SINGLE LAYER
SECTION 1
HI-TEMP
application
Page 25
SQUARE EQUIPMENT INSUL. (cont'd.)
5A SQUARE EQUIPMENT INSULATION
5A1 INSUL-PIN SUPPORTS
5A1.1 Insul-pins shall be used to support the insulation on all surfaces of square equipment except the top surfaces.
5A1.2
On bottom surfaces the pins shall be spaced to allow 8
pins for each 12" wide x 36" long block of insulation.
(See figure 22) The bottom blocks shall extend, the thickness of the insulation, past the sides of the equip ment as shown in figure 22.