IS ASKAREL PHASING OOTT
WHAT IS ITT
''
Ilia term *askaral" as defined by IEEE, ASTK, and the National Electrical
Code generally describes a broad class of fire-resistant synthetic chlorinated
hydrocarbon Insulating liquids. By controlling the composition of these mix
tures, a manufacturer can obtain desired combinations of thermal, chemical,
and dielectric properties that result in Insulating liquids which have greater
resistance to oxidation and fire resistance than mineral oils.
The Monsanto Chemical Company is the sole supplier of polychlorinated (
biphenyls (commonly referred to as PCB). Under'their trade name "Aroclor", ^
they also mix this dielectric fluid with chlorobenzenes to produce fyranol
and Inerteen, the trade names of askarels used by the General Electric and
Westinghouse companies respectively.
CHARACTERISTICS. AND USES
Askarels jre one of the best liquid insulations developed by science
if and accounts for its popularity since they were introduced h5 years ago.
Askarel is chemically stable, fire-resistant, heat stable, non-corrosive,
non-conducting, and has a high dielectric strength under operating conditions.
Beoause of these characteristics, they-have been used for many industrial
and consumer applications. Askarel also gives electrical equipment the
critical advantages of reliability, long life, compactness, and low cost.
Because of its fire-resistance, askarel equipment has been permitted
by the National Electrical Code and Insurance companies to be located Inside
of buildings with its installation savings as well as the safety aspects.
Arcing in askarel, however, will breakdown askarel and liberate mostly
hydrogen chloride and small amounts of carbon.
2 -J , _ 'V (/. --- / ' 1 d t.
This arc-formed gas from
MGNS 071115 ')
transformer askarel is non-flmmable and non-combustible. The carbon will discolor the liquid and reduce Its dielectric strength. Askarel-flllad Interrupter switches were used years ago In Industry, but have been super seded by the air type.
The following use categories or applications are Important to know because of the environmental and ecology storyt
1. Open, e.g. paints, printing inks, paper coatings, plastics. carbonless duplicating paper, calking compounds, asheslves, nonflammable
2. Nominally closed application systems, e.g. hydraulic, heat transfer, and lubricating fluids.
3. Closed applications, e.g. sealed transformers and capacitors.
ENVIRONMENTAL AND ECOLOGY CONSIDERATIONS Although askarels have been In use for 43 years. It was only recently
that there was evidence to Indicate that PCBs were rather widely dispersed In the environment, Including terrestrial and aquatic environment, although the largest amount is present in landfills and dumps.
Askarels are chemically stable--Incredibly stable, which is part of the environmental problem, i.e. they do not readily degrade. It persists, and if discarded in the environment in sufficient quantities, it could result in a gradual accumulation in certain ecological systems. This was the reason FCB was put on the Environmental Protection Agency (EFA) Toxic Pollutant Ust. Many industrial materials more dangerous to handle and more immediately harmful are not on that list.
About 1971, widespread newspaper headlines were generated whan large
MONS 071116
P- 3
quantities of fowl in Minnesota and in North Carolina and large numbers of
eggs in several locations were destroyed after they were found to be eon*
taminated with high concentrations of PCB. In each ease, the source of
contamination was traced to a Claja"2 (nominally closed system), leaking
heat exchanger cooling system in a fish meal processor's plant which appar
ently went unnoticed for some time. Unfortunately, this fish meal was used
as an ingredient in a commercial poultry feed product.
PCBs were first identified as potential food contaminants in 1966.
These were in residues of fresh water fish attributable from various sources,
from carbonless paper (Category #1), and food packaging materials, some of
which migrated into packaged food.
It is unfortunate that the scientific area did not have sensitive and
meaningful diagnostic evaluations in the earlier years. It was a Dr. Jensen
of Sweden (1966) who first referred to PCB as a new pollutant in our environ
ment (36 years since the commercial use of askarels).
In 1971, representatives of several government agencies established
an interdepartmental task force to coordinate the scientific efforts of
the government aimed at understanding the family of PCB chemical compounds.
