Document MKgvMj0b4Rpxov986OMOoamj
c.c D. Wood - Brussels J M.K. Thomson - London< G.C.G. AlberiBi - Milan
31t October, 1968*
Dr. G, Kaachio, Pirelli General Cables Ltd.* haatleigh, Hampshire.
Dear Dr. Kiuiehiot
Aroclor 1242 1 quantity and Nature of Deeopposition Products
It was a pleasure to meet you and Mr* Simmons os 16th October. 1 should now like to answer the questions that you raised during the neeting.
1) Theoretical calculation of the volume of hydrogen chloride produced l^ecSj^te" de<^m^ltlSr'{^ 'AroSor''^. 1 litre of Aroelor 1242 at 2QC weighs 1*>6 kg and contains 0.58 kg of chlorine. Complete decomposition would produce 0*60 kg of hydrogen ohloride which occupies s volume of 266 litres at a temperature of 0 C and a pressure of 7&0 torr. This is an extreme case assuming s sufficiently high input of energy. Since the Bunsen coefficient for the solution of hydrogen chloride in water is 412 st J0C at this temperature this volume of hydrogen chloride would be dissolved by O.89 litres of water.
2) Volume of gases produced by decomposition of askarels in electric arcs During 1994, one of our transformer customers carried out experiments on the volume of gases produced by powerful arcs in mineral oil and transformer askarels (lyroclor). Records of the pressure sad volume of gas produced end its composition were obtained together with oscillograph records of the are conditions. Later, s second series of tents was made on Aroclor 1242, 1248 and 12>4, but in this series the volume of gases was not measured. However, from the pressure data recorded for both series it is possible to estimate the volume of gases produced in the second series where these values were not measured directly. The arcs took place in a steel tank with a volume of about
/2
0573496
HARTOLDMONOOQ4754
2
32 litres. The volume of liquid for each test was about 10 litres. The electrodes were of copper, arranged about ?6 ea below the surface of the liquid, fhe gap was 12.7 am and the arc was initiated by 2 strands of 40 S.s.G. (0.122 am diameter) fuse wire, fhe free volume of the tank was evacuated before each test, fhe applied voltage was about 5 kv for all the tests.
fhe following table gives the results of the testsi-
Liquid
Mineral oil If it ft (|
pyroclor tl If It
Aroclor 1242 Aroclor 1248
If Aroclor 125^
It If if
Symmetrical Breaking Current
CkARMS)
6.38 10.4
13.5 5*94 6.13 6.06 10.4 9.96 10.1 9.4
5*05 9.40
10.3 9.58
Arc duration (0,01 s)
- 2.0 3.0 3.2 3.0 3.1 3.0 3.0 2.0 3.9 1.9 4.0 3.0 2,0 3.0
fotal Arc Lnergy(kJ)
Volume of gases at Mff (1)
18.3 64.7
136.0
95*8 130,0
71.2
529 105
319 86.2 73.0 180 29.4
214
6.8
13 37 122 178
54 496
45 235
73.3 26,3 115
15 116
Volume/ Energy (1/kd)
0*37 0.20 0,2? 1.27 1.37 0.76 1.51 0.43 0.74 0.85 0.35 0.63 0.50 0.54
Although a total of 4 tests were made with Aroclor 1242, only in one ease was the pressure recorded from which it is possible to estimate the volume of gases produced. We can summarise the previous table of results as followsi-
'no, of Liquid results
Mineral oil lyroolor Aroclor 1242 Aroclor 1248 Aroclor 1254
3 4
1
2 4
Volume of gas at NfP produced for uni!, arc energy ff/kJ)
Kang*
Average
0.20 to 0.37 0.?6 to 1.51
*
0.74 to 0.85
0.35 to 0.63
0.28
1.23 0.43 0.80 0.50
Although the amount of gas produced by arcing in insulating liquids depends upon the test conditions, these figures enable the order of magnitude to be calculated for a particular fault level.
n 0573*9?
HARTOLDMONOOQ4755
5.
