Document M4Ow0vY4DdwKmemkywjGgyBLk
ANALYZER CARRIER GAS BANK SYSTEM
The carrier gas bank system will automatically switch the carrier gas banks to the analyzers. MON-ARC SPECIALTY GASES is responsible for changing out empty banks and resetting regulators.
This system is set up so that the banks will automatically switch at 120* PS1. This is done with check valves and regulator pressure settings.
EXAMPLE: When BANK A" is on line the bank pressure is approximately 2500* PSI. The output pressure of regulator "A" is 140* PS1. This regulator feeds regulator X". Regulator "C has an ouput of approximately 100* PSI. Check valve B" keeps regulator A from back-pressuring regulator B . When BANK "A drops below 120* PSI BANK "B will come on line because of the check valve arrangement. After BANK "A'is replaced, but before* it is put on line. BANK "B is set at 140* PSI and regulator A" is set at 120* PSI. This will keep BANK "B" on line and BANK 'A" ready when BANK B is empty.
ALARMS:
There are four different bank systems for the analyzers, (hydrogen, nitrogen, helium, zero air >. Each system has an alarm for low pressure.
EXAMPLE If BANK A drops below 120* PSI. the pressure switch on A will actuate; also. BANK "B will come on line. In this situation there will be no alarm. With BANK A empty and BANK `B drops to less than 500* PSI. pressure switch B will actuate causing an alarm. This is a warning that both banks are near empty. ACTION NEEDS TO BE TAKEN.
CORRECTIVE ACTION: CONDITION *1:
A) Verify both banks are low by looking at inlet pressure gauge on
both regulators A and B .
DO 0146.4R OONFTDFNTTAI
c B) Check to insure both banks are in service; valves open.
O Call MON-ARC SPECIALTY GASES and tell them you need a bank of carrier gas.
Di If unable to reach MON-ARC. there is a spare bank of each gas kept at the main instrument shop. A cherry-picker is required for transportation of the bank
' CONDITION 2: A) If alarm sounds and both banks have sufficient pressure check the outlet pressure of regulators A and B (should be 120 - MO* PSD.
B) Check valves 1 and 2 to insure they are open.
C) If valves 1 and 2 are open check output pressure of regulator C\ This should be approximately 100 PSI
DI If you cannot restore pressure block valve *3 and openvalve *5 ai valve *6. Also, open valve on single cylinder. This puts the single cylinder on line which will give you approximately 24 hours of rui time.
E) Notify analyzer person of situation as soon as possible.
47? 0 PSL 1
1&
y7>'* PSL 2
!___ __________
___ I
* PSL 3
NOTE: ML SWITCHES WILL OPEN ON DECEASING PRESSURE.
t: A PSL 4
ii
- AC
TO ANNUCIAT
AN OPEN CIRCUIT 1 SOUND THE ALARM
14649 r-ONFTOFNT TAt
r C
r>
N.
(
.TO *- > - '( AukLyzeK
. jao Bauk A
/%* &a*IK O
S/M4^E CVL/NOfK
DO 014650 CONFTDFNTTAl,
DO 014651
OONFTDFNTTA
CARRIER CAS BANK SYSTEM
100*
.......o wJo
RIG. *C*
V3
TO ANALV7IHS
VS
VI V?
CHECK VAIVE 'A-
z CHECK VAIVE*#
100*
REG. 'A
120* MO*
81EEO VALVE
O
oiil.'
REG. *8 170*
140*
BLEED VAIVE
BANK "A
BANK "B
V_____ /
SIN6L E CYLINDER
TYFiS F PE3AWI1(N]
PIPING AND INSTRUMENT DIAGRAM (P&ID) INDEX FLOW SHEET. INDEX & INSTRUCTION. (LEGEND & REFERENCE SHEET), PLOT PLAN. ETC. CIVIL, CONCRETE (FOUNDATION), ETC.
STRUCTURAL & ARCHITECTURAL PIPING
MECHANICAL INSTRUMENTS ELECTRICAL NON-PROCESS EQUIPMENT (A.C.), ` . MOD V GRAPHICS & ALARM PANELS ' COMMUNICATION *
HEAT & MATERIAL BALANCE (HMB)
ALTERNATE SOURCE TEMPORARY DRAWING
id: IF
& 8 1/2* x ir 22" X 34'
P 11* X 17*
TVF1S F F&
RHPID3 10/89
H ORIGINAL ORAWING (RECORD DOCUMENT / AS EXISTS / AS BUILT)
2 PROJECT DRAWING (PROPOSED ADDITIONS, TIEPOINT,
PROPOSED MODIFICATIONS, DEMOLITIONS, ETC.)
3 DEMO DRAWINGS
A) XB1-100-N50-001 (MANUAL)'
;> V ^ :~
* kB) B1-X100-N50-001 (ELECTRONIC^FOR: ARCHIVE).
CVOQN/RHPID3JX3N Sap. 13,190116*3:02
-
:;V'" '
- ;'
y-`' no 014466?5?
"7',. rONFTDDFNNTl T Al
DRAWING NUMBERS
1) DRAWING NUMBERS ARE ISSUED BY ENGINEERING RECORDS A) CONSUELLA ELLIS EXT. 6806
2) CHECK WITH PLANT FOR NUMBERING SYSTEM A) SOME PLANTS SECTION OFF BY AREAS B) SOME PLANTS NUMBER BY TRAINS C)SOME PLANTS USE NEXT NUMBER AVAILABLE NOTE: TRY TO AVOID USING A,B*C, ETC.
3) DO NOT REUSE VOIDED OR SUPERSEDED DRAWING NUMBERS A)VOID DRAWINGS BY PERSON AND DATE B)SUPERSEDE BY NEW DRAWING NUMBER OR NUMBERS
4) PROJECT OR 'P* DRAWINGS A) AN ORIGINAL P&ID SHOULD BE ISSUED BEFORE *P* DRAWINGS ARE CREATED B) ONE (1) 'P" DRAWING IS MADE FOR ALL ON-GOING PROJECTS C) RECONCILE ALL COMPLETED PROJECTS ON ORIGINAL DRAWING
5) DEMO OR *X* DRAWINGS A)USED FOR ONE PROJECT B)SHOULD BE MANUAL CJMAKE ELECTRONIC DEMO DRAWINGS UNDER SPECIAL CONDITIONS NOTE: SEE B.J. JOHNSON EXT. 6S76 FOR STORING DEMO DRAWINGS
C^DGN/DWGNUM.DQN Oct 28,180118:17:00
RJH 10/28/81
00 014650 CONFTDFNTTAl
f
ENGINEERING RECORDS DRAWING NUMBER CONVENTION
10-1 -<51
STANDARO DRAWING NUMBER
B 1 1000-N50-001
THIS LETTER OICTATES T*C SIZE OF TIC ORAVING. EXAMPLES* A - 81/** X II*
B 22* X 34* B 24* X 36* C - 18* X 24* C * 28* X 24* 0 - 11* X 17*
THIS LETTER AM) NLUCER COeiNATION OICTATES THE PLANT COOE.
THIS NUMBER OICTATES TIC . -- DISCIPLINE OF TIC ORAVING. EXAMPLES* 81 - UCEXES. FLOW SHEETS
1 -PS 10'S 2 - CIVIL 3 - STRUCTURAL 4 - PIPING 5 - VESSEL 6 - INSTRUMENTATION 7 - ELECTRICAL 8 - MOO V GRAPHICS *) COMMUNICATION 18 - ICAT 6 MATERIAL BALANCE
THIS IS TIC ACTUAL ORAWIM) NUMER.
SHEET 1 OF 2
* -
.. .
..
' '
i
DO 014654 OONFTDFNTTAt
ENGINEERING RECORDS DRAWING NUMBER CONVENTION
10-1-SI
ADDITIONAL LETTERS ACCEPTED TO THE STANOARO
FB4-1000-N50-001
THIS LETTER IS USED TO IMDICATE FIRE PROTECTION DRAWINGS.
J
XB1-1000-N50-001
THIS LETTER IS USED
J
TO INDICATE A DEMOLITION
DRAWING.
B1
1000-N50-001P
THIS LETTER IS USEO TO IMDI CATE TRACING OF A PIPE SPOOL.
TB4
J
THIS LETTER IS USED TO INOICATE A PROJECT. PROPOSED. OR PRELIMINARY
1000 - N50 - 00 r
HISC ADDITIONS TO THE STANOARO
T*S LETTERS ARE USED TO INOICATE A TEMPORARY ORAWING.
zrBL A
pi
1000-N50-001 1000-N50-001
THIS LETTER 1$ USED TO UOICATE A DRAWING IN OUR DIVISION PLOT PLAN SYSTEH.
g^
SUCLE OR DOUBLE
I>
LETTERS ARE ALLOKO TO KEEP:
'A CERTAIN SEQUENCE OP,;- ; : \ .
oraminos tooether.
" ' \T '
1000AA-N50-001
VL - A .
-"
eifCT 7 OF 7
`
I;,-.1*.*' *'
V- r' T
'is' V."--DO 014655
` W-Hfe conftdfnttai
f
LINE BUBBLE
LINE NUMBER
PIPING SPECIFICATION
SERVICE DESIGNATION PIPING SIZE
(WAT-100 -6"
-A ~)
T=E
I
TRACING SPECIFICATION
C=F4
t
INSULATION TYPE A CLASS
'
' .*
^
'*
^*
.
1 ; V*
-
-> ' ' - > ` k SKv,' * f .
