Document MJRr6yk0wQ0kgJ5JYN3BQwj8x
90
CHAPTER 6
1962 Guide And Data Book
Table 2.... Pressure Drops in Common Use for Sizing Steam Pipe*
{For Cormpoodiag boHtd Stoaxj fnnWMi
faiftof Stopni ftlllBW, fvj
Pressure Drop for lOO Ft, Pd
fold Pressure Drop to ftomn Soppty Piptog, PU
Fig. 21.... Relation Between Elapsed Time, Steam Pressure, Condensate and Air Elimination Rates
rate is obtained when the system steam pressure is lower than that existing during a period of constant condensing rate. It will also be noted that the peak rate of air elimina tion does not coincide with the higher condensing rate.
Steam Flow
Subatmos. or - \ vacuum return/
0 1 2 5 10
15 30 50 100 150
2-4 os
X OS 2 os 2 os 4 os 8 os
l'psi 2 psi 2-5 psi 2-5 psi 2-10 psi
1-2 psi
1 os 1-4 os
8 os IX Pei
3 psi
4 psi 5-10 psi 10rl5 psi . 15-25 psi 25-30 psi
* Equipment, control vain*, etc., most be ectactori os the best <rf delivered
The rate of flow of dry steam, or steam with a small
amount of water flowing in the same direction, is in ac
cordance with the general laws of gas flow, and is a func-
' tion of the length and diameter of the pipe, the density of the
steam, and the pressure drop through the pipe. This rela
tionship, developed by Unwin and later by Babcock, has
been used for years as a means of determining steam flow
through pipes. The new charts for weight-flow rate, pres
sure drop, and velocity presented in
chapter take into
account the Reynolds number and its effect on friction loss,
two items which were not considered when using the Un
win or Babcock formulas.
The data presented in Figs. 22, 23, 24, 25, 26 and Table
5, in later sections of this chapter, are based on the Moody
Friction Factor where the absolute roughness of the internal
pipe surface is that of new commercial steel or wrought iron.
The Reynolds number, as expressed by Equation 1, Chap
ter 7 of the 1961 Guide Arm Data Book, is
The velocity is determined by the equation
V--*ZBOOpA
(2)
where
W ~ given weight-flow rate, pounds per hour. A -- internal pipe area, square feet.
The values used for the absolute viscoatyof saturated steam are those of Iieb, published in Combustion, Decem ber, 1940. The relative roughness of the internal pipe surface is obtained by dividing the absolute surface roughness by the internal pipe diameter. The values for absolute rough ness are those presented by L. F. Moody in Mechanical Engineering, Vol. 69, 1947, p. 1005. From the Reynolds num ber and relative roughness, the friction factor / is obtained from the Moody Friction Factor Chart, fig. 19 of Chapter 7 of the 1961 Gums And Data Book.
The head loss in feet is given by the equation
dVp AT*.
tt)
where
V m velocity of the steam, feet per second, d " internal diameter of the pipe, feet. . p -- density of saturated steam at a specified saturation
pressure, pounds per cubic foot. ft absolute viscosity, pounds per foot-second.
SLY' 2fld
(3)
where
/ = friction factor. L -- length of pipe (100 ft). g ** acceleration due to gravity, 32.174 feet per (second)
(second).
Table 3.... Comparative Capacity of Steam Lines at Various Pitches for Steam and Condensate Rowing in Opposite Directions*
(Pitch of Pip* to todhot pot 10 B. Velocity to Fi pot Sec)
Pitch at Pip*..
X
Xfa.
tfa.
IX fa-
2 to.
3 to.
4 to.
5 to
Pip* Sit* lochoi
Capoc*r
Max. YoL
Capaci*r
Max. Vol.
Capoc*r
Max. Vol.
Capoc-
Max. VoL
Capocfly
Max. Voi.
Capoc-
Max. VW.
Capoc-
Max. V*l.
CapocHr
Max. VL
Capacity Expressed in Pounds per Hour
H
6.3 12
7.6 14
9.3 18 10.1 19 10.6 20 11.5 21 11.9 22
12.3 23
l
11.5 12
13.2 15 15.8 17
17.5 20
18.8 22 20.8 23 22.0 25
22.6 26
iX
26.2 18 29.3 20 33.3 23 36.1 25 38.5 27 41.3 28 43.2 29
44.6 31
IX 35.7 18 39.8 21 45.3 23 49.1 25 52.3 27 56.0 28 58.7 30 60.7 31
2 S9.0 19 65.9 20 74.9 23 81.4 25 86.6 27 92.4 28 97.1 29 100.3 30
From TBi Ami
SocrrrT or Ubatimo. Bmusnuwo amp ij>ComonM Ejraurssae Buererrh iAbontay.
Steam Heating Systems
The pressure drop in pa per 100 ft of pipe
pAfi AP 144
(4)
pipe Sizes
The determination of pipe sizes for a given load in steam
hating depends on the following principal factors:
1 The initial pressure and the total pressure drop'which may be allowed between the source of supply and at the end of tbe return system.
