Document MGaBewR7VDxZGwJMKV4rQ19nx
852
CHAPTER 54
1965 Guide 'AndData B6ok
Unit Ventilators and Unit-Heaters
853
Fig. 7 .... Propeller Fan Unit Heater--Horizontal-Blow Type
Gossification.
- The various types- of unit heaters in present use afly be classified according to one or morn mith<vt^, -
usu
Rgl 9,..:. Floor-Mounted Centrifugal Unit Heater-*-'
Cabinet Type
'V
_1- By heating medium: Under this classification there - are
five heating media to be considered: (a) steam, (b) hot'water,
(c) gsa, (d) oil, (e) electric.
->
'By type of fan:] Under this classification there are two
types rf tens to be -considered: (a) propeller and (6) centrif
ugal:- Propeller fan units may be of the koriamtaLbloa - or
down-biota type. Centrifugal fan imita may' be of the gmiw
cabinet- type or larger mdustrial type.'- Either- may.-be ar
ranged for the delivery of air horizontally, or vertically. up or
Unit heaters located overhead permit 100 percent utiliza tion of floor space. They may often be used to advantage in specialized applications requiring spot or intermittent hoaring such as the blanketing of outside doom in industrial plants or in corridors and vestibules. Unit heaters are alaft employed where filtration of.the heated air is required,,and- they may be modified to provide .ventilation where the introduction of.out-,
3. By arrangement of dements: Under thin ' classification there'are two types of units .to be considered:' (o) the drawUumgh.type, in which the-fan draws air-through, and ft) the oioto-tkrougk type,.in which the ten,blows air through the heat ing element. Direct-fired unit heaters are always of the blowthrough type.
Application
door air is, required.
,
Unit heaters are principally used for hearing .cnmmerrnnl
and industrial structures such,, as garagew, factories, ..ware
houses, showrooms, stores, and laboratories,
for-heating
corridors, lobbies, vestibules, and similar auxiliary,spaces in
all types ofjbuikUngs.
,,
,
Unit heaters may- be applied to.a.number-of,industrial
Unit heaters have three principal characteristics, as dis
tinguished from gravity"heating units: (1) relatively large
feating capacities in compact casings, (2) the ability to'pro-
ject heated air in a controlled manner over a <*ingidrfthu
distance, and (3) a relatively low installed cost per' Btu
output.- They are, therefore^' usually employed in applications
.where, the, heating capacity requirements, or the' physical
volume of the heated space, or both, are larger than: those'
that can be adequately or economically handled by gravity
heating unit8.
.- > .
Where the heating capacity requirement is large, the in stallation of a small number of unit heaters will usually
processes, such-as drying and curing, in which the,use,,of' heated air in rapid circulation with-uniform .distribution-is of particular advantage. They may be-used for moisture absorption applications, such as fog removal in dye houses, or for the prevention of condensation on ceilings or other-cold sur faces of buildings in which process moisture is released- When. such conditions are, severe, it is necessary that the units be equipped to. draw air from -outdoors in sufficient, volume to provide a rapid air change and that they operate in con junction with exhaust ventilators or fans for eriumsting the moisture-laden air. (See discussion of condensation in Chap ter 23.)
prove more economical than will the use of a multiplicity of gravity heating units of.the same total capacity. Where the
Factors Affecting Application,-'
volume of the space is -large, and especially where ceiHngp
There are five major factors to be considered in the ap-
are high, unit heaters can provide comfort through uniform-, 'plication of'unit heaters: (1) .the-heating medium to be
heat distribution, and can provide economy of operation by employed, (2) the type of unit, (3) - the';location of the unit
confining the heat to the occupied zone and eliminating for proper heat distribution, (4) the permissible sound level,
stratification in a manner which is .difficult to attain with : -, and (5) the degree of filtration required for the air circulated. gravity radiation.
uoToa--
SUPPLY.
--
TING ! / ELCUCMT
TrTT: Tr-rf TAN / ^ OUTLET'
Fig. 8 .... Propeller.Fqn.Urnt Heater^rDown-Blow.Type
The selection of the proper heating medium`is usually de^
termined on an economic basis
requires an examination
of the first cost; the'operating cost, and the conditions of'use.'
Steam'and hot water unit heaters are relatively inexpensive^
biit require a boiler plant and piping system, the "per-unit
cost of which generally decreases as the number of.units in
stalled'increases: Gas- and oil-fired'units are mdre'costly,
but the fuel lines and vent flues required, are'comparatively -
inexpensive, and the overall installation cost'will usually-be
lower when a small number of units is used. Electric'units are
relatively inexpensive to purchase and install but are
usually associated with a high operating cost per Btu output;
unless electric rates are very favorable.., -
, i;
.. Steam ar hotiwater units are most frequently .used in new
installations in which the number of units is large.enough,to
justify the expense of a new boiler and piping system,.and.
in gristing installations or additions; in .which the;system is
of, sufficient-capacity to .handle the additional- load. High?
pressure steam or high-temperature hot water, units are-usu
ally employed in larger installations or, where-a high tern?,
perature; medium .is also required,,-for - process^_work.
Low-pressure steam and conventional bot water . units are
usually installed in smaller installations and in those pri
marily concerned with comfort heating. -.
........ . j.
Gas-fired and oil-fired unit heaters sire usually preferred
in installations in which the number of'units required does
not justify the expense of a new boiler and-piping system,
where the space or the'time required`to'construct a new
boiler plant is not- available, or where individual metering
of the fuel-supply is required; as.in a shopping center..Gasfired units are usually of the horizontal propeller type or the industrial centrifugal type. Oil-fired units are-largely of.the industrial :centrifugal . type. Some codes limit the use of di rect-fired unit heaters in certain applications. ;, '
Electric unit heaters are used where low cost electric power is;available, or-for isolated locations, intermittent use, sup^ piementary heating,' or .temporary service requirements. Typ ical applications are ticket booths, -watchmen's: offices,- fac tory offices, locker rooms, and other isolated rooms scattered over , large areas. Electric units are particularly useful in isolated and untended pumping stations or pits, where they may be thermostatically, controlled to prevent freezing tem peratures.
Type. of; Unit .
Propeller /an'units are usually used in- free-delivery ap plications where the heating capacity and distribution1 re quirements can best be met by units-of moderate output, used singly or in multiples,-and where filtration of the heated, air <is not required. Horizontal-blow units are usually asso ciated with low to -moderate ceiling heights. Down-blow units are employed in high-ceiling spaces and-where-floor and= wall space limitations dictate an out-of-the-way location for the heating equipment.
.: Fig.. 14 .. .> OflrFired .Centrifugal Fan .Unit Heater---, ' Floor Mounted