Document MJ4kRN8Eo4rZDR7XEa6Lxv489
American Water Works Association
ANSI/AWWA C400-80 (Revision of AWWA C400-77)
AWWA STANDARD
for
ASBESTOS-CEMENT DISTRIBUTION PIPE, 4 IN. THROUGH 16 IN.
(100 mm THROUGH 400 mm) NPS, FOR WATER AND OTHER LIQUIDS
[AMERICAN NATIONAL) VHSTANDARDHP
First edition approved by A W WA Board of Directors May 15, 1953. This edition approved Jun. 15, 1980.
Approved by American National Standards Institute, Inc., Feb. 19, 1981.
AMERICAN WATER WORKS ASSOCIATION
6666 West Quincy Avenue, Denver, Colorado 80235
Committee Personnel
The Standards Committee on Asbestos-Cement Pressure Pipe that reviewed and approved this standard had the following personnel at the time of approval:
R. S. Bryant, Chairman J. L. Warden, Vice-Chairman
T. R. Gillen, Secretary
Consumer Members
S. C. Baker, Naval Facilities Engineering Command, Alexandria, VA
Glenwood Bretz,* Civil Engineer, Port Hueneme, CA R. S. Bryant,* Department of Water & Power, Los Angeles, CA F. G. Denson, Works & Operations Department,
Winnipeg, Manitoba Roger Graff, City of San Diego, San Diego, CA J. E. Johnson,* U.S. Water & Power Resources Services,
Denver, CO W. J. K eller,* Water Department, Rapid City, SD R. A. Marchand, Water Department, Warren, OH J. L. Warden, U.S. Water & Power Resources Services,
Denver, CO
(NAVFAC) (NAVFAC)
(ASCE)
(AWWA) (AWWA)
(USWPRS) (AWWA) (AWWA)
(USWPRS)
General Interest Members
G. C. Anderson, Insurance Services Office, New York, NY R. A. Barrows, C. E. Maguire, Inc., Waltham, MA V. R. Bickel, Department of Environmental Health,
Albuquerque, NM S. L. Bishop,* Metcalf & Eddy, Boston, MA T. J. Brown, Jr., Factory Mutual Research Corp., Norwood, MA C. W. Cline,* Thompson & Litton, Inc., Norton, VA L. J. Dosedlo, Underwriters Lab, Northbrook, IL C. L. Frick,* Insurance Services Office, Atlanta, GA R. S. Holmgren, Jr., James M. Montgomery, Pasadena, CA L. L. Lyles, W. M. Lyles Co., Visalia, CA F. A. Obert, Metcalf & Eddy, Boston, MA M. R. Suchomel,* Underwriters Laboratories, Northbrook, IL W. Taggart, Wright-McLaughlin Engineering, Denver, CO J. R. Williams, McLean, VA
(ISO) (NEWWA)
(APWA) (NEWWA)
(FMR) (AWWA)
(UL) (ISO) (AWWA) (AWWA) (WPCF) (UL) (ASCE) (AWWA)
*Alternate
Copyright 1980 by American Water Works Association Printed in US
ii
Committee Personnel (continued)
Producer Members
J. F. Baker, CertainTeed Products Corp., P & PG, Valley Forge, PA
F. V. Camarda, U.S. Steel Corp., Gary, IN W. R. Carter, Hersey Products, Inc., Dedham, MA T. R. Gili,en, Johns-Manville Sales Corp., Denver, CO Gustavo Herrera, Asbestos Monterrey, S.A., Mexico R. W. Hood,* Hersey Products, Dedham, MA Leo Horvath,* Asbestos-Cement Pipe Producers Assn.,
Arlington, VA J. C. Jackson, Asbestos-Cement Pipe Producers Assn.,
Arlington, VA R. P. Korobij,* CertainTeed Products Corp., Valley Forge, PA S. G. Leyshock, Cement Asbestos Products, Birmingham, AL H. L. Oi son,* Johns-Manville Sales Corp., Denver, CO
`Alternate
(AWWA) (AWWA) (AWWA) (AWWA) (AWWA) (AWWA)
(ACPPA)
(ACPPA) (AWWA) (AWWA) (AWWA)
in
Table of Contents
SEC
PAGE SEC
Foreword
5.4
I History of Standard ......................
v
II Information Regarding Use of
5.5
This Standard .............................
v
III Major Revisions ............................. viii 6 IV Metrication ..................................... viii 6.1
Standard
6.2
1 General.................................. I
1.1 Scope ................................................ I 1.2 Definitions....................................... I F. I
1.3 Affidavit of Compliance............... 2
1.4 References ....................................... 2 F.2
2
Materials..........................................
2
2.1
Composition ...................................
2
2.2
Physical Requirements..................