(I)
Their report '
UOr/SH'l^ represents and reflects the position of the agencies
of the Federal Government.
That task force reviewed all of the available scientific Information
on various aspects of the PCB problem and found much data that it regarded
as inadequate and many questions that remained unanswered. But on the basis
of available information, the task force concurs on the following findings,
conclusions, and recommendations> (They list nine items but only a few are
listed here.)
MONS 071U7
p. A
1. "PCBs should ba restricted to essential or non-raplaceable uses which Involve minimal direct human exposure since they can have adverse effects on human health. There currently are no toxicological or ecological data available to Indicate that the levels of PCBs currently known to be in the environment constitute a threat to human health, but additional ex periments are underway to evaluate the Impact of low level, long-term exposure to PCBs."
'll 5. Housekeeping Is particularly Important In the manufacture, use. and disposal of PCBs/ Note especially their following recosnendatloni 6. -The use of PCBs should not be banned entirely. Their continued use for transformers and capacitors In the near future Is considered necessary because of the significantly Increased risk of fire and explosion and the disruption of electrical service which would result from a ban on PCS use. Also, continued use of PCBs In transformers and capacitors pre sents a minimal risk of environmental contamination - -
n 9. More scientific Information about PCBs Is needed, and several government agencies are seeking It through research. The task force recognises that the scientific basis of much of our knowledge must be strengthened through research. The total exposure of a human being to a given substance from all sources--air, water, and food--must be considered, and interactions of FCBs and other substances within and outside the body must be evaluated. Similar consideration must be given to the other body organisms." And, the report goes an to state that the current soientlflo knowledge ln.d from laboratory animal experiments if often Inadequate to allow
,,ONS 071118
P- 5
reliable interpretation of the data In tarns of possible affacta on nan.
scientific basis for Interpreting such tests must ba Improved bacausa
of tha sparsity of knowledge about PCBs in the environment.
'
It is not surprising that based on the above government report as wall
as other information that industry does not agree with many of the PCI
proposed rules, regulations, or standards; they are not practical and are
not based on ecological facts, e.g. available data do not support categor-
icing PCBs as a "highly toxic" material, nor setting standards on the basis
of an arbitrary ha2ard rating; and the maximum recommended concentration
of PCBs in fresh water is a meaningless number that is not supported by
convincing ecological data.
When questions about the effect of PCBs on the environment first sur
faced, the Monsanto Company--the sola United States manufacturer of PCB--
reviewed its product line and their applications. They then took steps
to reduce the entry of PCB into the environment.
Monsanto Tgrba-g*.stopped the sale of PCB to applications in the first
two categories, l.e. open and nominally closed applications. This, in
itself, decreased their PCB outpul
the applications which caused.*
Today, the.PCB manufactured by Monsanto is sold only to tha electrical
Industry where it is used in closed aystems as a dielectric fluid in trans
formers and capacitors--applications where there are no known acceptable
aubstltutes.
Housekeeping is particularly important in the manufacture, use, and
a
fluids.
MCNS 071U9
'
Thus, the situation today is drastically different from conditions which existed only four years ago: First, the amount of FCB used is only
h-/r
about^dus to eliminating the open and nominally closed applications! and, second, is carefully used in the United States by less than 50 companies in their use in sealed electrical equipment. Prior to 1971, there were thousands of users.
What is needed is a broader educational program directed to users of
PCBs to assure proper handling and disposal.
WHAT ARE THE ALTERNATIVES TO ASKARELT
Many companies are working on substitute fluids which will hare the
attractive characteristics of askarels but without their environmental
problem.
Much work has already been done for capacitor fluids; Honstanto has
in service a new liquid--1016--which retains a high dielectric constant
and yet is^biodegfadable. General Electric has a liquid for small capacitors
as Econol, and Dm Chemical has an alkylated ehlorodiphenyl oxide fluid
which also'pot a PC3; both of these are In the market development stags. -/!> *-- h ***
I* has- been in use for several years but that is hardly long enough time*
for adequate testing.
