CHAPTER 33
1954 Guide
stabilize the flow entering the impeller when adverse flow conditions existi<||
in the approach to the inlet.
/ 1 'jfi
As>tul flow fans develop none of their static pressure by centrifugal iut ug , ^
but all from the change in velocity in passing through the impeller, and its*^
conversion into static pressure. They are'thus inherently high velocity
fans, and are very dependent on blade conformation for good characteristics.^
For that reason, an air foil section, such as developed in wind tunnels forlgy
aircraft work8 is frequently used. Since any shape of blade can only be'i|
correct for a harrow range of capacity at constant speed, the performance
curves for any blade show definite characteristics. To absorb energy, the'Jgt
air must be given a tangential motion in passing the impeller,7 and wheh'|y
operating against higher pressures, must have guide vanes (see vaneaxial -|
fans) to obtain best efficiencies.
"ft
Fans
741
downward trend from no delivery to free delivery with the maximum at no delivery, contrary to that of a centrifugal fan. The type of guide vanes in a vaneaxial fan has a distinct bearing on the shape of the horsepower curve. The maximum efficiency tends to occur at a percentage of free delivery capacity higher than for a centrifugal fan.
The sound curve, which may have a minimum value comparable to centrifugal fans, is again lowest near maximum efficiency, but has a charac teristic rise when the fan is operating at low capacities and the stall point of the blade section is reached.
Since propeller Jans are, designed for operation near free delivery, less attention is given the regaining of velocity to static pressure, and the pressure curve rises constantly from free delivery to no delivery. The"
I
I
1
.1
Fig. 4. Percentage Performance Corves of an Axial Flow Fan
.'ft
;,f
While axial flow fans are inherently a higher capacity type than centrif-
ugal fans, they, too, may be designed with widely varying characteristics?;
As- with a centrifugal fan, the pressure rises generally from free delivery'
to no delivery, but tubeaxial and vaneaxial fans may have a drop in pressure, /
when the capacity decreases below a certain volume, a condition also found':
in the case of the centrifugal fan having forward-curved blades. - The
pressure drop is caused by the same condition for both fans, i.e., the static'
pressure: is largely dependent on conversion of velocity pressure,' and '
velocity pressure is small at low capacity. Tubeaxial and vaneaxial; fans.
may also have performance curves resembling somewhat those of a centrif
ugal fan with backward-curved blades. Fig. 4-shows the performance
curves for a typical design.
; 'If
The horsepower curve may be flat with a self-limiting characteristic: as in a backward-curved blade centrifugal fan, or it may have a generally
AIR VOLUME. CUBIC FEET PER MINUTE IN THOUSANDS
Fig. 5. Parabolic System Characteristic Curves
horsepower is highest at no delivery, and decreases toward free delivery, m contrast to a centrifugal fan. .Maximum total efficiency is obtained at a higher percentage of free delivery than for other types.
SYSTEM CHARACTERISTICS
Any ventilating system consisting of duct work, heaters, air washers, "h^rs, etc., has a system characteristic whdeh is individual to that system, and is independent of any fan which may. be applied to the system. This characteristic may be expressed in curve form in exactly the same manner that fan characteristics may be shown. Typical system characteristic curves are shown as A, B and C in Fig. 5. These curves are drawn to oliow the simple parabolic law in which the static pressure or resistance o flow of air varies as the square of the volume flowing through the sys"m- .Heating and ventilating systems follow this law very closely and serious error is introduced by its use.
When a constant speed fan curve tor a given size fan is super-imposed