;*
T^. r
.v -
' v*V-
, >jW *-*', ? --fc'* -''/ L r-,',>*' *'* - S*,, ;-T` '
/& o,- r0>0n 014656
. CONFIDENT!Al
OONF T OTNT T Al
n
00
1*
i8
i
_i_____________1-___________*_______________
HI----f 1--TIPIUTIM
*
him --
.
-B=
________,____________________ OAAVtHC DOCK
_____u
1
llSSL
IfSr.
k BUsr1 im?
ii J ft I!
LINE SERVICE DESIGNATION
PRO
PW
STM CL2 CTS
CON
HO MOH N2 CTR OM VNT REF IA INH FW OW DRN SA
PROCESS
PROCESS WATER
STEAM
CHLORINE
COOLING TOWER WATER SUPPLY
CONDENSATE
HOT OIL
METHANOL NITROGEN
_______
COOLING TOWER WATER RETURN
OIL MIST
VENT
REFRIGERANT
INSTRUMENT AIR
INHIBITOR
FIREWATER
POTABLE WATER
DRAIN
SULFURIC ACID
V*
:
014659
. V"-* j . - .. ,, .
PIPING SPECIFICATIONS
PEC
SERVICE
'cRRr-2p; feAf5$buCT CRU&ASoUCT
CELL EFFLUENT
Ft PN.IA.CT< ON:.. M2
` "Hf
^CRyOEPROOUCT VAPOR " (CORROSIVE)
liOS7a^! ^5S3T?"EN
iW -kj' nRAI--N rR
PRESSURE/TEMP PSIC/ F
408/100 - 384/400 408/100 - 384/400 285/100 - 200/400 285/100 - 200/400 285/100 - 265/180
f75/100 - 225/212 75/100 - 225/212 275/100 -175/350 285/100 - 170/500 20* VAC 20* VAC - 25/2. 446/100 - 404/550 445/100 - 445/400 446/100 - 379/650 285/100 - 200/400 212/100 285/100 - 70/150 285/100 - 200/400 230/100 - 160/400 600/100 - 415/400 600/100 - 480/400 600/100 - 475/650 285/100 - 170/500 446/100 - 404/550 200/1025 285/100 - 185/400 285/100 - 230/400 230/100 - 185/400 285/100 - 200/400 673/100 - 501/725 446/100 - 446/400
446/100 * 404/550 200/AMO. 100/150
ANSI FLANGE RATING PSIG
300 150 150 150 150 150 150 150
N/A N/A
300
150 150 150 150 150 3O0 300 150
150 150 150 150 300 150 150 150 150
ro> o
Z3
-on o-1
T1 *
z O'
>, H-T<> Oo'
V.j>:
1 '
' 'if-
PIPE MATERIAL
A-333 A-333 A-333 A-333
PPL LINED
KYNAR LINED TFE LltCD
CS
FRP FRP
CS CS CS CS CS gal. CS CS SS 304L SS 304L MONEL MONEL cs/ss cs/ss INCONEL 600 A-20 CS MONEL CS CS CS GAL. CS CS/SS CS PVC GAL. CS
C O N FID E N T TAI.
AAHL ANALYSIS ALARM' HIGH OR LOW ACV ANALYZER CONTROL VALVE AE ANALYZER ELEMENT AI ANALOG INPUT
AO AOV AR AT BMS CGA , CGM
ANALOG OUTPUT AIR OPERATED VALVE ANALYSIS RECORDER ANALYSIS TRANSMITTER BURNER MANAGEMENT SYSTEM COMBUSTIBLE GAS ALARM
COMBUSTIBLE GAS MONITOR
n : CT
CONDUCTIVITY TRANSMITTER
? CV FLOW CONTROL VALVE
: oi> DIGITAL INPUT
DO DIGITAL OUTPUT
EBV EMERGENCY BLOCK VALVE
EV ELECTRIC VALVE (SOLENOID) EW EMERGENCY VENT VALVE - FAH FLOW ALARM HIGH
f FAHL FLOW ALARM HIGH OR LOW
f ' FAL FLOW ALARM LOW
FE FLOW ELEMENT
FFA FLAME FAILURE ALARM / / FFIC RATIO FLOW* INDICATING CONTROLLER
>. FFS FLAME FAILURE SWITCH r FI FLOW INDICATOR(LOCAL)
: FIC FLOW INDICATING CONTROLLER FR FLOW RECORDER
FRC FLOW RECORDING CONTROLLER FSH FLOW SWITCH HIGH
FSHL FLOW SWITCH HIGH OR LOW FSL FLOW SWITCH LOW
, Si-FTiV. FLOW TRANSMITTER ii- GFO , GROUND FAULT DETECTOR
' * GL -:: GREEN LIGHT
.W: B8BB
HICi; HAND INDICATING CONTROLLER HOA _ : HAND-OFF-AUTO SWITCH
HAND SWITCH HSA ,, HAND SWITCH ALARM
V. I/Pi5{; transducer
o>vI/S- CURRENT/SPEEO TRANSDUCER
a /II3* CURRENT INDICATOR (AMPS) o t IR ,C CURRENT RECORDER -* >,IT.'i^; CURRENT TRANSMITTER LAH y LEVEL ALARM HIGH ff'/'LAHH LEVEL ALARM HIGH-HIGH ~ LAHL LEVEL ALARM HIGH-LOW
`, LAL\' LEVEL ALARM LOW
LC LEVEL CONTROLLER LCV LEVEL CONTROL VALVE
utr WEIGHT INDICATOR CON. Jt WEIGHT TRANSMITTER CON
LE LEVEL ELEMENT
ZSC LIMIT SWITCH CLOSED
LI LEVEL INDICATOR
ZSO LIMIT SWITCH OPEN
LIC LEVEL INDICATING CONTROLLER
LIT LEVEL INDICATOR TRANSMITTER
LR LEVEL RECORDER
LRC LEVER RECORDING CONTROLLER
LSHH LEVEL SWITCH HIGH-HIGH
LSHL LEVEL SWITCH HIGH-LOW
LSL LEVEL SWITCH LOW
LT LEVEL TRANSMITTER
PAH PRESSURE ALARM HIGH
PAHL PRESSURE ALARM HIGH OR LOW
PAL PRESSURE ALARM LOW * PB PUSH BUTTON
PCV PRESSURE CONTROLLER (SELF-CONTAINED)
PDAH PRESSURE DIFFERENTIAL ALARM HIGH
PDAHL PRESSURE DIFFERENTIAL ALARM HIGH OR LOW
PDI 1PRESSURE DIFFERENTIAL INDICATOR
PDIC PRESSURE DIFFERENTIAL INDICATING CONTROLLER PDR PRESSURE DIFFERENTIAL RECORDER
PDRC PRESSURE DIFFERENTIAL RECORDING CONTROLLER OPT PRESSURE DIFFERENTIAL TRANSMITTER PI PRESSURE INDICATOR
PIC PRESSURE INDICATING CONTROLLER PR PRESSURE RECORDER
PRC PRESSURE RECORDING CONTROLLER ,PSH PRESSURE SWITCH HIGH
PSL PRESSURE SWITCH LOW
RL RED LIGHT
RO RESTRICTING ORIFICE
SC SPEEO CONTROLLER
SDA SHUTDOWN ALARM
SG SIGHT GLASS
SSH SPEEO SWITCH HIGH
SSL SPEED SWITCH LOW
ST SPEED TRANSMITTER
TAH TEMPERATURE ALARM HIGH
TAHL TEMPERATURE ALARM HIGH OR LOW
TCV TEMPERATURE CONTROL VALVE
TE TEMPERATURE ELEMENT
TP PRESSURE TRANSMITTER
TR TEMPERATURE RECORDER TSH TEMPERATURE SWITCH HIGH
TT TEMPERATURE TRANSMITTER UA UNIT ALARM
VAH VIBRATION ALARM HIGH
VE VIBRATION ELEMENT
VFD VARIABLE FREQUENCY DRIVE VI VIBRATION INDICATOR
TWOGAL LOME EUIBELI
LINE NUMBER 7 size7 V SPEC
-----------j
TRACING --^
71 INSULATION
(PRO-12604- 1 1/2* -X )
T^ST-----
----- FC7
TV IPO GAIL LONE (NlTOINiy^TO@lNli
DESTINATION 1 DESTINATION 2 DRAWING NUMBER
ON OR OFF PAGE LEFT OR RIGHT
T-100 A/B B1-100-NS0-001
\
>
/
NON-DIRECTIONAL
STM-40101-24*-X 235 STM HEADER B1-401-V51-001
BI-DIRECTIONAL
WELL NO. 21 STORAGE WELL L B1-1021-B60-001
TO AND FROM ADJACENT PAGE LEFT OR RIGHT
E-101 A/B/C 1b1-2505-P45-002
-(PRO-12604 - 11/2* - X )
P-101 A/8 B1-2505-P45-002
<reO-12604-ll/2* -X^)
BHP1D4 10/69
OJDQN/RHP1D4IX3N 8p. 13,109116:1834
* DO 014662
- CONFTDFNTTAt
ONiiaG@MMiTOINI@ LON I
PROCESS (THIN) PROCESS (THICK) ELECTRICAL OR T.C. INSTR AIR OR PNEUMATIC CAPILLARY TUBING HYDRAULIC SIGNAL LINE DATA HIWAY SERIAL LINK
FIBER OPTIC
T? /' 0 '
X X X X X- X X X -X X X X X -X
-t--t--t--fc--t--t--b--t--t--fc--t--t--t---
00000000 -0 00000
typocal DNsirimuiMiENir tta
PREFIX ROOT -
SUFFIX
FIELD
O MOUNTED BEHIND CONTROL
0 ROOM PANEL MOUNTED
CONTROL ROOM
0 PANEL MOUNTED LOCAL FIELD
BEHIND PANEL MOUNTED
LOCAL FIELD PANEL MOUNTED
CONTROL ROOM MICRO DEVICE
cpu-room ^ ~ MICRO DEVICE
FIELD COMPUTER DEVICE
CPU-ROOM COMPUTER DEVICE
CONTROL ROOM COMPUTER DEVICE
RHPID6
10/M
CVDGN/RHP1D5.DGN S*p. 13,190116*433
,* .V':
00 014663 W CONFTDFNTT A(
TWO AIL I@(U)0(PMiMT TA
PREFIX ROOT
SUFFIX
TRACING _J
L INSULATION
T-ST C-E7
TWDaL
BQWY SVH1ILS
RHPID6
10/80
IX GATE VALVE CX DIAPHRAGM VALVE tm PLUG VALVE IX NEEDLE VALVE Dea BALL VALVE CX GLOBE VALVE CX BUTTERFLY VALVE rear barstock valve CX slide valve Cg] 3-WAY VALVE
C^3 4-WAY VALVE
eg] 3-WAY PLUG VALVE
4-WAY PLUG VALVE DgCl 3-WAY BALL VALVE
4-WAY BALL VALVE
DO 014664 OONFTDFNTTAI
TmPOCAIL @IMTIF&ll V&ILVI
MODULATING ON/OFF SOLENOID
MOTOR
v--
PRESSURE REGULATING
?mm 8VI
TRP TRAP SYMBOL
TP TIE POINT
ECCENTRIC REDUCER
CD CONCENTRIC REDUCER
ANGLE VALVE
r-**i CHECK VALVE Dga TRANSFLOW VALVE
Y OR 45 DEG. VALVE
r4i SPRING bOADEO
CHECK VALVE D PIPE CAP
PIPING NOZZLE. /
^PIPING NOZZLE W/FLANGE V-
P=-------------------I-II
FLANGE
BREAK-OUT FLANGES
TO PLANT DRAIN SYSTEM
RHPID7 10/80
C^0GN/RHPI07JX3N S#p. 15,1091 0823:13
Y
OPEN FLOOR
. DRAIN
U
TRENCH
ORAINv. : . ii'. Yi-4'' '*
D0 014665
' ' ; ,: ;L: CONF T DFNT T Al
-
- i'
.'*? j.