^
-
itecj .QMt'* -
Silicon* ` fluids* ^ --T*
'
Che of the attractive liquid chemicals that may replace askarel for
transformers is^silicone fluid--dimethyl slloocane, a silicone oil. These
are manufactured by at least four United States companies with Dow Corning
and General Electric the two major sources. Silicone fluids have many of tha desirable electrical characteristics
HONS 071120
of askarel and yet ere not toxic. The excellent dielectric properties of silicone fluids ere e consequence of their unique chsmlcel structure. Basically, there Is nothing In the silicone structure that can provide any thing but good electrical properties) except gross contamination or eater.
Silicons fluids are available In a wide range of viscosities and for nanv applications. Companies have seroed-ln for a viscosity around JOcs whloh is a compromise in terms of flash point about 550? and eith a fire point higher. (Askarel has no flash point.)
Silicone fluids have low toxicity and physiological inertness; for example, their use is permitted by the Food t Drug Administration (FDA) and are currently being used in a wide variety of medical and pharmaceutical
The silicone fluids are used where their' general inertness is an essential property. They are compatible with most of the materials used in existing askarel transformers with the exception of silicone rubber which is sometimes used in gasketing. (The silicone fluid acts as a plasticizer for the silicone rubber causing it to swell.)
Silicone fluids will burn under the right conditions, so they cannot be classed as "nonflammable1' like askarel. They will burn only if the flame or source of heat is continuous; if that is removed, the silicone will cease to bum. Therefore, they might be classed as self-extinguishing.
CL does not approve or reject liquids for use in electrical test equipment, nor do they test or list any liquid-filled electrical equipment. However, they do provide a classification service of flaamabillty rating. A comparison of a few fluids is included here!
HONS 071121
p. 8
nmi
. EtoHalllix, Patent
Ither Mineral oil (Transformer)
Silicone oils (Transformer) (jOcs) Askarels
100 10-20 4-5
2-3
Thus,
transformer silicone oil is close to askarel In this Important
rating. C<_
Also, silicone oil has mm unique characteristic which may have a
special significance for transformers. Since most transformer faults start
as tum-to-tum faults, the arc breaks down the fluid forming gases and
teml-solld residues which remain in suspension and are relatively conductive
reducing the dielectric strength and snuffing out the arc.
While there Is a considerable amount of data available relating to .
the performance of silicone fluids under dielectric stress, there are many
voids In the Information which must be filled in order to develop confidence
In the use of the fluid for an acceptable normal life of liquid-filled trans
formers; specifically, considerably more in-service installations in various
Industrial and utility environmental locations.
Dow Coming has had several of their load-center type transformers
retrofitted with silicone oil (50es) the last few years to gain emparlance.
Their future plant transformers will use silicone oil. Thus, this will
help fulfill the experience gap. In most cases, there should be only a
few parts to be replaced during retrofitting, but check with the transformer JLr*
manufacturer. The change In the transformer rating should also be checked;
It may be about 10 percent^due to the difference In heat conductivity and
viscosity of silicone oil.
"5. Japanese National Railway has used silicone oil-filled transformers
on their electric coaches for about five years with good results, but these
required several design modifications.
HONS 071122
" A+ fh*-
'Aaz.
--,
'//t-o-Ja h ,/pCa.-w / <nj*~
p. 9
The silicone fluids hairs bean used for many years In specialty uses, primarily for radar, but that service experience, while helpful, will not qualify the fluid for larger ratings for industrial service (OSHA)
One vary important area is the UL, Code,and insurance companies' accept ability of silicone oil-filled transformers for indoor and other locations presently approved by these groups for askarels. That will involve testing and on-site experience. As a suggestion, these groups should consider the tentative approval of silicone fluid applications in specified physical and environmental locations to obtain the experience. The authflr further suggests an Investigative and experience program by manufacturers^ users, UL, and insurance companies to obtain Information useful in determining if such transformers can replace askarel units--either for all or only specific locations.
