CHAPTER 45
1960 Guide
necessarily i"mii that corrective equipment must always be installed, but in most cases it is desirable to determine what advantages may be gained by improving the power factor. With purchased power, if the rates include a clause embody ing a penalty for low power factor, or a bonus for high power factor, the saving in power costs may often make a very good return on the investment required for the corrective equip
ment. Synchronous motors are used to drive fans, blowers, pumps,
compressors, and other applications. Compressor applications having a high peak torque require the use'of flywheels to smooth out power peaks, and should always be referred to the electrical manufacturer for recommendations.
Synchronous motors are provided with built-in damper windings on the rotor and operate during the starting period similarly to squirrel-cage motors. After the motor is nearly up to speed, field excitation is applied and the motor draws into step at synchronous speed. After excitation is applied, the motor runs at exactly constant speed and will remain at this speed until a load approaching the pull-out load is reached, whereupon the motor pulls out of synchronism and
stops. In applying synchronous motors, consideration must be
given to the torque the motor c-a-n develop on pull-in, that is, at the instant when field excitation is applied. Table 5 shows typical application requirements of synchronous motor drives, listing starting, pull-in, and pull-out torques.
Multi-Speed motors provide flexibility in many types of drives. Synchronous motors can be furnished only with a 2 to 1 ratio in speed, single-winding. Squirrel-cage induction mo tors may be 2-, 3-, or 4-speed. Two-speed induction motors are usually of single-winding type, having a 2 to 1 speed
ratio such as 600 rptn and 1200 rpm, or may be double winding. Three-speed induction motors are always two-
winding, and four-speed motors are usually two-winding with
a 2 to 1 speed ratio in each winding. Motors can be provided in constant torque, varying torque, or constant horsepower
ratings. The constant horsepower type of motor is consider
ably larger
the constant torque motor, due to the fact
that the
horsepower must be developed at either reduced
speed or high speed. In selecting two-speed motors for fan, pump, blower, or
compressor applications, it is usually found that two-winding
motors are more expensive than the angle-winding type. The
control cost for two-speed, two-winding motors, however,
is more economical, and therefore the combined price of both
motor and control for the two-winding motor is only slightly
higher. Because of the improved performance of the two-
winding motors, and because of the factor of safety provided
by two independent windings, the increased cost is frequently
worth the difference.
Single-phase Motors
Single-phase induction motors have auxiliary windings or devices for starting, and are classified by the method used.
Capacitor-start motors develop high starting torque in fractional horsepower ratings, and moderate starting torque in larger ratings. They are used for constant speed drive such as fans, blowers, and centrifugal pumps. During the starting period, a winding with a capacitor in series is connected to the motor circuit and when the motor comes up to speed, a centrifugal switch cuts the capacitor and second winding out
of the circuit. Tiro-value-capacitor motors develop high starting torque
Table 5 .... Typical Application Requirements of Synchronous Motor Drives Showing Starting, Pull-In, and Pull-Out Torques
Application
AWftorf of Connecting Motor to Load
Storting Condition*
Storting
Ton*PwO-to Pvtt-Otrt
femorir*
Fans
Exhaust aod venti Coupled or belted lating
Usually loaded
50 60-125 150 WR* of fan must be considered
Cycloidal positive
Coupled or engine Unloaded type
40-60 40-60
150 Two-speed motors sometimes used
Blowers
Blowing engines re Engine-type ciprocating
Unloaded
40 40-60
Turbo high speed
Direct connected or Unloaded (in
step up gear
take closed)
30
50
150
150 WR* of blower must be considered
Air
Engine-type
Unloaded
40 30 150 Flywheel effect im
portant
Ammonia and am High speed--belted Unloaded (by 40 30 150 Flywheel effect im
monia booster
Low speed--engine- bypass)
portant
type occasionally
Compressors
coupled
Freon
High speed--belted Unloaded (by
Low speed--engine
bypass)
45
50 150 Flywheel effect im portant
Gas reciprocating
High speed--belted Unloaded (by
Low speed--engine
bypass)
40
30 150 Flywheel effect im portant
Motors and Motor Controls
employing a starting capacitor and a running capacitor. The starting capacitor gives high starting ability, but is suited for short time operation only, and is cut out for the running condition by a centrifugal switch. The running capacitor gives high efficiency at full speed. These motors are used on compressors, reciprocating pumps, and similar equipment which may start under heavy load.
