258 CHAPTER 14 : 1949 Guide ' at the mean height of the roof or ceiling above the floor of the heated room; and in the case of floors, the air temperature at the floor level. - Temperature at Ceiling: The air temperature at the ceiling is generally higher than at the breathing level due to stratification of air resulting from the tendency of the warmer or less dense air to rise. An allowance for this fact should be made in calculating ceiling heat losses, particularly in the case of high ceilings.' However, the exact allowance to be made may be somewhat difficult to determine as it depends on many factors, including (1) the type of heating system, (2) ceiling height, and (3) the insideoutside temperature differential. The type of heating system is par ticularly important, as the temperature gradient from floor to breathinglevel to ceiling may depend to a large extent on whether direct radiation, Table 3. Approximate Temperature Differentials Between Breathing Level and Ceiling, Applicable to Certain Types of Heating Systems* Ceiling Height (FT) 10 11 12 13 14 15 16 17 18 19 20 ' 25 30 35 40 45 50 Breathing Level Temperature (5 ft Above Floor) 60 65 70 72 74 76 78 80 85 90 3.0 3.3 3.5 3.6 3.7 3.8 3.9 4.0 4.3 4.5 3.6 3.9 4.2 4.3 4.4 4.6 4.7 4.8 5.1 5.4 4.2 4.6 4.9 5.0 5.2 5.3 5.5 5.6 6.0 6.3 4.8 5.2 5.6 5.8 5.9 611 6.2 6.4 6.8 7.2 5.4 5.9 6.3 6.5 6.7 6.8 7.0 7.2 7.7 8.1 6.0 6.5 7.0 7.2 .7.4 7.6 7.8 8.0 8.5 9.0 6.1 6.6 7.1 7.3 7.5 7.7 7.9 8.1 8.6 9.1 6.2 6.7 7.2 7.4 7.6 7.8 8.0 8.2 8.7 9.2 6.3 6.8 7.3 7.5 7.7 7.8 8.1 8.3 8.8 9.3 6.4 6.9 7.4 7.6 7.8 8.0 8.2 8.4 8.9 9.4 6.5 7.0 7.5 7.7 7.9 8.1 8.3 8.5 9.0 9.5 7.0 7:5 8.0 8.2 8.4 8.6 8.8 9.0 . 9.5 10.0 7.5 8.0 8.5 8.7 8.9 9.1 9.3 9.5 10.0 10.5 8.0 8.5 .9.0 9.2 9.4 9.6 9.8 10.0 10.5 11.0 8.5 9.0 9.5. 9.7 9.9 10.1 10.3 10.5 11.0 11.5 9.0 9.5 .10.0 10.2 10.4 10.6 10.8 11.0 11.5 12.0 9.5 10.0 10.5 10.7 10.9 11.1 11.3 11.5 12.0 12.5 ' The figures m this table are based on an increase of 1 per cent per foot of height above the breathing level (5 ft) up to 15 ft and i\j of one degree for each foot above 15 ft. This table is generally applicable to forced air types of heating systems. For direct radiation or gravity warm air, increase values 50 per cent to 100 per unit heaters or warm air is used, and in the latter case, whether the circu lation is by gravity, auxiliary fan or forced air. Although with properly adjusted air flow the temperature differential with unit heaters can be reduced to a minimum, it is possible with improper adjustment that it may be increased over that which would normally result without me chanical circulation of the air. It would be difficult from present available information to establish rules for determining the temperature difference to use in all cases How ever, for residences and other structures having ceiling heights under 10 ft, the comparatively small temperature differential between the breathing level and ceiling may generally be neglected without serious error. For higher ceilings where specific test data are not available, an allowance of approximately 1 per cent per foot, of height above the breathing level may be made for ceiling heights up .to 15 ft and approximately -fa of 1 deg per foot of height above this level. The values in Table 3 are calculated Heating Load 259 on this basis. For direct radiation and gravity warm air systems, the allowance should be increased from 50 per cent to 100 per cent oyer those given in Table 3. These rules should; however, be used with considerable discretion. Temperature at Floor Level: According to the University of Illinois Research Residence tests', the temperature at the floor level ranged from about 2J to 6 deg below that at the breathing level, or somewhat greater than the difference between the breathing level and ceiling temperatures. Tests at the University of Wisconsin* indicated a some what smaller differential between the floor and breathing level tempera tures. As a general rule, if the breathing level to ceiling temperature differential is neglected (as with ceiling heights under 10 ft), the breathing level-floor differential may also be neglected as the two are somewhat compensating, especially where both. floor and ceiling heat losses are calculated for the same space. In other cases, the 10 ft ^temperature differentials in Table 3 may be used in arriving at the floor heat loss, these differentials to be subtracted from the breathing level, temperature- ATTIC TEMPERATURES Frequently it is necessary to estimate the attic temperature, and in such cases Equation 1 can be used for this purpose: ,4or/c?i (0(Arr/r -{- A.r/. + A|(/|) - A.T7. J- AJI. 4- A.U. 4- A.U. (1) where' . U = attic temperature, Fahrenheit degrees. t, = inside temperature near top floor ceiling, Fahrenheit degrees. t. = outside temperature, Fahrenheit degrees. Ao = area of ceiling, square feet. A, = area of roof, square feet. A, = area of net vertical attic wall surface, square feet. A, = area of attic glass, square feet. Uc -- coefficient of transmission of ceiling, based on surface conductance of 2.20 (upper surface, see Chapter 6). 2.20 = reciprocal of one-half the air space resistance. Ur -- coefficient of transmission of roof, based on surface conductance of 2.20 (lower surface, see Chapter 6). Vw = coefficient of transmission of vertical wall surface. Ut = coefficient of transmission of glass. Example 1. Calculate the temperature in an unheated attic, assuming the follow ing conditions: t, = 70; fo = 10; A,, = 1000; Ar = 1200; Aw = 100; A, = 10; U, = 0.50; U,, = 0.40; U,, = 0.30; U. = 1.13. Solution: Substituting these values in Equation 1: . ( = (1000 X 0.40 X 70) + 10[(1200 X 0.50) + (100 X. 0-30) + (10 X 1.13)) * " (1000 X 0.40) + (1200 X 0.50) + (100 X 0.30) + (10 X 1-13) 34,413 t, 33.1 F. 1041 Equation 1 neglects the effect of .any interchange of air such as would take place through attic vents or louvers intended to preclude attic con- ! ;`ii, ! ! i l l! ; I.-l I- ! t I i