2 F.3
2.3
Chemical Requirements...............
4
3.
Design...............................................
4
3.1 Pipe Classes...................................... 4
3.2
Pipe Diameters ...............................
4 F.4
3.3
Pipe Lengths ...................................
4
3.4
Couplings..........................................
4 F.5
3.5 Joints ................................................ 5
3.6
Wall Thickness ...............................
51
2
4 Workmanship and Finish......... 5
4.1
Imperfections...................................
53
4
5 Inspection, Testing, and
Rejection.....................................
5
5.1
Inspection..........................................
5
5.2
Physical Test Requirements.........
6
5.3 Retests (Physical) and
Rejection .....................................
7
. PAGE
Test for Uncombined Calcium Hydroxide ...................................
Test Records ...................................
7 7
Marking and Delivery .................
Marking.............................................. Preparation for Shipment ...........
7 7 8
Tables
Asbestos-Cement Pipe Type Recommended for Interna] Water Aggressiveness...............
Aggressiveness of Nonsulfate Acidic Soils to _ Asbestos-Cement Pipe.............
Asbestos-Cement Pipe Type Designation Chemical Resistance to Nonacid (pH + 7.0) Soluble Sulfates in Water and Soils ..............................................
Sulfate Aggressiveness in Water and Soil............................
Metric Conversion Factors..........................................
Flexural Test Loads.......................... Design Internal Pressure
and Design External Load .... Wall Thickness Tolerance ........... Hydrostatic Tests ...........................
vi
vi
vi viii viii
2 3 5 6
Appendix
Dimensional Table of Fittings Ends Designed for Use with Asbestos-Cement Pressure Pipe...............................
8
iv
Foreword
Thisforeword isfor information only and is not a part of A WWA C400.
IHistory of Standard
A new pipe material consisting of an intimate mixture of portland cement and asbestos fibers was introduced to the North American market in 1931 following several years of satisfactory usage in other countries, particularly Italy.
In the ensuing years this type of pipe gained popularity, and in 1949 AWWA established a committee on standard speci fications for asbestos-cement pipe under the chairmanship of S. M. Clark of Greeley and Hansen, Chicago.
The committee developed a standard for asbestos-cement water pipe, which was approved by the AWWA Board of Directors as a tentative standard, AWWA C400-53T, May 15, 1953. In 1958 the committee was reactivated as Committee ' 8340D on Asbestos-Cement Pipe under the chairmanship of Roy H. Ritter of Whitman, Requardt and Associates, Baltimore, to review several suggested changes and to recommend revisions to the standard. The committee produced a revised tentative standard adopted by AWWA as C400-64T Jan. 27,1964, which was advanced to standard without re vision Jul. 2, 1965.
In 1968 the committee was reactivated as the Standards Committee on Asbes tos-Cement Pipe to review and revise all AWWA standards on asbestos-cement pipe. The committee produced a revised standard approved by the Board of Di rectors Jan. 31, 1972 designated as AWWA C400-72, "Asbestos-Cement Pres sure Pipe for Water and Other Liquids."
In 1972 and 1973 the committee was reorganized and enlarged to include rep resentation of national organizations hav ing an interest in the scope of the commit tee and wishing to participate in the work. The reorganized committee reaffirmed
C400-72 without revision so that it could be presented to the American National Standards Institute for designation as an American National Standard.
In 1975 the committee produced a revised standard approved by the AWWA Board of Directors Jan. 26, 1975 desig nated as AWWA C400-75, "AsbestosCement Pressure Pipe, 4 in. Through 24 in., for Water and Other Liquids." At that same time a new standard was produced by the committee and approved by the AWWA Board of Directors and desig nated as AWWA C402-75, "AsbestosCement Transmission Pipe, 18 in. Through 42 in., for Water and Other Liquids."
The possibility of confusion between the two standards (C400 and C402) was carefully reviewed by the committee. The result was C400-77, which reduced the sizes covered from 4 in. through 24 in. to 4 in. through 16 in., eliminating any overlap between the standards.
In 1979 the committee again revised this standard to make reference to ASTM C500-77, "Testing Asbestos-Cement Pipe,''and to include dimensional require ments for fittings in the Appendix.
II Information Regarding Use of This Standard
II.A General. When ordering pipe covered by this standard, local installation and operating conditions should be con sidered to determine the class and type of pipe to specify. Also, certain other items must be specified to describe completely the pipe required.
According to the conditions of installa tion and operation in many water distri bution systems, the pipe may be used at operating pressures equal to the class
VI FOREWORD
designations. The purchaser should de termine for himself from AWWA C401, "Standard Practice for the Selection of Asbestos-Cement Distribution Pipe, 4 in. Through 16 in., for Water and Other Liquids," the proper class of pipe to be used under the installation and operating conditions that will exist for the project on which the pipe is to be used.