. Permanent-split-capacitor motors have low starting torque and are ideally suited for small fan drives. Operation is similar to the capacitor-start motor, except that the capacitor is not cut out when running. These motors, when equipped with a high-slip rotor, may be used for adjustable-speed operation by employing line voltage control, or a tapped winding.
Repulsion-start Induction-run motors develop high start ing torque. The motors have a wound rotor connected to a commutator for starting. A centrifugal switch shorts the .commutator bars when the motor comes up to speed to ob tain a winding approximately like the squirrel-cage in its function. These motors are suitable for applications, such as industrial compressors, requiring high breakaway torque, and where commutator and brush noise are not factors.
Split-phase motors have a high-resistance auxiliary winding which is in the circuit during starting, but is disconnected through the action of a centrifugal switch as the motor comes up to speed. Under miming conditions it operates as a singlephase induction motor with one winding in the circuit. These units are available in fractional horsepower ratings and are ideally suited for fan duty.
Speed-torque characteristics of single-phase motors are shown in Fig. 4.
Pud-voltage starting of single-phase motors is general practice, but since mo6t of these motors are connected to secondary distribution systems located in light-load density areas, power companies check carefully the starting currents in order to prevent objectionable voltage dips. This is par-
663
ticularly important for motors started frequently, such as those controlled by pressure or temperature-sensitive devices and applied to refrigerators, stokers, oil burners, and water pumps.
Tim report of a joint committee of AIEC-EEI-NEMA recommended three application rules taking into account the greater annoyances resulting from frequent motor starting during lighting hours against infrequent starting at any time. Table 6 shows typical applications of these rules which are becoming widely accepted for full-voltage starting. Rules 1 and 2 apply to general use.
Rule 1 limits the locked-rotor current to 20 amp at 115 volts, and 25 amp at 230 volts when automatically controlled (usually frequently started) motors are used. Rule 2 permits twice these values when manually controlled (usually in frequent starting) motors are used. Rule 3 applies to special
Table 6 .... Recommended Single-Phase Motor, Ratings for Full-voltage Starting
Hf Sating
locked-rotor Current* at 25 C
General tin (fetor 1 t 21
Special Conditions (wifh Utility Perm'*-
tion) (Unto 3)
1)5 V 230 V US V 230 V )IJ V 230 V
Ho 20 10 A-M A-M A-M A-M
H 20 10 A-M A-M A-M A-M
H 20 10 A-M A-M A-M A-M
H 23 11.5 AM A-M A-M A-M H 31 15.5 M A-M A-M A-M
H 45 22.5 M A-M A-M A-M
H 61 30.5
M A-M A-M
l 70 35
M AM A-M
iH 40 M A-M
2
50 M
A-M
3 70 .
A-M
5 100
A-M
A refers to eutometkeUy ooatrolled devioea. M refer* to manually controlled devices. * These valuesgf Locked-rotor current are the samea* the NEMA standard (or tingle phase Design M motors.
fig. 4 .... Speed Torque Characteristics of Single-phase Motors
conditions where larger currents may be allowed above Rules 1 and 2 upon approval of the electric company.
Hermetically-enclosed single-phase a-c motors are widely used in appliances such as domestic and commercial refriger ators, room air conditioners, beverage coolers, freezer chests, and water coolers.' Larger sizes are employed in air condi tioners, condensing units and heat pumps. The motors are sealed inside the compressor, and the gas and oil circulate ^ freely within and around the motor. Centrifugal starting switches are not used on such motors because any arcing in the gas and oil atmosphere would be detrimental, and also because the units are permanently sealed and are difficult to service or repair in the field. In place of a centrifugal switch, an external relay is used to start hermetically-enclosed mo tors.
Hermetically-enclosed motors for refrigeration compressors will, in the future, have the horsepower rating eliminated. The full-load current is to be the operating current in am peres, when the compressor is delivering rated output. The motors for hermetically-enclosed service are usually of the