Document M4yD0VeEXVxrVq71DZgeK3v7M

S.vf. Filth Avenue Portland. Oregon 97204 503/222 5561 PLAINTIFF'S EXHIBIT August 6, 1973 GP-1436 Mr.- P. C. Johns New York State Department of Labor Division of Industrial Hygiene 2447 Sheridan Drive Tonawanda, New York 14150 Subject: BPA-218-73 Bag Packer Dust Collection System Joint Cement, Akron. New York Gypsum Plant. Fan System No. 10 Dear Mr. Johns: Enclosed are the necessary forms and drawings for our application to install an exhaust system for the above subject. Our original application for this system was disapproved by your department on July 6, 1973, due to the fact that the drawings did not contain sufficient details. With reference to our proposed Fan System No. 9 for the bag slitter vent hood, we have deleted this item because we are now obtaining air velocities of 275 feet per min ute across the face of the hood. Your vent requirements for this area were 200 feet per minute. The increased velocity was accomplished by totally enclosing three sides of the vent hood. If additional details or documentation is required, please feel free to contact me at the Portland office. Sincerely, L George Turner Project Engineer Gypsum Division GTsvm Enc. cc: Mr. I. A. Hoekstra - Erie County, New York Mr. J. D. Rauch - Akron / Mr. W. Hammer - Akron Mr. V. J. Tretter - Portland SGP 0021910 4. Air contaminant emissions to outer air; list by contaminant name and indicate whether contaminant is (s) solid, (1) liquid, or (g) gas. Describe color and/or odor of visible and/or odorous contaminants. Contaminant Joint Cement Dust (white, odorless) Quantity (lb/hr) 0.04 / Contaminant % Quantity (lb/hr) - - Describe method for determining emissions: Estimate 40 Lbs/Hr of Joint Cement Dust to 99.9% Efficient Cyclone & Baghouse Emissions: (40 Lbs^ir) (0.001) = 0.04 Lbs,Alr 5. Air or gas flow rate If cyclic, SCFM/cycle, ; hrs/cycle ; cycles/yr If continuous, SCFM 3650 ; hrs/day 20 ; days/yr 340 (Average) 6. Physical characteristics of emission point a. gas temperature at point of discharge: 70 F. b. -Inside dimensions of outlet. ^ in. x 13% in. or --------------7?^ /^v> -\ It - _ / " --y in. dia(n^tfer o c. height above eround 14'6" ft. 7. Fuel (complete if fuel used as a process constituent) "Not Used" a. Coal (Type) Anthracite_ Bituminous_ ; lbs/hr. ZSulfur by Wgt. \ b. Oil (Grade) 2 4 5 6 GPH ZSulfur by Wgt._ c. Gas (Type) MFD ; Nat.; _________ CFH; BTU/CF 8. Is this a new or existing source? New 9. If existing, has an environmental rating been certified for this emission source? Not Applicable 0. If yes, give "E" number assigned SGP 0021911 NEW YORK STATE DEPARTMENT OF ENVIRONMENTAL CONSERVATION AIR RESOURCES MANAGEMENT PROCRAM APPLICATION TO CONSTRUCT OR MODIFY A SOURCE OF AIR CONTAMINATION FOR COMPLIANCE WITH 10 NYCRR 175-180 PROCESS. EXHAUST OR VENTILATING SYSTEM 9TE: See form Alr-100.1 for application instructions and form Air-51 for address of field representative where application Is filed. 