the trans former should be in the range of about 5 to 12 per oent, measured at 60 cycles and 100C. With field service of the transformer the power factor value is expected to increase somewhat. However, such a power factor increase alone does not seem to have harmful effeot on the operation of the transformer, A more usual measurement used for transformer fluid is volume-resistivity. This value of the new dieleotrio prior to filling the transformer should be about 500 x 109 ohm-om. at 1,000 cyoles and 100C. The similar value of the fluid taken from a new transformer should be at'least, about, 50 x 109 ohm-cm and no lower than 25 x 10^ ohm cm. With long field service volume-reBistivlty values de crease Bomewhat but seem to level off around 10 x lo9 ohm-cm, with satisfactory transformer operation. However, if the volumereslstivlty of the fluid falls below 10 x 109 ohm-cm, the matter should be looked into. 74 023730? TOWOLDMON0027537 WATER_PCB-00012006 CHAPTER 9 DERMATOLOGY AMD TOXICOLOGY Skin patch tests using Aroolor 1254 (biphenyl Chlorinated to the extent of 54# by weight) applied to gauze and placed In oontaot with the skin showed no primary irritancy or sen sitization, The testB were conducted under competent medical supervision and the standard procedure recommended by Drs. Louis Schwartz and Samuel M, Peck, Reprint No, 2552, Public Health Reports, Vol. 59, No, 19 (April 28, 1944) was used. If Aroclors are spilled on the skin, the skin should be washed In the usual manner with soap solutions. If accidental burns occur from contact with hot Aroclors, the burn should be treated the Bame as any ordinary burn, Aroolor adhering to the burned area need not be removed Immediately unless treatment of the burn demands It, In which case use soap and water or repeated washings with a vegetable oil. At ordinary temperatures Aroclors have not presented Industrial toxloologioal problems. If Aroclors are used at elevated temperatures In open Bystems, methods must be designed to exhaust any vapors arising. Experimental work on animals Indicates that the maximum safe concentrations of vapors In workrooms Is In the range of l,p to 2,0 milligram per cublo meter of air. This applies to all of the liquid Aroclors. 75 i3?J08 | TOWOLDMON0027538 WATER_PCB-00012007 Laboratory technique merely requires keeping the hands free of the liquid and handling It under a well ventilated hood. Localized or spot ventilation together with general work room exhaust Is recommended for plant operations. When sampling tankcars, canvas gloves and safety glasses or goggles should be worn. No speolal clothing Is required but the worker's garments Bhould be laundered at least weekly and ohanged in ease Aroclor or Aroclor mixture is spilled on the clothes accidentally. If workmen are exposed to Aroclor vapors at relatively high levels, as may be the case when opening a heated capaoltor impregnating chamber, a respirator should be worn during these short Intervals. The many years of satisfactory and safe use of Aroolors and their mixtures with ohlorlnated benzenes In the electrical Industry for Impregnating capacitors and filling transformers has demonstrated the Industry's ability to handle these fluids without hazard to the workmen. It is a simple matter and In line with good "housekeeping" and personal cleanliness to exerolze the suggested and required precautions In all cases. 76 0^7309 TOWOLDMON0027539 WATER_PCB-00012008 0237310 TOWOLDMON0027540 WATER_PCB-00012009 0237311 TOWOLDMON0027541 WATER_PCB-00012010 0237312 TOWOLDMON0027542 WATER_PCB-00012011 p p p o z -zs 0237313 || TOWOLDMON0027543 WATER_PCB-00012012 0237314 TOWOLDMON0027544 WATER_PCB-00012013 TOWOLDMON0027545 WATER_PCB-00012014 0237316 TOWOLDMON0027546 WATER_PCB-00012015