The purchaser is referred to AWWA C603, "Installation of Asbestos-Cement Pressure Pipe," for guidance in laying of the pipe.
II. B Flexural load test. The flexural load tests for pipe sizes, 4,6, and 8 in. (Sec. 2.2.1 and 5.2.3) are intended only for use as a quality control test; not a simulated service test. Asbestos-cement pipe will not be subjected to flexural stresses if properly installed with satisfactory bed ding methods.
For diameters 10 in. and larger, the wall thickness increases to a point at which the flexural strength is not a controlling factor, and hence, routine testing is not required.
II.C Type of pipe. The following criteria are presented for determining the type of pipe to be used under various soil and water conditions. Each condition should be considered separately even though each may exist in combination with others. These criteria are based on exposures within the temperature range of 40-80 F (5-28 C). For exposure of pipe to temperatures beyond these limits, consult the manufacturer.
The following criteria are referenced as 1. Internal water (Table F. 1). 2. External water (Table F.2). 3. Nonacid soluble sulfates--internal
and external (Table F.3). 4. Acid soluble sulfates--internal and
external. II.C. 1 Internal water. Aggressive ness of water transported through asbestos-cement pipe is related to the type of designation of asbestos-cement pipe
TABLE F.l
Asbestos-Cement Pipe Type Recommended for Internal Water Aggressiveness
Internal Water Aggressiveness
Highly aggressive Moderately aggressive Nonaggressive
Recommended Pipe Type*
t n
1 and 11
Type I--no limit on uncombined calcium hydroxide; Type II--per cent or less uncombined calcium hydroxide.
t The serviceability of pipe for such applications should be established by the purchaser in conjunction with the manufacturer.
TABLE F.2
Aggressiveness of Nonsulfate Acidic Soils to Asbestos-Cement Pipe
Water Conditions Within the Soil Environment
Minimum pH of Acidic Soils When
Using AsbestosCement Pipe
Essentially quiescent Mildly fluctuating Rapidly moving or
grossly cyclic
Type I
5.0 5.5
6.3
Type II
4.0 5.0
5.5
. TABLE F.3
Asbestos-Cement Pipe Type Designation Chemical Resistance to Nonacid {pH = 7.0) Soluble Sulfates in Water and Soils
Type Designation
i*
n
Chemical Resistance to Nonacid Soluble Sulfates in Water and Soils
Will be attacked to various degrees by all but the nonaggressive levels of sulfate concentrations in waters and soils.
Resistant to all levels of soluble sulfates.
The guideline criteria for sulfate resistance of Type I pipe were taken from the Concrete Manual. 8th edition. Bureau of Reclamation. 1974. Sulfate resistance here applies to all soluble sulfates regardless of the cation.
FOREWORD
vii
suitable for such use in Table F. 1. Aggres siveness of water is defined as follows.
a. Highly aggressive: pH + log (AH)< 10.0
b. Moderately aggressive: pH + \og (AH) = 10.0- 11.9
c. Nonaggressive: pH + log (AH)> 12.0
where pH = Index of acidity (or alkalinity) of the water--standard pH units. A = Total alkalinity--ppm (mg/L) as CaCCF. H = Calcium hardness -- ppm (mg/ L) as CaCCF. It should be recognized that water
that has a pH + log (AH) less than or equal to 10 is an extremely aggressive water and would be very corrosive to almost all materials found in a typical water system, including the plumbing in consumers' homes. Such waters should be treated to increase pH or hardness to protect the entire network of materials making up the system. If such water treatment is not undertaken, the manu facturer of each item used in the water system should be consulted for recom mendations regarding the use of his product in an extremely corrosive en vironment.
Note: The expression pH + log (A H) is a modification of the Langelier Index. It has been prepared so that the aggressive ness of the water can be determined easily. A reasonable comparison of the two would be as indicated below.
Highly aggressive water
Moderately aggressive water
Nonaggressive water
pH + log Langelier
(AH)
Index
<10.0
<-2.0
10.0-11.9 -2.0 to-0.1
>12.0
>0
1I.C.2 External water. Aggressive ness of external water (water within the
soil environment) is related to asbestos-
cement pipe in Table F.2. The guidelines
for the use of asbestos-cement pipe in
nonsulfate acidic soils are based upon
minimum pH factors alone. Asbestos-
cement pipe may or may not perform
satisfactorily in acidic soil environments
that have pH values below those listed in
Table F.2. To determine the suitability of
asbestos-cement pipe in soils having lower
pH values, each situation should be
evaluated individually and take into con
sideration all aspects of soil environment
that affect asbestos-cement pipe cor
rosiveness. II.C.3 Nonacid soluble sulfates--
internal and external. Aggressiveness of
nonacid (pH>7.0) soluble sulfates in water
and soils is related to the type designation
of asbestos-cement pipe suitable for such
use in Table F.3. Sulfate aggressiveness in
water and soil can be classified as indicated
in Table F.4.