LME TOdlilOlN]'
(mEZZD
LINE SERVICE
01 THRU SB PAGE NUMBER (B1-105-XXX-001)
OIMSTiyiMlINlT IN) y (Ml 1110 INI'
PREFIX
PAGE NUMBER (B1-243-XXX-001)
01 THRU SB
PREFIX
POINT NUMBER CAN NUMBER SYSTEM NUMBER
OINlSTiyUllNlT iYM!lILS
INSTRUMENT ELEMENT
O THERMOWELL
|>! RESTRICTING ORIFICE # CRITICAL INSTRUMENT HEX IVH SAMPLER (ANALYZER) E3 DIAPHRAGM SEAL
ROTOMETER
INLINE INSTRUMENT
RHPID10 1O/B0
C^DON/RHPtDlO.DON Sap. 15,1091 09:1326
i.l. -
DO 01466?
';J, i-r-- OONFJOFNTTA!
' -S.
iAFETY KMOlPdEOT
SPECTICLE BLIND
HAMER BLINO
FI
TRACING
T=SI!L T=NONE
PS* PS*
RHPID11 10/B9
C^DGN/RHPID11.DGN Sp. IS, 10911030622 <jT" V-
INSULATION TRACING AND INSULATION
PIPING
C=F7 C*F4PP
T*STM T=NONE C=F7 C=F4PP PS= PS=
.*
DO 014608 CONFIDENT T A1
iOTS B>EWE1LIPEB SYIIEOL:
CO
PITOT TUBE
GEAR PUMP
MONO PUMP
RHPID17 9/91
C^DGN/RHPIDI7JDOH Sp. 16,169117:38:05
+ .-I , *,-i \'s ' ; t-5"^mT. ,- * : -* .?<*** .v\j * - . .* -s. 'Fv^
DO 014670 nONFTOFNTTAI. -
'' *-v >' 7 >'*
' Vv-y zj:
MTO!. SST^TTOM L W M@ W
RHPID12 10/80
;' no oi4f>7i
` CVDGN/RHP1D12.DGNS*p. 15,199111:1432 '
'
r?f f ONFTDFNT T Al
P>U1MIP STATOIM @ILE> V8 IMID W
RHPIDU 10/00
C:/DGN/RHPID14.DGN Sop. IS, 19911123:18
no
01 46^0
tdfnttai
conf
TWOAIL
(H1
RHPID13 10/80
C:/DGN/RHPID13.DGN8p.15,1991 11:3341
4-. ?; -
DO 014670 C0NFTDFNTTA1.
TI RAFIK ATM Eli Piwoa
TEMP ELEMENT W/ THERMOWELL
TEMP ELEMENT WO/ THERMOWELL
DUAL TEMP ELEMENT W/ THERMOWELL
TT W/ THERMOWELL AS A UNIT
TT (FIELD MOUNTED) W/ SEPARATE
THERMOCOUPLE * WELL
TEMP INDICATOR W/ THERMOWELL SPECIFIED TOGETHER
CAPILLARY TEMP INDICATOR W/ THERMOWELL & INDICATOR
SPECIFIED TOGETHER
THERMOWELL ONLY
RHPID1S 10/89
C-/0GN/RHPID15.DGNS*p. 15,199111:3fc26 ^
v-
DO 014674 OONFTDENTT Al
MM-OME FL@W IIWOCI
MAGNETIC FLOW METERS. TURBINE METERS. VORTEX SHEDDING METERS, SONIC METERS,
TARGET METERS. AND OTHER SIMILAR IN-LINE FLOW DEVICES
Ft FT 101 102
ORIFICE PLATES FLOW TRANSMITTER
W/ REMOTE TRANSMITTER
W/ BUILT-IN TRANSMITTER
FLOW METERS
ROTAMETER
ORIFICE
RHPID16 10/89 ,,
C^DON/RHPIOI 0.OGN $p. 15,1961 1153:39
ORIFICE PLATES. DUAL-FLOW TRANSMITTER
no 01 4fj7Fi
rONFTDFNTTAI
SCHEMATIC ON
MATERIAL LIST (7) TBV Vi' NPT-?????
(F) ROSEMOUNT MOUNTING AOAPTOR.????
HUBER MAGNUM SERIES S22 OBL.FLG. 3J WITH MOUNTING BRACKET
NOTESt
01 4f>7F,
r,nNFTOFNTTAl
1 ALL P1PE.F1TTINGS & VALVES SHALL CONFORM TO PIPE SPECS. 2. SUPPORT TUBING CONTINUOUSLY FROM PROCESS TO TRANSMITTER.
< 3* FIBERGLASS CHANNEL EXTREN 500)
3. TU8ING SHALL SLOPE FROM PROCESS TO INSTR. A MINIMUM OF !4*PER FOOT. 00 NOT TRAP.
SPEC. BY
HPS
THE DOW CHEMICAL COMPANY
** SA01-7G851
CHECKEO. ?? VINYL II - -
. . . ;.V;
-'
APPD.
- FLOW "TRANSMITTER DETAIL
f' -h , ` > v- - .0 \ - ,
'
oatej
3/16/88 REVISION OATE A
B | .
-------------------------------------------- ------------------------------- --:--------1----------------- ;
1
BLOCK CC r;, INSTRUMENT
` ' `V- INSTALLATION DETAIL
OCTAL N&
ar 2
-"-*A6-1077
TAG ITEM -1
SCHEMATIC Or
MATERIAL LIST
(7) TBV J$*NPT-????7
(2) TBV Vz' NPT-?????
@ J4*MALE PLUG
**T *V4*npt male connector
ALL TUBING TO BE %' MONEL ALL TUBE FITTINGS TO BE MONEL
ALL TUBE VALVES TO BE SWAGELOK M44S6 BALL VALVE
,a HUBER MAGNUM SERIES S21 SNG. FLG. 7> WITH MOUNTING BRACKET
NQTESi
1. ALL PIP&FITTlNGS & VALVES SHALL CONFORM TO PIPE SPECS.
2. SUPPORT TUBING CONTINUOUSLY FROM PROCESS TO TRANSMITTER.
C y FIBERGLASS CHANNEL EXTREN 900)
^
__
3. TUBING SHALL SLOPE FROM PROCESS TO INSTR.A MINIMUM Oi 00 01 4677
PER FOOT. 00 NOT TRAP.
CONFTDFNTT Al
SPEC. BY
HPS
THE DOW CHEMICAL COMPANY
* SS01-76A2C
OCCKEOi ?? VINYL II
BLOCK K
INSTRUMENT .