1. DATE OF APPLICATION August 6, 1973 EMISSION SOURCE REFERENCE NO. Not Assigned APPLICANT, LEAVE BLANK 1- E- 2. APPLICANT (Finn, Municipality, School, etc.) AND MAILING ADDRESS Georgia-Pacific Corporation 900 S.W. 5th Avenue Portland, Oregon 97204 3. NAME OF APPLICANT'S REPRESENTATIVE George Turner TITLE Project Engineer 4. NAME AND ADDRESS OF AUTHORIZED AGENT (If any) SUBMITTING APPLICATION: None PHONE NUMBER 503-222-5561 ATTENTION PHONE NUMBER 5. NAME OF PROFESSIONAL ENCINEER OR ARCHITECT PREPARING PLANS N.Y.S. LICENSE NUMBER Ear land E. Harvey______ ______________ 6. LOCATION OF INSTALLATION STREET ADDRESS City Bloomingdale Road VII Use Q Town BUILDING Joint Cement Mfg. FLOOR 19250 CITY, VILLAGE, TOWN, COUNTY Akron, Erie County DEPARTMENT Packing 7. TYPE OF INSTALLATION IF MODIFICATION, LIST NEW AND EXISTING EQUIPMENT New Modification 8. a) HAS PREVIOUS APPLICATION FOR AIR POLLUTION CONTROL APPROVAL BEEN MADE FOR THIS INSTALLATION? b) IS THIS A RESUBMISSION OF A PLAN PREVIOUSLY DISAPPROVED? Enter Previous Application Number BPA--218--73 C) IS THIS A MODIFICATION OF A PLAN PREVIOUSLY APPROVED? Enter Previous Application No. YES j Q NO 9. CAS CLEANING OR TREATMENT EQUIPMENT: If none, check here"! a. Type Cyclone & Baghouse b. ManufacturerCyclone : "Dustex 1c. Model or Catalog No. (Reverse Air Cleaning) Jaghouse: "Flex-Kleen" Cyclone: 28-1005-32 Baghouse: 84-CT-D4 d. Size Cyclone: 2' 8" Dia. Baghox^usoeT: o!6' ' * x 14--3----Iong- g. Rated Overall Emfficiency e. Design Capacity or Requirement ACFM 3650 Deg. F 70 h. Cost of Cleaner f. Maximum Pressure Drop 16 Inches W. G. 99.9 % 10. ARE COLLECTED AIR CONTAMINATES RECYCLED OR SALVAGED? Describe recycling, salvage process or disposal method. Complete Installation: 3Yes Q No $20,000.00 Collected material from cyclone and baghouse is recycled to bag packer feud hopper via bucket elevator. 11. EXPECTED PROIECT COMPLETION DATE December 15, 1973 12. HAS APPLICANT COMPLIED WITH OTHER APPLICABLE CODES? 0 Yes No 13. ENUMERATE DRAWING NUMBERS OF PLANS SUBMITTED IN TRIPLICATE WITH THIS APPLICATION #40-73-1 #40-73-2 #40-73-3 #E-41-251 #7307-1 14. TYPE OF ESTABLISHMENT (Product manufactured or service rendered) (e.g. Foundry, Retail Store, Municipal, Lighting Fixtures, Toys, etc.) Gypsum Products Manufacturer is Type OF OPFFaT'ON OR PROCFSS le y. Woodworking, Coating, etc.) SGP 0021912 it. EMISSION SATE POTENTIAL* (The rate In pounds per hour it which air contaminants would be emitted to the outer air In the absence of air pollution control facilities or other control measures.) A. Gas and Liquid Particulates Type "Not Applicable" Quantity (Ibs/hr) Quantity (tons/yr) B. Solid Particulates Type Joint Cement Oust \ .-- Process Weight (Total Weight of all materials introduced into a process; e.g. coke, limestone, etc.) 4 Tons per hour C. Average hours operation 20 per day 120 per week SEE PAIT T87 FOI DEFINITIONS AND APPLICABIUTV 17. A. Proposed or Certified Environmental Rating (for process, exhaust or 8. If Environmental Rating has been certified, enter here ventilation system applicable under Pait 187) E- 18. EMISSIONS (Actual) A. Gaseous Not appli2 able Material Quantity (lb/hr) Stack Concentration ppm 8. Particulates Materia! Joint Cement Dust Quantity (Ib/hr) 0.04 Undiluted Exhaust