11 .C.4 A cidsoluble sulfates--internal
and external Aggressiveness of acid
(pH<7.0) soluble sulfate waters and soils
to asbestos-cement pipe must be evaluated
independently.
Acid sulfate soils and waters, whether
the acid is inorganic or organic, must be
evaluated independently of the criteria
and guidelines set forth in Sec. II.C.2 and
II.C.3 and must take into consideration
soil permeability and other factors. Con
sult the manufacturer for guidance.
II. D Supplementary specifications.
The following information summarizes
the conditions and items that the purchaser
should consider when preparing his sup
plementary specifications. The section in
the standard where they can be found is
also listed.
1. The standard used; that is, A WWA
C400.
`
2. Affidavit of compliance, if required
(Sec. 1.3).
3. Type of pipe to be furnished (Sec.
2.3 and Foreword II.C).
viii FOREWORD
TABLE F.4 Sulfate Aggressiveness in Water and Soil
Water
Soil
Sulfate Aggressiveness Classification
Water Soluble Sulfates--ppm SO*
Water Soluble Neutral Sulfates--ppm SO.\
Nonaggressive Mildly aggressive Moderately aggressive Highly aggressive
150 and less 150-1500
1500-10,000 10,000 and greater
1000 and less 1000-2000
2000-20.000 20,000 and greater
TABLE F.5 Metric Conversion Factors
To Convert From US Customary Units
Inches (in.) X 25.40 X 2.54 X 0.0254
Feet (ft) X 304.8 X 30.48 X 0.3048
Pounds (lb) X 0.4536 Pounds per square inch (psi) X 6.9 Pounds per linear foot (Ib/lin-ft) X 1.488
To Metric Units
= Millimetres (mm) = Centimetres (cm) = Metres (m) = Millimetres (mm) = Centimetres (cm) = Metres (m) = Kilograms (kg) = Kilopascals (kPa) = Kilograms per metre (kg/m)
4. Class of pipe (Sec. 3.1). 5. Nominal inside diameter (Sec. 3.2). 6. Lineal feet to be furnished in stan
dard and random lengths (Sec. 3.3). 7. Number, size, type, class, lengths, and extent of machining of special short lengths (Sec. 3.3.3). 8. Whether inspection by the pur chaser (Sec. 5.1) and special mark ing (Sec. 6.1.4) are required.
Ill Major Revisions
Major changes to the 1977 standard that were made in this revision are
1. Soft metric equivalents have been included.
2. Explanations of the test methods for hydrostatic, flexural and crush ing requirements have been deleted and references have been made to ASTM C500, "Testing AsbestosCement Pipe."
3. A dimensional table of fittings for use with asbestos-cement pressure pipe has been added as Appendix A.
IV Metrication
The tables in this standard are stated in both US customary units and metric equivalents. Throughout the body of the standard, metric equivalents (rounded off) are set in parentheses next to the cus tomary units. Metric conversion factors are listed in Table F.5.
American Water Works Association
AWWA C400-80 (Revision of AWWA C400-77)
AWWA Standard for
Asbestos-Cement Distribution Pipe, 4 in. Through 16 in. (100 mm Through 400 mm) NPS,
for Water and Other Liquids
Section 1--General
Sec. 1.1 Scope
Sec. 1.2 Definitions
This standard covers three pressure classes of Type I and Type II asbestoscement pipe, 4-16 in. (100 mm to 400 mm) in diameter for water and other liquids intended to be laid underground in public and private rights-of-way.
1.1.1 Use. Asbestos-cement distri bution pipe is to be used in pipe systems having relatively unpredictable flows and many appurtenances that do not permit reasonable hydraulic analyses, including that for surge pressure.
1.1.2 Pressure classes. The pressure class designations of class 100, class 150, and class 200 are the same as those used in AWWA C401 (formerly AWWA H2), "Standard Practice for the Selection of Asbestos-Cement Distribution Pipe, 4 in. Through 16 in., for Water and Other Liquids."
The following definitions shall apply in this standard.
1.2.1 Inspection. Inspection of the pipe and the tests by the inspector.
1.2.2 Inspector. The authorized rep resentative of the purchaser, entrusted with the duty of inspecting pipe produced and tests performed under this standard.
1.2.3 Lot. A lot as used herein is defined as all pipe of any one class, type, and size manufactured on any one machine in 24 hr but not to exceed 300 lengths.