APPth
FLOW TRANSMITTER OETAIL
INSTALLATION DETAIL
OATEi 3/16/8*5 REVISION OATE A
: |
OCTAL ML
-------------------------------------------------------------------------------------------------------- 1 WT l flf 2_____
A6-1071
TYPOOAIL OM8TAILILATOON
V
TRP 1
NOTIi STRAIN1R UiKD IP NOT INTIRNAL TO TRAP
on oi467a CONFTDFNTTAI
CW T-XXXXX
00 014679 OONFTOFNTT AL
Y>M*Y
SET o I50PSIC
SET Q 10PSIG ,
TYP. A
VHT-
SET 150PS1G TYP#
PflQ-XXXXX- X -X )
DO 014880
oo 014681
CONFTDFNTTAl
I
USE k CARE OF PORTABLE
COMBUSTIBLE GAS
k
OXYGEN METERS
I. REASONS FOR HAVING THESE METERS
A. DIVISION HAS 22 PLANTS WITH PIPES. VESSELS, AND CONTAINERS WITH FLAMMABLE. EXPLOSIVE AND NON LIFE SUPPORTING ATMOSPHERES.
B. EMPLOYEES MUST ENTER OR OTHERWISE BE EXPOSED TO THESE ATMOSPHERES FROM TIME TO TIME.
C. METERS ARE USED TO ASCERTAIN THE CONDITION OF THE ENVIRONMENT TO WHICH WE ARE GOING TO EXPOSE OUR PEOPLE.
D. LET'S US KNOW WHETHER IT'S SAFE TO OPERATE EQUIPMENT.
f I
on 014<Sfl3 CONFTOFNTTAl
III. ABOUT THE METER (actually two meters in one)
A. OXYGEN -
ELECTROCHEMICAL FUEL CELL THAT DEVELOPS A VOLTAGE WHICH IS PROPORTIONAL TO THE OXYGEN CONCENTRATION OF THE GAS PASSING THROUGH THE CELL. THE CELL IS DEPLETED OR USED UP AS OXYGEN MEASUREMENTS ARE MADE.
B. COMBUSTIBLE -
CATALYTIC BEAD IN CELL WHOSE TEMPERATURE IS CHANGED BY THE AMOUNT OF COMBUSTIBLE GAS IN THE SAMPLE. AS THE TEMPERATURE IS CHANGED, ITS* RESISTANCE CHANGES. UNBALANCING ONE LEG OF A WHEATSTONE BRIDGE CIRCUIT COMPARED TO A SECOND BEAD WITHOUT CATALYST THAT WILL NOT REACT TO THE COMBUSTIBLE GAS. THIS TYPE OF CELL REQUIRES SOME OXYGEN (10%) FOR SUCCESSFUL OPERATION.
I
On f'rwr
IV. TERMS
A. LEL (LOWER EXPLOSIVE LIMIT - The least concentration of a combustible as m air that will lKnite
B. VAPOR DENSITY - The weiRht of a sas as compared 10 air.
C. OXYGEN DIFICIENT OR RICH ATMOSPHERE The combusubJe as sensor requires at ieast 10 * oiVRen anti a maximum of 25 oivgen to work accurately
ii
DO 0146R.S
donftdfnttai
lover EXPLOSIVE LIMIT (LEL)
00 014686, OONFTDFNTTAI.
OXYGEN DEFICIENT ATMOSPHERES & YOU
nXYRFN % IN AIR (APPROX. 21 X NORMAL)
12 - 18%
10 - 12%
AT RFST SlfiNS & SYMPTOMS
BREATHING & PULSE RATE INCREASED; COORDINATION POOR.
DEEP, FAST RESPIRATION; GIDDINESS; POOR JUDGEMENT; LIPS BLUE.
8 - 10% 6-8%
4% 0%
NAUSEA; VOMITING; INABILITY TO MOVE FREELY; UNCONSCIOUSNESS; ASHEN FACE.
8 MINUTES - 100% FATAL 6 MINUTES - 50% FATAL 4 MINUTES - ALL RECOVER WITH TREATMENT
\ 1
COMA IN 40 SECONDS; CONVULSIONS; RESPIRATION CEASES.
INDIVIDUAL IMMEDIATELY BECOMES UNCONSCIOUS; WILL RECOVER ONLY IF GOOD AIR IS IMMEDIATELY AVAILABLE
WARNING: THE WARNING SYMPTOMS OF AN ATMOSPHERE
DEFICIENT IN OXYGEN ARE COMPLETELY INADEQUATE AND, ALTHOUGH. A TRAINED OBSERVER MAY, WHEN ALERT, RECOGNIZE THE INCREASE IN PULSE AND RATE OF BREATHING IN TIME TO RETURN TO GOOD AIR, THE AVERAGE INDIVIDUAL FAILS TO RECONIZE THE DANGER UNTIL HE IS TOO WEAK TO SAVE HIMSELF, ESPECIALLY WHERE THE RETURN TO GOOD AIR INVOLVES CLIMBING STAIRS OR A LADDER.
DO 014687 CONF TDFNT T At.
EXPLOSIMETER LIMITATIONS-IT CAN'T DO IT ALL
Instruments by design and application, have specific limitations. The Explosimeter is no exception. The following information indicates these areas, and it's imperative that anyone operating an explosimeter know and understand them before using them in the field.
1. The explosimeter is a tool to assist in the planning and preparation of some jobs (hot work, vessel entry, etc.). It does not replace pre paration,planning, and common sense, and should not be regarded as a guarantee that a job is safe.
The explosimeter cannot measure or detea chemical irritation and/ or toxicity.
The explosimeter is designed to process certain gasious or "dry" vapor samples only. It should not be used on liquids, solids, dusts, mists, or wet" vapors.
A. The explosimeter is designed for use over a temperature range of 10 - 110 F. If a unit is to be used in a area where the ambient temperature is 110 F or above, the explosimeter should be first checked and calibrated under similar conditions. Make sure-the area used to check the meter is known to be free of combustibles. Sample temperatures should be the same as the explosimeter, otherwise, condensation of the sample vapors may occur causing false readings.
5. The explosimeter is designed to detea the presence of flammable gas or vapors in air; it will not work on such gases in inert at mospheres.
6. The explosimeter should not be used to check for flammable mix tures which contain less than 10% or more than 25% oxygen.
DO O14688 OONFTDFNTTAl
7. There are some gases which affect the accuracy of, or damage, the oxygen sensor. Strong acid gases (HQ, sulfuric, etc.) may damage the oxygen sensor by permanently changing the pH in the electro chemical cell
R. Some gases or vapors, even though non-flammable, may result in explosive readings if sampled. Helium, because it is lighter than air, has a cooling effect on the sensor causes a negative response. Argon tends to insulate the sensor and cause an increase in the meter s response. Many Freons decompose upon contact with the sensor and cause an explosive reading.
9. Tetraethyl lead, silicones, and many sulfur compounds will poison the catalytic activity of the combustible sensor causing incomplete combustion and lower explosive readings or no response at all.
10. Keying portable radios within 10 feet of the explosimeter can cause false readings on the explosimeter.
r>0 014689
( t'ONFTOFNTTAI
PRE-USE CALIBRATION CHECK OF BIO MARINE 902 & GASTECH GX-3 COMBUSTIBLE GAS/02 MONITORS
1. CHECK UNITS WITH HOSE & PROBE CONNECTED..
2. CHECK FILTER & WATER TRAP. SHOULD BE CLEAN AND DRY.
3. CHECK BATTERY VOLTAGE. NEVER CALIBRATE ANY METER WHILE PLUGGED INTO THE CHARGERl
4. CHECK PUMP FLOW AND ALARM.
5. CHECK OXYGEN READING IN AIR. SHOULD BE 21%. IF NOT, ADJUST TO READ 21%.
6. CHECK COMBUSTIBLE GAS ZERO. IF NOT ZERO, ADJUST TO READ ZERO.
7. INTRODUCE CALIBRATION GAS (2.3% METHANE IN AIR). COMBUSTIBLE GAS METER SHOULD GO UPSCALE TO 2.51 ON BIO MARINE UNITS OR TO 55% LEL ON GASTECH UNITS. IF READING IS INCORRECT, ADJUST WITH GAS SPAN POT TO OBTAIN PROPER READING. THE SPAN POT FOR 310 MARINE UNITS IS LOCATED ON TOP CONTROL PANEL. THE SPAN POT FOR THE GASTECH GX-3 UNIT IS LOCATED IN THE FRONT CHAMBER,
FSPAN POT #3. \ 8. IF UNITS CANNOT BE ADJUSTED PROPERLY, OR IF YOU FEEL THE UNIT IS NOT OPERATING CORRECTLY, DO NOT USE IT. TAG THE UNIT AND SEND IT TO THE CENTRAL INSTRUMENT SHOP FOR A THOROUGH CHECKOUT AND REPAIR.* 1
PRE-USE CALIBRATION CHECK OF GASTECH 1214SMP COMBUSTIBLE GAS/02 MONITOR
1. CHECK UNITS WITH HOSE & PROBE CONNECTED.
2. CHECK FILTER & WATER TRAP. SHOULD BE CLEAN AND DRY.
3. PRESS RED "POWER" SWITCH TO TURN UNIT ON. THE STATEMENT "GASTECHTOR ON - TAKE TO GAS FREE AREA" WILL SOUND AND DISPLAY WILL BLINK. THE UNIT DISPLAY WILL CONTINUE TO BLINK FOR A TWO MINUTE WARM-UP PERIOD.
4. AFTER THE TWO MINUTE WARM-UP PERIOD HAS ELAPSED, THE STATEMENT
"PRESS ADJUST BUTTON" WILL SOUND. PRESS THE BLACK ADJUST BUTTON.