Gas (Ib/lOOOlb) Not applicable 19. POINT OF DISCHARCE A. Location Through Wall . Horizontal distance to nearest bldg beyond property line cjqq C. Exit gas or air temperature (*F) 70 20. FUEL USED IN PROCESS "None" A. Coal-Type Ibs/hr B. Height (ft above ground) 14* 6" E. Exit inside - dimensions (inches) 12 X 13*5" H. Air or gas flow rale (CFM) 3225 X Sulfur by Weight C. Elevation at ground level , , 686 Ft. F. Exit gas or air velocity (tt per minute) 1. Draft 3500 Q Natural 2 Mechanical B. Oil-Grade GPH X Sulfur by Weight C. Gas-Type Cu ft/hr 'X SIGNATURE of individual or official George Turner title Project Engineer/y/ :*? Any person knowingly moking any faTse statement or false report in connection with this application shall be lioble^fpripenolties os prescribed by low. ' ^3 . " cos / SGP 0021913 SHEET, FORM IH-212.1 FUR UU/UARLC It* i nt rwcraka i lun wr uammuj < j / j . *-m . <ntCLEANING DATA IS AIK CLEANING EQUIPMENT PROVIDED? 19. TYPE OF AIR CLEANING EQUIPMENT (H tny) TO BE USED (Cretan*. Hoth Anmtlor. F.le.t Syes no Cyclone and Baghouse (Reverse Air deeming)________ 13a ir cleaner manufacturer _ Cyclone: Dustex, Inc. . 20b. MODEL OR CATALOG NO. Cyclone: 28-100S-32 20c. SIZIE Cycl one; 2* 8" Dia. x - ^nghnnsp:___Fleix-Kle.en.__Inc. Baghouse: 84--CT-54______ 8* Q_. JLiQng_ 21 aXIMUM PRESSURE DROP THROUGH AIR CLEANER AT Cyclone 5" Baghouse: 6*0" Oia. OPERATING CONDITIONS (-W.C.) Baghouse; 7" 14*3" Long AN DATA {If more than one fan system is shown on plans, each fan should be numbered and described) O. FAN NO. 22. MFR.'S NAME FAN TI'PE DESIGN SIZE 10 New York Blower Co. Centrifugal Material Handling 192 *. MFR.'S RATING: RPM CFM S.P. (In- wmfr) B.H.P. MOTOR H.P. 25. FAN CONDITION 3130 3650 16" 15.9 20 t?C ! New | | Reconditioned 1 1 Existing 6. DESIGN REQUIREMENTS: CFM 3225 S.P. (In. wmfr) 14" 127. FAN INLET DIAMETER | 12 taeh,, 28. FAN OUTLET DIAMETER OR SIZE 12 BC 13% inch*! UMENSIONS OF UNITS EXHAUSTED (Identify oo plan by letter; uae separate sheet if necessary) r-~\- - - p^ti -v1 -r rurr^rn py SGP 0021914 Division of Indusaiel Hygiene Eogineeting Section EXHAUST SYSTEM PLAN PLAN NO. DATE REC'D. FEE REC'D. // FILING INSTRUCTIONS - ONE COMPLETED COPY OF THIS FORM MUST BE FILED FOR EACH FAN SYSTEM IN THE EXHAUST PLANS BEING SUBMITTED. Forward exhaust system plans IN TRIPLICATE, together with one completed copy of this form for each .on system, to the Engineering Section of the Division of Industrial Hygiene at one of the following Department of Labor Offices. Plans for exhaust systems to be installed in the counties of Cattaraugus, Chautauqua, Erie, Genesee, Livingston, Monroe, Niagara, Ontario, Orleans, Woyne, Wyoming and Yates should be sent to: 2447 SHERIDAN DRIVE, TONAWANDA, N.Y. 14150, Plans for exhaust systems to be installed in counties other than those listed above, should be submitted to: 80 CENTRE STREET, NEW YORK, N.Y. 10013. IMPORTANT: Effective June 1, 1963, the Industrial Commissioner is required by section 204-a of the Labor Law to charge a FEE FOR THE EXAMINATION OF EXHAUST PLANS. Please forward with the plans a check or money order payable to the