1.2.4. Manufacturer. The person, firm, or corporation that manufactures the pipe.
1.2.5 Operatingpressure. The max imum hydrostatic pressure to which the pipe will be subjected in normal operation after installation, exclusive of allowance for water hammer.
i
2 AWWA C400-80
1.2.6 Purchaser. The person, firm, corporation, or government agency enter ing into a contract or agreement to pur chase pipe according to the provisions of this standard.
Sec. 1.3 Affidavit of Compliance
Whether factory inspection has been required or not, the purchaser's supple mental specifications may require an affi davit of compliance from the manufac turer that the material furnished under the purchaser's order comply with all appli cable requirements of this standard.
Sec. 1.4 References
This standard references the following documents. They form a part of this
standard to the extent specified herein. In any case of conflict, the requirements of this standard shall prevail.
AWWA C401, "Standard Practice for the Selection of Asbestos-Cement Distribution Pipe, 4 in. Through 16 in., for Water and Other Liquids."
ASTM* C500, "Testing AsbestosCement Pipe."
ASTM D1869, "Specification for Rub ber Rings for Asbestos-Cement Pipe."
American Society for Testing and Materials 1916 Race St. Philadelphia, PA 19103
Section 2--Materials
Sec. 2.1 Composition
Sec. 2.2 Physical Requirements
Asbestos-cement pipe shall be com posed of an intimate mixture of either (1) Portland cement or portland blast furnace slag cement and asbestos fiber with or without silica, or (2) portland pozzolana cement and asbestos fiber. Both (1) and (2) can be with or without the addition of curing agents. The pipe shall be formed under pressure and cured. The finished pipe shall be free from organic materials.
2.2.1 Flexural strength. Each length of pipe 10 ft (3 m) or longer for pipe sizes 8 in. (200 mm) and less shall have the minimum flexural strength prescribed in. Table 1 when tested in accordance with the Flexural Test Proof Method as re quired in the latest edition of ASTM C500, "Testing Asbestos-Cement Pipe."
2.2.2 Bursting strength. Each length of pipe and each coupling sleeve shall
Nominal Diameter
in. (mm)
4 (100) 6 (150) 8 (200)
TABLE 1
Flexural Test Loads Total Applied Load--lb (N)
Class 100
lb (N)
1200 2800 5330
( 5340) (12,500) (23,700)
Class 150
lb (A)
1470 3700 7600
( 6540) (16,500) (33,800)
Class 200
lb (AO
1870 4900 10,130
( 8300) (21,800) (45,100)
A-C D IS T R IB U T IO N PIPE
Nominal Pipe Size
in. (mm)
4 (100) 6 (150) 8 (200) 10 (250) 12 (300) 14 (350) 16 (400)
TABLE 2 Design Internal Pressure and Design External Load*
Class 100
Internal Pressure
External Load
psi (,A Pa)
lb l tin ft (A N/m)
417 441 472 490 490 500 500
(2900) (3000) (3300) (3400) (3400) (3400) (3400)
4100 4000 4000 4400 5200 5200 5800
(60) (58) (58) (64) (76) (76) (85)
Class 150
Internal Pressure
External Load
psi (A Pa)
lb/ fin ft (A N/m)
616 632 653 650 658 650 654
(4200) (4400) (4500) (4500) (4500) (4500) (4500)
5400 5400 5500 7000 7600 8600 9200
(79) (79) (80) (102) (111) (126) (134)
Class 200
Internal Pressure
External Load
psi (A Pa)
lb/Iinft (k Njm)
809 815 824 826 830 826 825
(5600) (5600) (5700) (5700) (5700) (5700) (5700)
8700 9000 9300 11,000 11,800 13,500 15.400
(127) (136) (136) (161) (172) (197) (225)
*lt is necessary to apply a load factor (see AWWA C40I) to the three-edge bearing loads obtained in the crushing tests specified in Sec. 5.2.4 of this standard in order to correlate them to the field loads.
4 AWWA C400-80
have sufficient strength to withstand the design internal pressure indicated for its class in Table 2 when subjected to the hydrostatic test procedure specified in this standard.
2.2.3 Crushing strength. Each length of pipe shall have sufficient strength to support the design external load indicated for its class in Table 2 when subjected to the crushing test procedure specified in this standard.
Sec. 2.3 Chemical Requirements
Pipe shall be designated as either Type 1 or Type 11 according to its content of uncombined calcium hydroxide as de termined by the test procedures in this standard for uncombined calcium hydrox ide. The requirements for each pipe are:
Type I--no limit on uncombined calcium hydroxide.
Type II--1 percent or less uncombined calcium hydroxide.
Section 3--Design
Sec. 3.1 Pipe Classes
Pipe supplied under this standard shall be made in one or more of the following classes: 100, 150, or 200.