UNIT SHOULD THEN READ 20.9% 0, and 0 COMBUSTIBLES. ANYTIME THE
ADJUST BUTTON IS PRESSED THEREAFTER, THE UNIT WILL DISPLAY THE
NUMBER OF BATTERY HOURS REMAINING.
on 014690
5. CHECK PUMP FLOW.
ft rONFTDFNTTAl
6. INTRODUCE CALIBRATION GAS (2.5% METHANE IN AIR). METER SHOULD READ 551 LEL. IF NOT, ADJUST SPAN POT LOCATED ON SIDE OF UNIT AND MAKE METER READ 55%.
7. IF UNIT CANNOT BE ADJUSTED PROPERLY, OR IF YOU FEEL THE UNIT IS NOT OPERATING CORRECTLY, DO NOT USE IT. TAG THE UNIT AND
CHECKING FOR COMBUSTIBLE GAS IN INERT BACKGROUND USING SPECIAL FITTING ON STANDARD EXPLOSION METER
1. Calibrate unit without special fitting using 2.5% Methane in air cal. gas. Combustibles should read 55% LEL. If not, adjust span so that meter does read 55% LEL. Oxygen should read 21%.
2. Put special fitting on unit and introduce cal. gas again (2.5% Methane in air). Combustibles should read approximately 27.5% LEL. Oxygen should read 2IS.
3. Put 2.5% Methane In Nitrogen in unit. Combustibles should read about 27.5% LEL. Oxygen should read approximately 10.5%.
4. THE UNIT IS NOW READY TO BE USED.
5. After a line has been checked with a standard (without fitting) meter and the line has less than 10% oxygen, you would then use the special meter (with fitting) and check the line for combustibles.
f
i
6. Always be aware of your oxygen reading when using the meter with the fitting on it. Your oxygen reading can tell you many things. For example, the oxygen reading taken without the fitting must differ from oxygen reading taken with the fitting in place.
NOTE: ANY COMBUSTIBLE GA5 READING OBSERVED WHILE USING THE UNIT MUST BE MULTIPLIED BY TWO TO OBTAIN THE ACTUAL %LEL.
rONFTDFNTTAl
METERS ARE NOT DESIGNED TO
TAKE LIQUID SAMPLES
' DO 01469? rONFTDFNTTAt
CAUTiON 1 NITROGEN
PAD IN use1 ON FLAREPACK.
ME7ERS SHOULD NOT BE USED TO
IEA SURF COMBUSTIBLE GAS IN
ATMOSPHERES THAT ARE OXYGEN
DEFICIENT
00 014690 COIMFTDFNTTAI.
V
r ^ GAS TCT~ORR CXKLLEE
TAKF TO BLASSS AttFA
`TEfRA ETHVL LEAD OR SILICON COMPOUNDS POISON COMBUSTIBLE GAS SENSORS
DO 0 1 4 6 9 4
OONFTDFNTTAL
BE" ALERT!
O1 4 ^
CONFTOFNTTA!
DO 0 1 4 6 9 6
C O N F ID F N T T A l
-------------------------------
---------------- - w *
.---------- Ul L /
WHEN ACTING AG SAFETY OBSERVER
Always look for potentme hazards
FROM SURROUNDING AREAS
BE ALERT!
00 O ? 4697
CCiNF 7 OF NT IAL
ACIDSAFE. CMP
MINIMUM SAFETY EQUIPMENT REQUIRED IN C!. M. P . ACID AREAS
WALK - THRU
OPEN LINES BLEED DOWN
C--202 BTMS.
E-212 H2S04 T/C RACK (CAR CONNECTED) T--900 C--650 C--202 DECKS H2S04 T/C RACK (CAR NOT CONNECTED) C-210
C-200 / C-201 BTMS. P-30) 'S C-610 / R-600
SLICKER SUIT / GOGGLES / RUBBER BOOTS, GLOVES
SAME AS ABOVE SAME AS ABOVE
SAME AS ABOVE SAME AS ABOVE
GOGGLES GOGGLES
GOGGLES
GOGGLES GOGGLES GOGGLES
FULL ACID SUIT
SAME AS ABOVE SAME AS ABOVE
SAME AS ABOVE SAME AS ABOVE FULL ACID SUIT GOGGLES (EXCEPT H2S04)
SLICKER SUIT / GOGGLES / RUBBER BOOTS, GLOVES SAME AS ABOVE SAME AS ABOVE SAME AS ABOVE
SAMPLES. C-200 / C-201 C-610 C-650 H2S04 T/C C-202 BTMS.
SLICKER SUIT / GOGGLES / RUBBER BOOTS, GLOVES SAME AS ABOVE FULL ACID SUIT FULL ACID SUIT FULL ACID SUIT
* CONTRACTORS IN AC I*) AREAS FOLLOW A DIFFERENT SET OF PROCEDURES. (SEE PROCEDURE FOR CONTRACTORS WORKING IN ACID AREAS.)
revised: 2/91 JRC/DRD
Ol 46923 oonftdfntta,
*- + - **
iS&L pBKkiij
!l > / \ CHLORINATED METHANES
SAFE JOE PROCEDURE
.apartment:, CMP
ob Title: R--250 PROBLEM SOLVING
-cope: GENERAL INFORMATION ON POSSIBLE PROBLEMS AND CORRECTIVE MEASURES
1. POSSIBLE CAUSES OF HIGH INLET PRESSURE ON R-250A
A. The reactor is carbaning up causing a large pressure drop making it more di-f-ficult to run the same loads. (May need to cut the reactor rates and run in this condition until the reactor can be recharged)
t k w.''c Lwivc 1 ^z "3 cp. ^ rcC'c'^or ^ 0 u ii F`" in^5 )
- > t i .... w c r.c c-iz-.-r ] ca ; c ,-er -from E-256 into E-245, causing : r, \j 1 r, E-245 which results ir. pressure swings. (Check
tr:''"".:" + r ; _ -a Lure pro-fils, carrying over liquid can - . t'"c c .7 c c c ' and oil tempers ture ' s tc decrease. Also - k i. s "-i-u',:: -flow r.eters, a- they are swing badly that ' : -..........-_:.ccic fracing af-csc the -flow meters.
-
r --
1
rr
r t r -- - -- k >'t * a f
r r; =r c: t? ir-ir fiM p,,ne;<-*A
high, inlet pressure
Ur-./ THE ME011 LOU PRESSURE SWITCH ACTIVATED.
pump trapped o-ff lore. When activated it 4- 4-- c- j1 i> i l tr1 y pur. p *
. Have someone check pumps and reset switchgear, cr repair.
R Recirculation valve on pumps is opened to much -for the load you are attempting to run.
a. Cut the recirculation valve back
C. Excessive rates or, both R-250's. (cut rates)
' -T-- *
j
li
DO 014699 CONFTOFNTTAl
Vi, HE adt
V!v
R-250 PROBLEM SOLVING
PAGE 2
' I ON r-ROM 3
L' . ;witch Ma 1 f unc tioned .
.. I f the au:; i 1 lary pump activated, did the switch clear.
i. Check TDC group 77, meoh -flow transmitter and see it the incoming flow is still stable.
. Check E-256 level and valve output. Has the valve output started increasing trying to maintain level, if not the switch is probably bad
. Contact instrument personnel to repair has to be shutdown/h.-2l 3
i-- I I
--' 1
*.*_ "W
_ *-- A- .
^11^ t I/-1,--rl-11 >--i --.
_ i i i-
i ..... . C W 1. i I g
uc. - tr.e column recycle temporctare to cecrea.se the overhead
:.. r H _ i u c
quc,,;. r; relemns. r: r: the overheat temp
:cr tre 1
is C Cr ,Ti Jj tz f >c. u. l_Cl O'*"
the quench
erheaca.
i pi \ J ^ W1 V1! *_ I
*- >
tc tlit. tnre, from Eh-Z59 should be about
1. i ,
O; *. w C_ ! o tLi
lee if it's running ^ v
tc cA 1" . .
ehac,: L" Lvf ref la,: flow. May be to low (increase)
Cheer. C-203 R-12 level may be to low (increase)
7 Blow down the level transmitter it may be full of
oil causinq a misce11aneous reading.
e. Check E-259 level transmitter. If this trans is indicating a level and E-259 is actually empty, we will be blowing baiK to C-350 (this is just as if the system wasn't on line!
Z. Increase in Ml from C-840.
a. Check. C-S4C overhead temperature, Make sure it is running normal. If not qoto "b"
L. Cneci. D-E340 R-12 level. Should be running appro:-; 357..
DO 014700 CONFTOFNTT Al
-'.m&t " %T j# ^ 3t-j. ,
*
aw. ***'--+* -<- '
-
*
R-250 PROBLEM SOLVING
OOKTI NJATION- PROM "#5
"
--
PAGE 3
C. Sor, acne may have increased the N2 seal purges on K~350. Check arid make sure its C?i t 3. normal rate.
L. A piece of equipment which contain N2 due to padding or purging has jsut been placed in service.
E. N2 ESW ' s on the R-250's are leaking by. Manually block them in.
L. PEE SI EMI REASONS WHY THE INDEPENDANT HIGH LEVEL ALARM ACTIVATED ON E-E5E.
A. It is aetua11y true.
.ediatly cut back you level in E-256 monitoring the
don't want to take a chance of pumping liquid into
fT* -
- - 1 --If w
J.
w. U I CA
+ i_ --,, T _ t_ r_
^
1 U > L . w i i Lc C i Ci ! ill L 1 fb I =r >
pressu the
icck both level transmitters see if they agree. Should be
m.r.1,,0 ucoro,. ELMO'... If
are both running within their
range arlw a..!' e_ ills Si-, i to i. may1 to bac. However; if
... io.,L:c) tr a, c,,,. vlc : -s :c<-.oir.q within tL normal range
ii 1.111--. ri^^iiiw^.i.i xCiC^ ir.diuQ
11.1 a u c 113) is rCu^inC
-* *-- --^ v."wt. i * *i- i,'r UfLciLi v' r
*l * !\l>Tt_ i yww c =.n
ij
i _ ic-
;
W 1 . _ \ Ic u c w
wi
,, I, J. gc q, u
. i -c -. O,
bJ l t
v dvet
w i loll i _j
tr.ey are swinging then across the flow oriface.
failing.
ti' a.'.s.i.itiers checked by instrument personnel.