Industrial Commissioner, in accordance with the following fee schedule FOR EACH FAN SYSTEM: CATEGORY A CATEGORY B "Simple single booths and enclosures, such os spray booths; canopy All systems other than category A. hoods; dilution, general and natural draft ventilation systems". Design CFM Fee Design CFM Fee less than 250 250 or more but less than 1,000 $10 20 less than 5,000 5,000 or more $10 20 1,000 or more but less than 5,000 5,000 or more but less than 10,000 10,000 or more 30 40 50 1. FIRM NAME Georgia-Pacific Corporation_______________________________________ 2. MAILING ADDRESS 900 S.W. 5th Avenue, Portland, Oregon 97204 3. PLANT LOCATION (Stft and Numbar, City, Town, Viilmgo; County) Bloomingdale Road, Akron, Erie County, New York 14001 44. PLANT REPRESENTATIVE TO BE CONTACTED REGARDING EXHAUST SYSTEM PLANS 4b. TITLE George Turner Project Engineer 5. NUMBER OF IN-PLANT EMPLOYEES AT THE ABOVE PLANT LOCATION: TOTAL 135 MALE 131 FEMALE 4 6. NO. OF EMPLOYEES AT OPERATIONS OR MACHINES 70 7. AUTHORIZED AGENT (H any) SUBMITTING PLANS (Eng.. Da,ifiner, Con.u/linfi Firm. Etc.) LETTER OF AUTHORIZATION MUST ACCOMPANY PLANS None . BUSINESS ADDRESS OF AGENT 9. NO. OF FAN SYSTEMS SHOWN ON PLAN (Fan Symtama Should Ba Numbarad) One (1) 10. SUBMITTED FOR COMPLIANCE WITH INDUSTRIAL CODE RULE NO. 10NYCRR-80 general data FAN SYSTEM NO 10 AMOUNT OF FEE FNfl nsFn * $30.00 previously sent for this system II. LOCATION OF SYSTEM . building Joint Cement ManufacturingFLOOr one None * Bage. department Packing d. NUMBER OF FLOORS IN BLDG. one I2. IS PROPOSED INSTALLATION NEW? _______ [x] YES QUO IJb. ADDITION TO OR RECONSTRUCTION OF EXISTING SYSTEM YES HN0 IJ. DOES THIS PLAN AMEND [x] YES PREVIOUSLY SUBMITTED PLAN? I NO IF YES. GIVE PREVIOUS PLAN NO. AND AMOUNT OF FEE PAID BPA-218-73 ($30.00) ___________ 14. IS THIS INSTALLATION TO COMPLY WITH ORDERS OR SPECIFIC RECOMMENDATIONS ISSUED BY THIS DEPARTMENT? YES NO IF YES. GIVE DATE OF ISSUANCE October 27, 1972 15. IS DISCHARGE OF SYSTEM TO BE RECIRCUL ATED TO THE WORKROOM* || YES f<0 (*Ot achargad Air Which Conlatna Dangaroua Air Conlnlnifa Shall Sot Ba Racircuiatad. * - Ru/a ig-g.S) 16 MSCHARGE POINT: l~" i ABOVE ROOF i I OUT OF WINDOW 20 FEET TO NEAREST FIRE ESCAPE OR EXIT I THROUGH SIDE WALL XJCXEOECXXJCXaC I I OTHER 5 FEET TO NEAREST WINDOW 17. MAKE-UP AIP. EQUAL IN VOLUME TO THAT EXHAUSTED, TO BE SUPPLIED BY Natural Draft 17. MEANS FOR HEATING MAKE-UP AIR None SGP 0021915 NEW YORK STATE DEPARTMENT OF ENVIRONMENTAL CONSERVATION DIVISION OF AIR RESOURCES BUREAU OF AIR QUALITY CONTROL 41 STATE STREET ALBANY, NEW YORK U207 ENVIRONMENTAL ANALYSIS REPORT - SUMMARY OF SOURCES For completion kf applicant (in triplicate) Report No. Use ana copy el this (arm at a cover sheet (or aach copy o( the Environmental Analysis Report submitted in triplicate 1. Nemo o( firm or owner , Georgia-Pacific Corporation BAQC Assign. 