Sec. 3.2 Pipe Diameters
Pipe shall be made with nominal inside diameters of 4, 6, 8, 10, 12, 14 and 16 in. (100, 150, 200, 250, 300, 350 and 400 mm, respectively). The average inside diameter of a standard or random pipe length shall not be less than the nominal diameter by more than 5 percent.
Sec. 3.3 Pipe Lengths
Pipe shall be produced in standard, random, and short lengths. At least 90 percent of the total footage (linear metres) of pipe of any class, type, size, excluding short lengths, shall be furnished in stan dard lengths. The remaining 10 percent may be in random lengths.
3.3.1 Standard lengths. Pipe is cus tomarily furnished in standard lengths of 10 ft (3 m) or 13 ft (4 m) in 4, 6, and 8 in. (100,150, and 200 mm, respectively) sizes, unless otherwise agreed upon at time of purchase. Sizes 10 in. (250 mm) and greater are customarily supplied in 13 ft (4
m) lengths, unless otherwise agreed upon at time of purchase. A maximum of 10 percent of each pipe size may be furnished in random lengths of not less than 7 ft (2 m). Short lengths for making connections to valves, fittings, or structures and for making closures shall be furnished as specified by the purchaser.
Sec. 3.4 Couplings
A coupling shall consist of an asbestoscement sleeve of the same type and class as the pipe and two rubber rings or a device that has equal or betterjointing character istics, strength, and serviceability as that of an asbestos-cement coupling. The man ufacturer shall submit specifications and drawings of alternate couplings to the purchaser for approval prior to man ufacturing.
3.4.1 Amountfurnished. One coup ling of the same size and class as the pipe shall be furnished with each standard and random length of pipe.
3.4.2 Rubber rings. Rubber rings shall conform to the requirements of the latest edition of ASTM D1869, "Specifi cation for Rubber Rings for AsbestosCement Pipe."
3.4.3 Coupling areas. Coupling areas
A-C DISTRIBUTION PIPE
5
for all lengths of pipe shall be properly machined at ends or over their entire length to serve their intended purpose, as specified by the purchaser.
less than the manufacturer's standard by the tolerance listed in Table 3.
Sec. 3.5 Joints
Joints shall be capable of withstanding, without leakage, a hydrostatic pressure test as defined in Sec. 5.2.2.1.
Sec. 3.6 Wall Thickness
The wall thickness of the machined portion of any length of pipe shall not be
TABLE 3 Wall Thickness Tolerance
Nominal Pipe Size
in. (mm)
4-12 14-16
(100-300) (350-400)
Wall Thickness Tolerance
in. (mm)
-0.06 -0.12
(-1.5) (-3.0)
Section 4--Workmanship and Finish
Sec. 4.1 Imperfections
4.1.1 Interior surfaces. The inside surface of each length of pipe shall be free from bulges, dents, and tears that could result in a variation in diameter of more than 0.20 in. (5 mm) from the diameter of adjacent unaffected portions of the surface.
4.1.2 Exterior surfaces. Flaking on the exterior surface and edge of machined ends shall not extend back by more than 0.500 in. (13 mm) from the end, have a depth of more than 0.125 in. (3 mm) or
extend around the perimeter for more than 0.500 in. (13 mm) at any one location.
4.1.3 Straightness. Each length of pipe shall not vary in straightness by more than 0.05 in./ft (4 mm/m) of length when the variation is measured as follows:
Measure the maximum ordinate from the exterior surface of the pipe by placing a straightedge or line that exceeds the pipe length against the exterior surface and measure the maximum distance from the exterior pipe to the straightedge or line.
Section 5--Inspection, Testing, and Rejection
Sec. 5.1 Inspection
5.1.1 General Inspection by the purchaser shall not relieve the manu facturer of the responsibility to furnish material conforming in all aspects to the requirements of this standard.
5.1.2 Notification. If inspection is specified by the purchaser under para graph 5.1.4, the manufacturer shall notify the purchaser in advance of the date, time,
and place of testing of the pipe so that the purchaser may be represented at the test.
5.1.3 Access. The inspector shall have free access to those parts of the manufacturer's plant that are involved in work performed under this standard. The manufacturer shall afford him, without charge, all reasonable facilities for de termining whether the pipe meets the requirements of this standard.
6 AWWA C400-80
5.1.4 Testing. If inspection is speci fied by the purchaser, he may, at his option, witness any or all test phases. The pipe to be tested shall have passed the routine inspection and testing of this specification. The number of tests to be conducted for flexural strength (4, 6, and 8 in., or 100, 150, and 200 mm re spectively), hydrostatic proof (3y times class), and, when required, crushing strength shall be limited to 1 per each 300 standard lengths of each size, type, and class of pipe on the order. If uncombined calcium hydroxide tests are required, the number of tests will be one for each size, type, and class of pipe on the order. The purchaser or his authorized inspector may select the pipe to be tested. Retesting and rejection stipulations as shown in Sec. 5.3 shall apply.