. c.'c c.'.cci.s o,..
. ha. a instrument personnel check
Will THE AD I BAT I L
MOREL SLOWLY INCREASING.
When the isothermic section of the reactor starts to carbon up it degreases the amount of reaction that takes place in the sop section therefore; the reaction increase in the bottoms i-------cion. With more reaction there is more heat. (INCREASE THE OIL TEMPERATURE A PEW DEGREES HOTTER THAN NORMAL. THIS WILL HELP BRING THE REACTION BACK UP INTO THE ISOTHERMIC SECTION).
If the Inlet OIL TEMPERATURE is too low it will cause the icotncrmic section of the reactor, to run at a cooler rate which will not be suffecient to react the HCL and MEQH. As in item (A; the r..a_jc: itv of the reaction will take place ir the bottom of the reactor. (INCREASE THE OIL TEMPERATURE
D IT E NORMAL OPERATING LEVEL)
Excessive rates can cause the bottoms temperature to increase iLOWER THE RATES UN THE REACTOR TO REDUCE TEMPERATURE)
00 014701 r.ONFTOFNTTAl
y-- s '
(
'n
i i
*1.
h
I
R--250 PROBLEM SOLVING
PAGE 4
e. POSE I EuE causes of low inlet and reactor temperatures.. ft. Licuid in the inlet line
a. Check E-25E level, it may be carring over liquid
(see item.it 11 )
.
h. Lest heat transfer in superheaters.
V, *
a. Check oil temperature to superheaters and also check
control temperature. (IF THE OIL TEMPERATURE IS OPERATING
ELcQW NORMAL CONDITION INCREASE) ,
,,> - - .. f.
c. Lew til flow to the reactor due to low setpoint settir.q,
control valve problems,transmitter problems and pump problem.
<
II sne nr c re nctucr were cc orift nigh at would ct.w.se one .'w.lvc- cucpw.t to decrease, thus ceore-esane the actual oil . - ow tlrcc.gr. t,L reactor. Check the total oil flow transmits t_ the i1 occ tore and do some calculation to see af the number:
jcl tweer,
'0 pounc de psr.d ir.q
JFE' E
~-^Lufi.(TL2 rL^nW^n. Tplt* c Ta HLsh1 *1
t or c 1 j t w
KI"
1--
" :r ittci' is malfunctioning
blew tr.c hagr. ant low level legs of the transmitter down arid sec if after blowing dawn it quits swinging. If not nave instrument personnel check.
;i:_E REASONS THE LOW LEVEu ALARM ACTIVATES ON E-256.
E-25E level is actually low.
a. Check- the pressure control valve. If the level is actually lower than normal the valve output on the steam valve will be higher than normal, for any given feed rate. The pressure me, br falling. If the exchanger goes empty the steam valve will go wide open trying to control pressure and the pressure wil! or.tinup tc fall.
IP "
Oo COh/p?
T0b1ptNyt0xp01
m*L.
_ ar? i ****<-
-ILO-aiLf
R-250 PROBLEM SOLVING
PAGE
CJNT INL AT I ON OF ITEM #10
b. Check the redundant transmitter on E~256 which is located
in group 118 on the TDC. See if the level indication agree's
with the control transmitter. If so than the transmitter is
I probably ok. If not have instrument personnel check the
i> transmitter.
\
'
r ., * . /
' V- } s
j >t
4 c. The level setpoint may be set to low. (increase) i s'.
d. The P-255 tripped off line or the recirculation valve on
the pump is open to much for the feed rate you are trying to
run (there is a MEOH header low pressure switch which will
activated if the pressure gets low and it will enegize the
auxiliary P-255).
e
E-25i `PF.;
.'RE SLOWLY-DECREASING AND STEAM VALVE
RE-'ESKS THE '.CD ICON KEEPS YLL FROM GOING ON HEAT UF.
rzbiccr. porn., ssi vc a ha./n't been met
-. H
flow ..as g"ester cr.ar 3O'O'O+f hr or the HCL control
vr . 'c
tp'j-1-
sn ' t it "ZE^C when the ''HCL AOV" switch
sc. * to tra ig-'r pc-s_tic" ;;,d the reset button was hit.
It;:,
w:: ci:, newever; er.ee the modicor. opened the
. ;L. AO. ' the oper:tor fazlcs tc reS'Sh the minimum
i-iiL. c1- Mi flew requires in the time frame <120 sec) allowed
i -- 3 ` < M -- Cl mm i
c. . when using the HCL heatup or Ml and the flow falls below tht m^r.iT.tiT. setpoints.
Tr.s "AOV" has mal f un ticned. Cneck the air to the AOV, If ok, have instrument personnel check transmitter.
Lr . Faulty HCL ADV SWITCH on tne board. Have instrument personnel checl .
D Fault in the program. If items "Aa,B & C" are ok contact modico; personnel.
.V -
D0 014703 CONFTDFNTTAL
wmpumim :E' -4..
Q'J'C ^j-A
PURPOSE:
BASIC PUMP MODULE
This module is to familiarize you with the Basic Operation and maintenance of a pump. On completion of this module, you have a basic understanding of how a pump operates and the necessary maintence required for. proper pump operation.
r
RESOURCE: (Pump Pilot Course,Human Resource,Pump manual)
REQUIRED LEVEL OF PERFORMANCE: 100%
OBJECTIVES:
1. Explain the operation,function, maintenance and instrumentation on the following.
A.'Seal D. Seal Flush G. Lubrication
B. Coupling E. Motor + Starter H. Impeller
C. Coupling Guard F. Recirc. Flows
2. Physically locate and explain the function and operation of a start/stop station and the corresponding switchgear,including auto or remote start/stop and variable speed on any given pump.
3. Explain and special safety hazards associated with the equipment.
4. Explain what the major causes of bearing failure are,and how these conditions can be eliminated.
5. Explain what the major causes of seal failure are, and how these conditions can be eliminated.
6. Demonstrate checking and adding oil to any given pump.
7. Demonstrate how to properly locate all pump parts at the cellulose warehouse using the pump parts book.
8. Demonstrate the proper procedure for taking a pump out of service and checking it for maintenance.
9. Complete a simplified drawing of the oil miBt system.
10. Explain the function of the oil mist system and how it operates.
11. Explain how you would determine what type oil is used for the oil mist system.
12. Explain why rotation is checked on a pump after the motor has been changed out or the electrical system has been worked on.
13. Explain the following.
A. Mag Drive Pump C. Centrifical Pump
B. Can Pump D. In Lin Pump
D0 014704 OONFTDFNTTAl
14. Explain the difference between a Mag Drive Pump and a Canned Pump.
DIFFERENCES BETWEEN CAN AND MAG DRIVE PUMPS
Both canned pumps and magnetic drive pumps have moving parts and sleeve bearings, which are lubricated by pumping fluid through them. They both lose efficiency because of the can.
Magnetic drive pumps use conventional,exterior mounted motors,were as canned pump motors are an integral part of the pump.
The canned pump motor is subject to the heat of the pumped fluid and the motor also adds heat to the pump.
In a mag drive pump the only barrier between the fluid and the moving parts is a non-magnetic can . In a can pump the motor shell provides containment since there are no moving parts outside of the can. This allows the can pump to be used with a higher pressure application.
The can motor is considered safer for critical application. Although the mag drive pump can be made thicker to retain high pressure,it further reduces electrical efficiency.
_____
HO 014705 OONFTDFNTTAl
MAGNETIC DRIVE PUMPS
Magnetic drive pump looks like a regular conventional pump, but their operating principles and design are quitedifferent.
The main and most distinct difference is that magnetic drive pumps are sealless - no mechanical seals as in conventional pumps. In magnetic drive pumps, a conventional motor drives a magnet which in turn drives another magnet that is attached to the back end of the pump shaft. The two magnets are separted by a non-magnetic can (shroud). This shroud,which is usually .020-.080" thick, is the only protection you have of maintaining the liquid within the pump or preventing an environmental incident. For this reason, the shroud should be monitored at all times. Nearly all malfunctions can be detected by monitoring the liquid temperature in the shroud area. Approximatly 3-5X of the pumped fluid is required to lubricate the shaft sleeve bearings and remove heat in the magnet area.