3) Information on the toxicity of hydrogen chloride and other gages
The following information ha* boon summarised from li.I. Sax, "Dangerous Properties of Industrial Materials", 2nd sdn., Keinhold Publishing Corporation, New York, 1963*
Hydrogen chlorldti TLV ^Threshold liasitinc value), ACQIH (accepted) i 5 ppa v/v in air, ? ag/sr of air. A concentration of 35 ppm causes irritation of the throat after short exposure. Concentrations of 50 to 100 ppm art tolerable for 1 hour. Concentrations of 1000 to 2000 ppm are dangerous even for brief exposures. Mists of hydrogen chloride are considered less harmful than the anhydrous hydrogen chloride.
Chlorine: TLV ACQIH (accepted) t 1 ppm v/v in air, 3 ag/nr' of air. a concentration of 3*5 ppm products detectable odour. A concentration of 15 ppm causes immediate Irritation of the throat. Concentrations of 50 ppm are dangerous even for short exposures. A concentration of 1000 ppm may be fatal even when exposure is brief.
Phosgene* TLV ACQIH (accepted) * 1 pj v/v in air, 4 mg/of5 of air.
Concentrations of 3 to 5 ppm cause irritation of eyes and throat with coughing. A concentration of 25 ppm is dangerous for exposures lasting 30 to 60 minutes. A concentration of 50 ppm is rapidly fatal after even short exposure.
Carbon monoxide* TLV ACQIH (accepted) t 100 ppa v/v in air, 115 mg/cf' of air. A concentration of 400 to 500 ppa in air can be inhaled without appreciable effect for 1 hour. One hour's exposure to a concentration of 600 to ?00 ppm will eause barely appreciable effects, exposure to 1000 to 1200 ppm is dangerous. Concentrations of 4000 ppm and over are fatal in less than an hour. Heported exposure to low concentrations up to 100 ppm is generally believed to cause no signs of poisoning or permanent damage*
The following additional information was summarised from l-'.A. tatty 'Industrial Hygene and Toxicology', 2nd edn.. Interscience Publishers, Hew York, 19&3*
Concentration of hydrogen chloride in eir (ppm)
effect
1 to 5 5 to 10
10 10 to 50 50 to 100
Aroclor 1242 vapour in air
Moot people can detect disagreeable
work undisturbed work difficult but possible
work impossible
TLV ACQIH (April 196?)* 1.0 sg/o5
4) Kate of decomposition of Aroclor 1242 at a temperature of about 1000C
1 regret that m do not have this information. We could make some estimates based on thermo dyn.and.cal reasoning but it would be necessary to make certain assumptions and the results would be of doubtful validity. Our only information of this type relates to the use of Aroclor in heat transfer '
/4 0573498 HARTOLDMONOOQ4756
systems operating at atmospheric pressure. Aroclor 1242 has a boiling point of about jS10G and a flash point by the method of AST*! D92-5? (Cleveland Open Cup) above 1?1C t by the mm test method, there is no Hr# point below the boiling point.
5) feats for the presence of chlorine and phosgene la the gasea resulting
from.tSe'1''^^
"...... . ' ' '" ' '
a) I enclose a xerox copy of a paper by P Jay 'ftude de la formation de phosgene par decomposition dmm l1arc dleetrique des hydrooarburas Chloree*, Chiaie et Industrie, g2, Ho. 5 (Noverabre 1964). 1 also enclose a copy of an English translation of this paper.
fh# Monsanto products equivalent to those mentioned in this paper are as followst-
Fyralene 1499 Pyralene 14?6 Fyralene 146?
-
Aroolor 1242 Aroolor 1254 Pyroclor (transformer aakarel)
You will see that Jay was unable to detect the presence of either chlorine or phosgene during the tests `on askarels.
b) In addition, I enclose an English translation of a report from the Chemlscb-Technisohe Heichanstalt, Berlin, Register Ho. 1?6/40C of 21st Hey 1940, `Opinion on the behaviour of Ciophena in thermal and electrical treatment1. We do not have the original version in the German language.
In this report, the Monsanto equivalents of those metnloned are as followsi-
' Clophen T64 Pyroclor (transformer aakarel) Glojtoen A50 - Aroclor 1254
At that time, trichlorodiphenyl was not widely used as a capacitor impregnent.
Again, the writer was unable to detect the presence of either chlorine or phosgene under a wide range of conditions.
X believe that X have new covered fully the questions that arose during our meeting, but please do not hesitate to let me know if you require further information.
CRCieah
fours sincerely,
ORC
Colin R. Coleman Research & Development Dept.
0573*99
.ammmmm
HARTOLDMONOOQ4757