2 The mT|'mnm velocity of steam allowable for quiet and dependable operation of the system, taking into consideration the direction of condensate flow.
3 The equivalent length of the run from the boiler or source of steam'supply to the farthest heating unit.
4. The direction of flow of the condensate^whether against or with the steam.
Initial Pressure and Pressure Drop
Theoretically, there are several factors to be considered such as initial pressure and pressure required at the end of the line, but it is most important that: (1) the total pressure drop does not exceed the initial gage pressure of the system, and in actual'practice it should never exceed one-half of the initial gage pressure; (2) the pressure drop is not so great as to cause excessive velocities; (3) there is a constant initial pressure, except on systems specially designed for varying initial pressures, such as the subatinospheric, which normally operate under controlled partial vacuums, and orifice and vapor systems, which at times operate under such partial vacuums as may be obtained due to the condition of the fire; and (4) the rise in water due topressare drop does not ex ceed the difference in level, for gravity return systems, be tween the lowest point on the steam main, .the heating units, or the dry-return, and the boiler water line.
Table 2 lists pressure drops in common use with corre sponding initial steam pressures`for dring steam piping. It is common practice to limit the total drop in the supply piping to approximately Vs of the initial pressure. The allow able pressure per 100 ft is thereby determined by the equiva lent length. Designers may utilize total pressure drops up to 14 the initial pressure when steam velocities and operating pressure requirements of the selected equipment will per mit. For initial pressures of 30 psig and higher many de signers prefer to size steam piping on the velocity method.
The total pressure drop should never exceed one-half of .the initial gage pressure when condensate is flowing in the same direction as the steam. Where the condensate must flow counter to the steam, the governing factor is the veloc ity permissible without interfering with the condensate flow. ASBRAE Research Laboratory experiments limit this to the capacities given in Table 3 for horizontal pipes at various grades.
Maximum Velocity
The capacity of a steam pipe in any part of a steam sys.tem depends upon the quantity of condensate present, the direction in which the condensate is flowing, and the pres.Rire drop in the pipe. Where the quantity of condensate is limited and is flowing in the same direction as the steam, mdy the pressure drop need be considered. When the conden*sate must flow against the steam, even in limited quantity, the velocity of the steam must not exceed limits above which the disturbance between the steam and the counterflowing water may produce objectionable sounds, such as
water hammer, or may result in the retention of water in
91
Table 4.... Length in Feet of Pipe to be Added to Actual Length of Run--Owing to Fittings--To Obtain Equivalent Length
tanqffi to foot to bo Added to lea
Six* at Pipo Inrfm
Standard Bbaw
Sid* Outlet Te*b
Gat* Valve*
Glob* Vatv**
Angle Valve*
X H l IX
IX 2 2X 3
3X 4 5 6
8 10 12 14
1.3 1.8 2.2 3.0
3.5 4.3 5.0 6.5
8 9 11 13
17 21 27 30
3 4 5 6
7 8 11 13
15 18 22 27
35 45 53 63
0.3 14 0.4 18 0.5 23 0.6 29
0.8 34 1.0 46 l.l 54 1.4 66
1.6 80 1.9 92 2.2 112 2.8 136
3.7 180 4.6 230 5.5 270 6.4 310
7 10 12 15
18 22 27 34
40 45 56 67
92 112 132 152
* Valve in full open pceitkm. b Value* gives apply only to a tee uaed to divert tbe Sow is the main to the
length in feet oC pipe to be added to actoal length at run.
LAST RISER OR RADIATOR
Measured Length -- 132.0 it
4 to. Gate Valve - l.tft
4-4 in. Elbow* - 30.0 tt
5-4 is. Tea
- 30.0 tt
Equivalent
* 2CS.0 ft
certain parts of the system until the steam flow is reduced sufficiently to permit the water to pass. The velocity at which such disturbances take place is a function of (1) the pipe size, whether the pipe runs horizontally or vertically; (2) the pitch of the pipie if it runs horizontally; (3) tbe quantity of condensate flowing against the steam; and (4) freedom of tbe piping from water pockets which under cer tain conditions act as a restriction in pipe size.
Reaming Important
It is extremely important that the ends of all pipe be reamed or filed. This insures full pipe area and minimises disturbance of the steam or condensate stream. -
Equivalent Length of Run
All tables for the flow of steam in pipes, based on pres sure drop, must allow for the friction offered by the pipe, as well as for the additional resistance of the fittings and valves. These resistances generally are stated in terms of straight pipe; in other words, a certain fitting will produce a drop in pressure equivalent to the stated number of feet of straight run of the same size of pipe. Table 4 gives the num ber of feet of straight pipe usually allowed for the more common types of fittings and valves. In all pipe sizing tables in this chapter the length of run refers to the equivalent length of run as distinguished from the actual length of pipe