The main reasons for magnetic drive pump failures are:
1. running dry/cavitation 2. dead heading 3. solids in the fluid 4. permanently greesed anti-friction bearings
The magnetic drive pumps are equipped with two thermocouples to show signs of these problems. The front thermocouple measures the temperature of the recirculated fluid used to lubricate the bearings and remove heat from the magnet area. This thermocouple will protect us in the event we dead head the pump,start the pump with the suction blocked or anything else that will cause this fluid to heat up. The back thermo couple monitors the temperature of the bearings or misalign ment problems. These temperature points should normally run about 10-15 deg c above the inlet fluid temperature with the alarm set at 20 c above the inlet temperature; therefore as the ambient temperature changes or during seasonal changes we may have to adjust the alarm setpoint. The most important thing is that if you get the alarm 20 c above the inlet temperature, you must react quickly.
The recirculated fluid serves a very vital function to the operation of the pump. As indicated above, its purpose is to lubricate the shaft sleeve bearings and remove, heat in the magnet area. There is a minimum flow required to remove the necessary heat from the pump. This is the reason for the automatic recirculation valve on P-259B. If someone blocks in the discharge, the automatic recirculation valve automatically bypasses a designed amount of fluid to remove the heat. If this is also blocked in, you will wreck the pump.
MAG DRIVE PUMPS
PAGE 2
TROUBLE SHOOTING
If you get an alarm 20 deg c above the inlet temperature, immediatly investigat to try to determine the problem.
1. Look at the discharge pressure guage to make sure the pump is not cavitating. If it is, immediatly shut the pump down and correct the problem.
2. Listen closely for any noise. This is also an indication of cavitation or the pump may be running dry.
3. Check to make sure that everything is lined up properly. Check the pump recirculation first.
4. Feel the pump by hand to see if it is truly running hotter than normal; however,if both temperature points increased, the instruments are probably correct.
5. If all else fails, call maintenance tech to check for vibration or excessive rubbing problems.
The main point to remember is that you need to take action as soon as you get an alarm.
GR 9/89
DO 014707 OONFTDFNTTAI
CANNED MOTOR PUMPS
A canned motor pump is a sealless centrifugal pump. In the pump the motor rotor is connected to the pump shaft and enclosed in a non-magnetic "can". This assembly is then inserted into the motor stator. The magnetic stator drives the rotor,just as with a conventional motor. Since the can is imposed within the magnetic field, the motor efficiency is reduced;
The rotor and all the bearings and moving parts of a canned motor pump are inside the can and exposed to the pumping fluid. This requires a sleeve-type bearing that must be lubricated by the fluid.
Canned motor bearing especially the rear bearings can get quite hot. Heat is generated by bearing friction as well as by the totally enclosed motor. To prevent flashing or decompositon of the lubricant and premature bearing failure, canned pumps must provides a positive flow of pumping fluid through the bearings. In some applications the fluid may have to be cooled or filtered before entering the bearings. GR 9/89
DO 01470ft rONFTDFNTTAI
ITEM
BASIC PUMP MODULE RESOURCES DEFINITION
ADAPTER - A mechanical piece used to permit assembly of two other parts or for a spacer.
ADAPTER,BEARING - A cylindrical piece used to mount a beraing on a shaft.
ADAPTER,TUBING - A cylindrical piece used to connect discharge case to encloseing tube.
BASE - A metal pedestal to support a pump.
BASE PLATE - A metal plate on which the pump and motor are mounted.
BEARING,INBOARD - The bearing farthest from the coupling of a pump.
BEARING,OUTBOARD - The bearing nearest the coupling of a pump.
BEARING,JOURNAL THRUST - A removable cylindrical piece mounted on the shaft and which turns in the bearing.
BOWL - The enclosure within which the impeller rotates.
CAN,ROTOR - A thin cylindrical part that separates the motor rotor from the pumped fluid.(can pumps)
CAN,STATOR - A thin cylinedrical, non-magnetic part that separates a stator core assebly from the pumped fluid.(can pumps)
CASING - The portions of the pump which includes the impeller chamber and volute.
CAVATION - When the pressure at the inlet drop too low then bubbles form and absorb heat. As these bubbles move out to the higher pressure the bubbles collapse. This collapse can be quite violent and can cause severe damage.
COUPLING- A device which is used to connect the motor to the pump.
COUPLING GUARD - A protective shield which is placed around/over a coupling.
COUPLING KEY - A rectangular piece of metal used to prevent the shaft from rotating inside a coupling half. DO 014709
----------------------------------------------------------------------------------------------------------- ---------------- CONFTDFNTTAI
DEFLECTOR - A flange or collar around a shaft, rotating with it to prevent passage of liquid,grease,oil or heat along the shaft.
DISCHARGE CASE - A guide for liquid flow from the bowl to th pump
column.
PAGE 2 FRAME - The part of the pump which the bowl and bearing housing are
assembled to and houses the rotating unit.
GASKET - material such as garlock or teflon of proper shape and characteristics for the use in Joints and between flanges to prevent leackage.
GASKET,BOWL - A gasket (garlock,teflon) that is used to seal the joint between the main pump body and the bowl.
GASKET,IMPELLER - A material used (teflon) to seal the joint (space) between the end of the pump shaft sleeve and the impeller.
GLAND - A follower which compresses packing in a stuffing box or retains the stationary element of a mechanical seal.
HOUSING,BEARING - A body in which the pump bearings are mounted. HOUSING,STATOR - A body in which the stator is mounted.(elec )
IMPELLER - The bladed member of the rotating assembly of the pump which imparts the principal force to -the liquid pumped.
IMPELLER KEY - a rectangular piece of metal used to prevent the impeller from rotating relative to the shaft.
LOCKWASHER - A device used to prevent loosening of a nut.
OILERS - A device/sightglass which is used on the bearing housing of a pump to maintain a level of oil in the bearing housing.
OIL SEALS - A device used in the bearing housing of a pump to seal the oil in and keep it from escaping to atmosphere.
OIL MIST SYSTEM - A system which supplies a fine oil mist through tubing into the bearing housing of a pump. This type system eliminates the use of oilers on a pump. 00 014710 OONFTDFNTTAI
PAGE 3 RELIEF VALVE - A mechanism to control the maximum pressure that the
pump can put out. ROTOR ASSEMBLY - A rotating assembly of an electrical machine
containing laminations and conductors,interaction with a stator core assembly produces torque.
SEAL - A device used to prevent the flow of a liquid from the pump suction/stuffing box to the atmosphere.
SEAL,MECHANICAL - A device flexibly mounted on the shaft in or on the stuffing box and having a smooth face held against the stationary sealing face.
SEAL,MECHANICAL COMPONENTS - A compresson unit,hard face (rotating units) and a carbon (stationary unit)
STATOR CORE ASSEMBLY - The fixed assembly of an electrical machine containing lamination and windings which creates magnetic fields.
STRAINER - A device used to prevent large objects from entering a pump.(usually wire mesh screen type)
STUFFING BOX - A portion of the casing through which the shaft extends and the packing and a gland or a mechanical seal is placed to prevent leakage.
TEST VALVE - A device to control the flow through the test pipe.
Do 747l1 c'ONF Tt)FNTTAl
BASIC PUMP MODULE RESOURES
MECHANICAL SEALS
Pumps handling hazardous or expensive liquids, or liquids where the necessary leakage from the stuffing box is objectionable, are often furnished with a mechanical seal.
A mechanical seal consists of a rotating element and a stationary element. The sealing faces are highly lapped surfaces (extreamly flat) on materials selected for there low coefficient of friction and their resistance to corrosion by the liquid being pumped. The faces have a minute running clearance and normally run with a very thin film of liquid. In addition, there must be means of loading the seal and providing flexibility. This is accomplished by the use of springs and shaft packing or with a flexible member of some organic material.
Mechanical seals are more widly used than shaft packing because they require less maintenance and hold leakage to a minimum.
The stationary seal ring is usually made of carbon. The rotating seal ring unit is comprized of a compression ring (springs) and a seal ring (hard face) and the seal ring is faced with a special metal where it comes into contact with the stationary unit (carbon). The compression unit is held in place on the shaft by alien screws. This allows the compression unit and the seal ring to move freely on the shaft.
The entire sealing unit operates by the springs pushing against the compression ring and compress the flexible (0) ring against the shaft and seal ring against the carbon to prevent leakage at this point.
There are some applications which require a seal flush to cool down the seal. Excessive heat will cause the seal to lose its load carrying capacity. Also if the liquid contains solid corrosive material a seal flush will keep the seal faces clean.
Seal typically fail because the carbon weares out. How ver there are other causes of seal failure such as EXCESSIVE HEAT,SHAFT MISALIGNMENT,PUMP MISALIGNMENT,BAD PUMP BEARINGS, PUMP CAVITATION AND DIRTY SERVICE.
00 01471? CONFTDFNTTAL
MECHANICAL SEALS
PAGE 2
HEAT causes a varity of problems that are not always obvious. When a teflon chevron ring (a ring inside the rotating seal ring used for sealing against the shaft) gets hot it will get soft and extrude into parts of the seal and cause the seal ring to lock on the shaft, then the seal is no longer able to move on the shaft and compensate for wear. Excessive heat will cause some acids to become very corrosive. Loss of a seal flush will cause the seal to overheat. Running a pump dry will cause the sealing faces to lose its film of liquid between them and overheat and cause excess friction and damage to the seal.
DIRTY SERVICE will cause the small springs to become clogged and will lose its ability to move on the shaft and compensate for wear. The abrasive particles may cause a grinding action on the shaft. If the stuffing box is small the solids will build up and prevent the fluid from reaching them.
BAD BEARINGS,SHAFT MISALIGNMENT AND PUMP MISALINMENT cause the seal to separate slightly allowing for uneven wear of the carbon and rotating seal ring thus resulting in leakage.