Sec. 5.2 Physical Test Requirements
5.2.1 Test specimens. All pipe and couplings tested under this standard shall be in a normal air-dried condition when tested.
5.2.2 Hydrostatic tests. 5.2.2.1 Each standard, random, or short length of pipe and each coupling sleeve shall be tested under an internal hydrostatic pressure as shown for the proof test in Table 4 in accordance with hydrostatic proof test requirements of the latest edition of ASTM C500, "Testing Asbestos-Cement Pipe." Any pipe length or coupling sleeve showing leakage, sweat ing, or other defects shall be rejected.
TABLE 4
Hydrostatic Tests
Class
Proof Test*
psi (k Pa)
Lot Testf
psi (k Pa)
100 150 200
350 525 700
(2400) (3600) (4800)
400 600 800
(2800) (4100) (5500)
Every length per paragraph 5.2.2.1. fOnc per lot per paragraph 5.2.2.2.
5.2.2.2 From each lot that has passed the hydrostatic proof test, one standard length shall be hydrostatically tested to the lot test in Table 4 for that class in the manner specified in paragraph 5.2.2.1. Each length of the pipe so tested shall be retested in the manner and at the pressure specified in paragraph 5.2.2.1.
5.2.3 Flexure tests. Each standard length of pipe and each random length of more than 9.5 ft (2.8 m) having a nominal diameter of 4, 6, or 8 in., (100, 150, and 200 mm respectively), shall be tested in flexure in accordance with the latest edi tion of ASTM C500, "Testing AsbestosCement Pipe." Each pipe so tested shall support, without evidence of cracks or other defects, the applicable total load shown in Table 1.
5.2.4 Crushing tests. On lots con taining more than 100 lengths of each size and class, one length from each 300 lengths or fraction thereof, shall be tested for crushing strength. If inspection by the purchaser has been specified, the length of pipe to be tested may be selected by the inspector. From each selected length, one unmachined section of pipe 1 ft (300 mm) long shall be cut. This section shall be tested for crushing strength in accordance with the latest edition of ASTM C500, "Testing Asbestos-Cement Pipe." The test section shall not fail until the total load applied meets or exceeds the appli cable value shown in Table 2.
5.2.5 Machinesfor testing. 5.2.5.1 The machine used for the hydro static test shall have gaskets that seal the ends of the pipe, coupling, or pipe and coupling with factory assembled joint, but exert no end pressure. Couplings may be hydrostatically tested with a rubber blad der inside the couplings, and if so tested, each coupling shall have sufficient strength to withstand a test pressure of four times the class of the coupling. 5.2.5.2 The machines used for the flexure and crushing test shall be sub
A-C DISTRIBUTION PIPE
7
stantial and rigid throughout so that the distribution of the load shall not be appreciably affected by the deformation or yielding of any part of the machine.
Sec. 5.3 Retests (Physical) and Rejection
5.3.1 Crushing strength. The failure of any specimen tested for crushing strength to support 75 percent of the crushing load required in Table 2 shall be cause for rejection of that portion of the lot of that size,, type, and class manu factured during the same shift as the test specimen. If any specimen tested for crushing strength supports more than 75 percent but less than 100 percent of the crushing load, then two additional pipe sections of the same size, type, and class manufactured during the same shift shall be subjected to the same crushing test. The additional lengths may be selected by the inspector if inspection by the purchaser has been specified. The failure of one of these additional specimens to meet the full crushing strength requirement shall be cause for rejection of that portion of the lot of that size, type, and class manu factured during the same shift as the test specimen.
5.3.2 Hydrostatic tests. If any pipe subjected to the hydrostatic tests specified in Sec. 5.2.2.2 fails to withstand the specified pressure, then two additional lengths of the same size and class manu factured during the same shift shall be subjected to the same hydrostatic test. The failure of one of these additional lengths to withstand the specified pressure shall be cause for rejection of that portion of the lot of that size, type, and class manu factured during the same shift as the test lengths.
Sec. 5.4 Test for Uncombined Cal cium Hydroxide
The manufacturer shall perform this test as often as necessary to ensure com pliance with the requirements for un combined calcium hydroxide in Type II pipe when tested in accordance with the latest edition of ASTM C500, "Testing Asbestos-Cement Pipe."
Sec. 5.5 Test Records
The results of all tests shall be recorded and retained for one year, and shall be available to the purchaser at the place of manufacture.
Section 6--Marking and Delivery
Sec. 6.1 Marking
6.1.1 Standard and random lengths. Each standard or random length of pipe shall be clearly marked on the outside surface with the trade name, nominal inside diameter, class, type, hydrostatic test pressure, and date and shift of manu facture.