2. Address of installation , Bloomingdale Road, Village of Akron, Erie 3. Person to contact in re(aranca to this submission, Georae Turner. Project Engineer Name qqq g # w. 5th Avenue 4. Proposed Environmental Rating(s) Portland, Oregon 97204 Address Emission Point No. Not Assigned Process, Exhaust or Ventilating System Bag Packer, Joint Cement Manufactur ing Proposed Env< Rot. Emission Point No. Process, Exhaust or Ventilating System Proposed Env. Rot. Continue on reverse side for listing of proposed ER's. S. Dote Aligned fi, 1 Q7*3a. Signoture , rf-*t 1 I t ---- por completion by field reprosentotlvo I recommend (occeptonce) (denial) of the proposed environmental roting(s) Remorks ________________. 7. Title Project: Engineer L (. Oet* , 9. Signoture , 10. Title SGP 0021916 oin NjO. Vtnrilotmq Syittn ER Point No. |__________ Vontilotinj Systom ER SGP 0021917 0 S.W. Fifth Avanu# Portland, Oregon 97204 503/222 5561 August 6, 1973 Mr.- F. C. Johns New York State Department of Labor Division of Industrial Hygiene 2447 Sheridan Drive Tonawanda, New York 14150 Subject: BPA-218-73 Bag Packer Dust Collection System Joint Cement, Akron. New York Gypsum Plant. Fan System No. 10 Dear Mr. Johns: Enclosed are the necessary forms and drawings for our application to install an exhaust system for the above subject. Our original application for this system was disapproved by your department on July 6, 1973, due to the fact that the drawings did not contain sufficient details. With reference to our proposed Fan System No. 9 for the bag slitter vent hood, we have deleted this item because we are now obtaining air velocities of 275 feet per min ute across the face of the hood. Your vent requirements for this area were 200 feet per minute. The increased velocity was accomplished by totally enclosing three sides of the vent hood. If additional details or documentation is required, please feel free to contact me at the Portland office. Sincerely, George Turner Project Engineer Gypsum Division GT:vm Enc. cc: Mr. I. A. Hoekstra - Erie County, New York Mr. J. D. Rauch - Akron Mr. W. Hammer - Akron Mr. V. J. Tretter - Portland SGP 0021918 4. Air contaminant emissions to outer air; list by contaminant name and indicate whether contaminant is (s) solid, (1) liquid, or (g) gas. Describe color and/or odor of visible and/or odorous contaminants. Contaminant Joint Cement Dust (white, odorless) Quantity (lb/hr) 0.04 ' Contaminant % Quantity (lb/hr) . * Describe method for determining emissions: Estimate 40 Lbs/Hr of Joint Cement Dust to 99.9% Efficient Cyclone & Baghouse Emissions: (40 Lbs/ftr) (0.001) = 0.04 Lbs/ftr 5. Air or gas flow rate If cyclic, SCFM/cycle; hrs/cycle ; cycles/yr If continuous, SCFM 3^30; hrs/day ^______________ ; days/yr 340 (Average) .6 Physical characteristics of emission point a. gas temperature at point of discharge: 70 F b. Inside dimensions of outlet ^ In. x ^~3^ in. or c. height above ground 1416"ft. 7. Fuel (complete if fuel used as a process constituent) "Not Used" a. Coal (Type) Anthracite; Bituminous; lbs/tir. ZSulfur by Wgt.^ b. Oil (Grade) 2 4 5 6 GPH ZSulfur by Wgt. c. Gas (Type) MFD; Nat.; _______________ CFH; BTU/CF 8. Is this a new or existing source? New 9. If existing, has an environmental rating been certified for this emission source? Not Applicable 7. If yes, give "E" number assigned SGP 0021919