One disadvantage of silicone fluids is its cost--about twice that of an askarel fluid; e.g. on a typical 1000-kVA. indoor load-center type trans former, the additional cost is 8 to 10 percent for the liquid only. There may be additional costs--or savings--but that can only be determined on design --------- basis.
Of eourse dry-type transformers are and can be used to replace askarelfllled transformers; practically all of these are the so-called "load-center* units for the construction, Industrial, and seme utility applications-- usually with primary voltages up to 15 kV and low-voltage utilization below 600 volts. Here are seme comparisons of these various types of transformers
MQNS 071123
p. 10
GENERAL COMPARISONS OF VARIOUS TYPES OF TRANSFORMERS
(1000 kVA)
Askers!
Dry Open
Typa Scaled
Gas
fries - relative
1.0
1.25
1.25
2.0
Wt. (lb) 5/15 kV
5400
6300
4000/5400 8300/9000
OL Capacity 750-2000.kVA 2500 kVA
15% 15% 33 1/3% None 25% 25% 33 1/3* None
BIL 5/15 kV
60/95
60/95
25/50
60/95
Sound level, dB
w/o fans running
60
60
65
64
with fans running
67
67
67
_
MONS 07U24
p. 11
EXPLOSIONS In tha last year or so "explosion" tests were conducted In Japan and
by ono miSSHESBm transformer manufacturer In the United States comparing transformer mineral oil, askarel, and d? silicone oil fluids. Tha fluids vara tested in small tanks with a loose cover and "shot" with 4000-5000 amperes at 4600V.
Not surprisingly, the covers blew off. (Such performance was known many years ago.) Such tests are not representative of actual operation. Such explosions do occur occasionally on exposed utility power systems, but they are rare on industrial service.
Transformer failures are usually associated with tum-to-tum failures and limited fault current and not the catastrophic magnitudes of the above tests. Hanufacturers offer various sensors and devices to detect incipient faults as well as severe faults. The author knows of only one such cata strophic occurrence--in that case, lightning hit an askarel transformer on the roof of a building--but there was no fire damage. A check with a major insurance company confirmed the scarcity of such accidents.
IS A MW LIQUID DIELECTRIC THE AHSHERI
Much emphasis is currently being directed to the use of silicone oil
in place of askarel. But, is that the right or only solution?
It may be that a new non-llauld transformer will emerge. Several
European manufacturers and at least one U. S. manufacturer offer such a
transformer in some of the lower load-center kVA ratings1 in
cast-
eoil design. Currently, such designs are difficult to manufacture except
in small ratings in the 100-500 kVA range. (Qgmaa^pap^HmamaMmmaam
HONS 071125
'More manufacturing development work is needed. Another alternative is a modification of existing open dry-type aa-c,
transformers for more universal applications. (The sealed-dxy^type is too large, too heavy, and too expensive for general use.)
CONCLUSION Unless the EPA suddenly prohibits the use of askarel, it is the
author's opinion that this fluid will continue to be used in transformers and capacitors until new liquid(s) become available and have been sufficiently
of tested for safety to obtain approval $9 the necessary bodies.
Askarel units have given excellent service over the past 45 years. And, with the present restriction to sealed equipments ^mCjn fr trans-
o--/*J' formers and capacltors^md carefully controlled by the equipment manu facturers along with the much better housekeeping in handling the liquids, there should be a minimum chance of loss to the environment.
One factor which may**WWFSBi effects* the use of askarel-fllled transformers is a new policy of indemnification by the buyer to the seller. The wording of the Indemnification contract may vary, but essentially it applies to any and all liabilities and expenses, including actions, suits, proceedings, investigations, instituted or Issued by any governmental agency or body. This includes the handling, possession, use, or disposition of askarels which may contaminate the environment.
The government should restrict the Import of askarels for use in olosed systems only as is true domestically.