6.1.2 Short lengths. Each short length of pipe shall be clearly marked on the outside surface with the nominal inside
diameter, class, type, and the letter "T" to indicate that it has been hydrostatically tested.
6.1.3 Couplings. All component parts of each coupling shall be clearly marked for use with the pipe for which they are intended. Each coupling sleeve shall also be marked with the letter "T" to indicate that it has been hydrostatically tested.
6.1.4 Special markings. If factory
AWWA C400-80
inspection is made by the purchaser or his authorized inspector, then each pipe and each coupling sleeve shall receive an addi tional special marking of no more than three letters, as specified by the purchaser.
Sec. 6.2 Preparation for Shipment
All pipe and couplings, unless otherwise specified, shall be prepared for standard commercial shipment.
Appendix A
Dimensional Table of Fittings Ends Designed for Use With Asbestos-Cement Pressure Pipe
This appendix is for information only and is not a part of A WWA C400.
In the figures and tables on the follow ing page, the dimensions shown are for fittings to be used with asbestos-cement pipe having the end dimensions in Table Al. Dimensions for fittings for use with other asbestos-cement pipe end machin ing will be included should such design be established.
Fitting tolerances, where indicated, are required of the fittings manufacturer to establish proper control.
Rubber gaskets to be purchased from the pipe manufacturer.
Fittings shall be made of such materials as will provide service compatible with asbestos-cement pipe.
\
TABLE A1
Pipe Size
in. (mm)
4 (100) 6 (150) 8 (200)
10 (250) 12 (300) 14 (350) 16 (400)
in. A (mm)
5.36 7.63 9.83 11.96 14.16 15.93 18:01
(136) (194) (250) (304) (360) (405) (457)
Class 100
in. 3 (mm)
4.93 7.20 9.40 11.53 13.73 15.37 17.45
(125) (183) (239) (293) (349) (390) (443)
Note: A. B & C tolerances are +.05 in. (1.27mm) -.04 in. (1.02mm)
in. C (mm)
4.74 7.01 9.21 11.34 13.54 15.17 17.25
(120) (178) (234) (288) (344) (385) (438)
in. A (mm)
5.53 7.63 9.83 12.38 14.64 17.08 19.32
(140) (194) (250) (314) (372) (434) (491)
Class 150/200
in. B (mm)
5.10 7.20 9.40 11.95 14.21 16.52 18.76
(130) (183) (239) (304) (361) (420) (476)
in. C (Him)
4.91 7.01 9.21 11.76 14.02 16.32 18.56
(125) (178) (234) (299) (356) (414) (471)
All Classes
in. W (mm)
in. N (mm)
0.95 0.95 0.95 0.95 0.95 1.00 1.00
(24) (24) (24) (24) (24) (25) (25)
3.50 3.50 3.50 3.50 4.00 4.50 4.50
(89) (89) (89) (89) (102) (114) (114)
Note: All dimensions and tolerances are in inches, (millimetres).
A P P E N D IX
Pipe Size
in. (mm)
4 (100) 6 (150)
8 (200) 10 (250) 12 (300) 14 (350) 16 (400)
Class 100
in. D (mm)
in. D.3 (mm)
4.64 6.91 9.11 11.24 13.44 15.07 17.15
(118) (176) (231) (286) (341) (383) (436)
4.80 7.07 9.27 11.40 13.60 15.23 17.31
(122) (180) (236) (290) (345) (387) (440)
Class 150/200
in. D (mm)
in. D (mm)
4.81 6.91 9.11 11.66 13.92 16.22 18.46
(122) (176) (231) (296) (354) (412) (469)
4.97 7.07 9.27 11.82 14.08 16.38 18.62
(126) (180) (235) (300) (358) (416) (473)
Note: Consult pipe manufacturer for pipe tolerances.
Dj D3
\0
AWWA C400-80 10 May 1982
Department of Defense Acceptance Notice
This nongovernment document was adopted and approved for use by the Department of Defense (DoD) on 10 May 1982. The American Water Works Association has furnished the clearance required by existing regulations. Copies of the document are stocked by DoD Single Stock Point, Naval Publications and Forms Center, Philadelphia, PA 19120, for issue to DoD activities only. Contractors and industry groups must obtain copies from AWWA, 6666 West Quincy Ave., Denver, CO 80235.
Title of Document: AWWA Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16 in. (100 mm Through 400 mm) NPS, for Water and Other Liquids
Date of Specific Issue Adopted: June 15, 1974 Releasing Industry Group: American Water Works Association
Custodians: Army--ME Navy--YD Air Force--99
User Activity: Navy--MC
Military Coordinating Activity: Navy--YD
Project No. 5630-0088
FSC 5630
4P--7.5M--43400--8/ 81--LL