American Society of Heating and Ventilating Engineers Guide, 1932
Table 6. Diameters of Branch Pipes and Calculations'of Main for Typical Exhaust System Illustrated in Fig. 1
Machine
Diameter
' or
Branch
Pipes
S .Area
Sq. Inches
Total
Load Area
q Inches
Total Load Area Sq. Inches
+ 25%
Section op Main
Diameter op Main in Even
Inches
Rip Saw............ ................................
Cut-off Saw. '........ ........................... Band Saw... .................. -.................. Planer Top Connection.................... Planer Bottom Connection............
5 in. 4 in. 5 in. 6 in.
6 in.
19.6 19.6
12.6 32.2
19.6 51.8 28.3 80.1 28.3 108.4
25 B 6 in. 40 C 7 in. 65 D 9 in.
100 135 E&F 13 in.
Table 7. Details of Calculation of Friction of Piping System Illustrated in Fig. 1
Section op
Piping
A B C D E F
Effective Length op
Pipe Taken As:
20 ft. 10 ft. 10 ft. 15 ft. 20 ft. 25 ft.
Diameter . op Pipe
in Inches
5 6 7 9 13 13
Area op Pipe
in .
Sq. Ft.
0.136 0.195 0.267 0.442 0.922 0.922
CFM
605 605 991 1,596 3,330 3,330
Velocity op Air Flow,
Feet per Minute
4450 3100 3700 3600 3600 3600
Friction PER 100 IT.
OP Length
7.4 3.1 3.8 2.8 2.0 2.0
Pipe Friction
1.48 0.31 0.38 0.42 0.40 0.50
Total pipe friction------
3.49
352
I i
Chapter-25--Ventilation of Industrial Buildings; Exhaust Systems
Resistance of System
The maintained resistance of the exhaust system is composed of three factors: (1) loss through the hoods; (2) collector drop; and (3) friction drop in the pipes.
The loss through the hoods is usually assumed to be equal to the suction maintained at the hoods. The collector drop in inches of water is given roughly by Eq.uation 2, but where possible the resistance of the particular collector to be used should be ascertained from the manufacturer as these resistances differ quite widely.
Drop = c(w)'
(2)
where
C = a constant which depends upon the type of collector and ranges from 0.065 to 0.145.
V = velocity in feet per minute of air entering the collector.
Friction drop in the pipes must be computed for each section where there is a change in area or in velocity. Find the velocities in each section of pipe starting with the branch most remote from the fan. The friction drop for these sections can be determined by reference to Table 5. Total friction loss in the piping system is the friction drop in the most remote branch plus the drop in the various sections of the main, plus the drop in the discharge pipe.
TYPICAL LAYOUT AND CALCULATIONS
To illustrate the method of laying out and calculating the elements of an exhaust system, assume a small wood-working shop, having one 16 in. diameter rip saw, one 12 in. diameter cut-off saw, one band saw with 2 in. blades, and one planer with 10 in. knives, and with the general arrange ment of the machines and exhaust system as shown in Fig. 1.
First, determine the sizes to be used for the branch connection to the hoods. These sizes can be taken from Table 1 giving due consideration to the type and.size of machines as well as the class of work handled. (See Table 6).
The next step is to determine the size of the main, which varies in diameter, increasing from its dead end towards the fan, as necessitated by the branch pipes entering it. Its exact diameter at any point is determined according tt) the following rule:
The area of the main at any point should be 20 per cent to 26 per cent in excess of the sum of the areas of the branches entering it between the point in question and the dead end of the main. Floor sweeps, if equipped with efficient blast gates, need not be included in computing the area of the main.
According to Table 3, 2 in. suction at the hoods is suitable for exhaust ing from wood-working machinery where the duty is light, as would be the case in this problem. The volume of air to be handled by the system - is determined from Tabled.