, 618 (JHAPTER 23 1957 Guide Panel Heating the temperature of the water in the system must be high enough to produce the re' quired output from that panel. 619 Room A B C Available Panel Area Sq ft 132 127 306 Required Panel Output (q,,) ' Btu/(hr)(sq ft) 25. 19.7 26.1 Step S. Panel Surface Temperature From Fig. 16 find the panel surface temperature needed to yield the required heat output to each room, using the output determined in Step 2 and the design room air temperature. Floor panel surface temperatures in excess of about 85 F are not recommended because of the probability of discomfort to the feet. If the required heat output cannot be obtained from an 85 F floor panel, heat losses should be reduced or sup plementary heating should be provided. Room A B C Panel Subface Temperature (lp) 85. F 82.5 F 85.3 F Step 4. Downward and Edgewise Heat Flow a. Determine the temperature of the surface of the concrete slab (t.) by adding to the panel surface temperature, the temperature difference caused by the thermal resistance of the floor covering, if any: K = G -f (?,, X rnc) (12) The value of (r,,c) for various floor coverings is given in Table 4. Room A B C fp 85. F 82.5 F 85.3 F 9 Toc 25. 0.8 19.7 0.8 26.1 0.8 t. 105. F 98.3 F 106.2 F b. .Determine the downward and edgewise heat loss coefficient C from Fig. 17 for the insulation to be used. Insulation with a conductance of 0.4 Btu per (hr) (sq ft) (F deg) extending two feet below the slab results in a slab downward and edgewise heat loss coefficient of 0.97 Btu per. (hr) (ft) (F deg) c. Apportion the downward and edgewise heat loss uniformly across the panel as follows: P X C,(t. - lo) Qde Ap (13) Panel. Construction Spac ing in. Thermal Resistance (F deg)(sq ft)(hr)/Btii Heat Flow Ratio ju/4d or qu/qi. 1 3 5 10 4 in. Concrete Slab--2 in. Cover up down .up down up down up down **ua rda raa . rda rQ8 rda Ma in. (nom.) non-ferrous tube 9 12 0.57 0.73 0.52 0.68 0.46 0.58 0.84 1.16 0.43 0.54 1.17 1.65 0.42 0.51 1.97 2.86 Vi in. (nom.) ferrous pipe or % in, (nom.) nonferrous tube .9 12 0.49 0.63 0.42 0.55 0.41 0.50 0.66 0.93 0.39 0.48 0:90 1.30 0.38 0.46 1.80 2.35 6 in. Concrete Slab--2 in. Cover in. (nom.) non-ferrous tube H in. (nom.) non-ferrous tube M in. (nom.) ferrous pipe 1 in. (nom.) non-ferrous tube or 1 in. (nom.) ferrous pipe 9 12 0.59 0.70 0.78 0.90 0.47 0.60 1.05 1.40 0.45 0.56 1.39 1.97 0.43 0.54 2.25 3.21 '9 12 0.51 0.61 0.43 0.08 0.78 0.54 0:87 1.23 0.41 0.51 1.13 1.63 0.40 0.49 1.78 2.61 9 12 0.47 0.63 0.55 0.71 0.40 0.50 0^77 1.07 0.39 0.48 0.98 1.44 0:38 0.46 1.50 2.36 . 12 15 0.59 0.73 0.66 0.83 0.48 0.57 0.98 1.21 0.46 0.54 1.30 1.73 0.45 0.51 2.11 2.74 ~~~r - 1 uru/t itPCiOtUIMA} Assume a tentative pipe or tube size and a spacing for each panel, choosing closer spacings and larger pipe or tube when higher heat outputs are required. From Table 3, find the thermal resistance (r,,.) of the slab of each panel, using heat flow ratios (?n/?iie) calculated from the flow rates determined in Steps 2 and 4, interpolating as required.. To the slab resistance (rul), add the resistance of the floor covering (foe , Step 4) to obtain the panel resistance to upward heat flow (r,,). Room Pipe or Tube Spacing <7u/<?de ruc ru . A 9 ins. 25 iO " 141 0.47 0.8 1.27 B 12 ins. 19.7 9.--0 = 2.19 0.55 0.8 1.35 C 9 ins. 26.1 -- = 3.68 0.40 0.8 1.20 All rooms: H-in. pips or $<-in. tube; 4-in. ooncrete slab. mean water Temperature . For the required panel output (qu) found in Step 2, the panel resistance (r,,) found 'n Step 5, and the room air temperature (t), find the mean water temperature (U)' from Fig. 16. Room A B C P 23 12 21 fa -- oa 105- F 98.3 F 106.2 F Av . 132 127 306 $d< 17.7 9.0 7.1 _____ Room A B C fmw 116.5 109.0 116.5 -. I n i I a