DO 014710 C0NFTDFNTTA1
BASIC PUMP MODULE TANDEM SEALS
Tandem seals are a specially designed seal for use in pumps where fluid problems exist. In our case they are mostly installed on equipment which contains METHYL CHLORIDE which has a one hundred pound reportable.
Tandem seals consist of two bellows seals with one gland. The inside seal has an oil flush which cools and lubricates the seal. The oil (cp 6000) which lubricates the seal comes from and external oil pot located next to the pump. The oil enters the seal where it comes in contact with pumping paddles which are built into the seal itself. The pumping paddles help move the oil through the seal and back to the oil pot. If the inside seal should start to leak the product will enter the oil and then the oil pot. It will cause the pressure on the pot to increase. This is one good indic ation that the inside seal has blown. If this should occur, depressure the oil pot to the throx and block it back in.Monitor the time in which it takes for the pot to repressure back up. If it pressures back up fairly fast,the pump needs to be taken down and the seal repaired.
Seal failure will result if the oil flow to the seal is lost. If the oil pot goes empty, the seal will run dry and overheat. If the oil level is to high it will become harder for the oil to circulate through the pump because of the extra head pressure (the oil returns to the pot about midway). Therefore it is very important that we maintain the proper oil level in the oil pot.
If oil needs to be added to the oil pot, it is best to swap pumps and shut the pump down before adding oil. This will keep from running the seal without an oil flush.
Use only CP-6000 in the oil pots for these seals. Do not use any type of regal oil. Standard regal oils are hydrocarbon based and will react with the HCL to form carbon. This carbon can get between the seal faces and cause the seal to fail.
The following pumps have tandem seal installed on them.
P-252 A&B P-256 A&B P-511 P-513 P-803 A&B P-804 A&B
T-851 T-850 BLOCK 43 BLOCK 43 T-104 * S C-850 REFLUX
GR 9/89
D 014714 r-0NFTDFNTTA,
BASIC PUMP MODULE RESOURCES IMPELLER
Centrifugal force is the force of spinning. When an object is spun in a circle.it pushes (outward from/inward towards) the center of the circle. One way to increase the energy of a liquid is to whirl the liquid around in a circle. When it is spun around it pushes (inward to the center/outward from the center) of the circle. This outward force is called centrifugal force. This is how a centrifugal pump operates. The liquid enter through the suction piping into the eye of the spinning impeller, the impeller wirls the liquid around in a circle. The liquid is forced from the center to the outside of the impeller. As the liquid starts to move to the outside of the impeller it picks up velocity as the liquid moves from the tips of the impeller into the case, its velocity is decreased and that sudden decrease in velocity causes an increases the pressure. GR 89
DO 014715 rONFTDFNTTAI
COOLING TOWER 1020 SAFETY
A -------------------------------------------------------------------------------------------------------------------------------------
PURPOSE: TO FAMILIARIZE YOU WITH THE BASIC SAFETY KNOWLEDGE REQUIRED WHILE OPERATING A COOLING TOWER AND RECIRCULATING COOLING WATER SYSTEM.
RESOURCES: P&ID'S, EXPERIENCED PERSONNEL, PRESSURE VESSEL DATA SHEETS REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT
OBJECTIVES:
1. State the hazards of the following chemicals A. HCL
'B. Chlorine C. Treatment Chemicals
2. State the procedure to be followed in the case of inhalation of the following gases. A. Chorine B. HCL
3. State the reasons the following areas are restricted. Also explain the restrictions. A. Tower Internal Walkway B. Fan Shroud Area C. Chemical Addition Area D. Acid Injection Area E. Chlorine Injector
4. State the hazards to plant personel in the cooling tower area created by the following. A. Wet Surface B. I ce C. Rotating Equipment
frO 01471^
rONFTDFNTTAI
( COOLING TOWER 1020 PROCESS FAMILIARIZATION TANKS AND VESSELS
PURPOSE:
TO FAMILIARIZE YOU WITH THE PURPOSE, DESIGN, AND OPERATION OF MAJOR TANKS AND VESSELS IN YOUR AREA. UPON COMPLETION, YOU WILL BE ABLE TO POINT OUT (ON A BLANK DRAWING) THE INTERNAL AND EXTERNAL COMPONENTS (FLANGES, TAPS, BAFFLES, ETC) AND EXPLAIN THEIR FUNCTIONS.
RESOURCES: P&ID'S, EXPERIENCED PERSONNEL, PRESSURE VESSEL DATA SHEETS
REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT* 1
OBJECTIVES:
1. Locate the following tanks and vessels in your area and explain their purpose. Include inlet and outlet service flows, destinations and product content (shell & tube).
A. T-1020 (HCL SUPPLY TANK) B. T-1021 (TREATMENT CHEMICALS TANK) C. CL-1020 (CHLORINATOR) D. V-1020 (FILTER) E. CT-1020 (COOLING TOWER)
2. Draw a simplified diagram of the equipment listed above and label the parts in their appropriate location.
3. List all the places we will supply cooling tower water to.
4. What is the purpose of the 8" line that ties into the cooling water return header.
5. What is the purpose of the 3" line that comes off of the return header and ties into the permitted outfall line.
6. State the purpose of the vent line on T-1020.
7. State where T-1020 gets its feed from.
8. State the purpose of the 3" line off the top of T-1020 to the permitted outfall.
DO 014717 CONFTDFNTTAI
COOLING TOWER 1020 COOLING SYSTEM FUNCTIONS -( ----------------------------------------------------------------------------------------------------------------------------------------------------------PURPOSE: To Familiarize you with how a cooling tower functions as a thermal management system to reject heat RESOURCES: Experienced Personnel, Operating Manuals REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT OBJECTIVES: 1. State how a cooling tower rejects heat. 2. State the definitions of the following terms A. Blowdown B. Evaporative losses C. Induced Draft D. Fouling E. Scale F. PH 3. State the reason for blowdown of a cooling water system. 4. Describe the effect of CL2 as a biocide with respect to the PH of the system.
Oo CO/VP
Tr^NTTAl
COOLING TOWER 1020 PROCESS FAMILIARIZATION
( VALVE OPERATION
PURPOSE:
TO FAMILIARIZE YOU WITH THE LOCATION, TYPE, OPERATION AND PURPOSE OF ALL VALVES USED IN YOUR AREA. CONTROL VALVE OPERATION WILL BE COVERED IN "CONTROL AND SENSING SCHEMES" SECTION.
RESOURCES: PLANT FLOW SHEETS, EXPERIENCED PERSONNEL, PICS DISPLAY
REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT
OBJECTIVES:
1. PHYSICALLY LOCATE, OPERATE (AS APPLICABLE), AND STATE THE FUNCTION OF ALL VALVES IN THE COOLING TOWER AREA.
A. AO(512) T-1020 LEVEL CONTROL VALVEB. AO(511) VALVE TO OUTFALL OR TO T-510 C. AO(502) PROCESS H20 MAKE UP D. DO(513) HCL SUPPLY TO T-1020 E. DO(504 ) 3 WAY VALVE TO OUTFALL OR T-510
2. GIVEN ANY VALVE, STATE IF OPENED OR CLOSED.
3. MANUAL VALVES ASSOCIATED WITH CT-1020 ARE AS FOLLOWING:
CL-1020 (CHLORINATOR)
A. DOUBLE BLOCK AND BLEED ON CTW TO CL-1020. B. CHLORINE TO CL-1020.
T-1020 (HCL)
A. B/V UPSTREAM OF AOV ON INLET LINE TO T-1020. B. DOUBLE BLOCK AND BLEED UPSTREAM OF LCV OR FCV TO CT-1020. C. MANUAL BYPASS AROUND LCV.
T- 1 02 1 (TREATMENT CHEMICAL)
A. 2" DRAIN UNDER TANK. B. (2) B/V UPSTREAM OF P-1021. C. (1) BLEED VALVE AT P-1021.
COOLING TOWER (CT-1020)
A. (3) SUCTION B/V TO P-1020 A,B,& C. B. (3) DISCHARGE B/V ON P-1020 A,B, & C. C. B/V ON RECIRCULATION. D. B/V ON RETURN COOLING WATER HIGH & LOW POINT TIE-IN
TO CT-1020. E. B/V OFF COOLING TOWER WATER RETURN TO CL-1020. F. 3" B/V UPSTREAM FCV TO THE OUTFALL.
DO 014719 CONFTOFNTTAl
COOLING TOWER 1020
PROCESS FAMILIARIZATION
( MECHANICAL EQUIPMENT
PURPOSE:
TO FAMILIARIZE YOU WITH THE FUNCTION, LOCATION, AND MAINTENANCE OF THE MECHANICAL EQUIPMENT IN YOUR AREA. UPON COMPLETION, YOU WILL BE ABLE TO PHYSICALLY LOCATE AND STATE THE FUNCTION AND MAINTENANCE REQUIREMENTS OF ALL MECHANICAL EQUIPMENT IN YOUR AREA.
RESOURCES: EXPERIENCED PERSONNEL, EQUIPMENT MANUALS, DATA SHEETS
REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT* 1
OBJECTIVES:
1. PHYSICALLY LOCATE AND EXPLAIN THE OPERATION AND FUNCTION OF THE FOLLOWING:
A. P-1022 B. P-1020 A/B/C C. FA-1020 A/B
(DO(502 ) , DO(512) & DO(522)) (DO(501) & DO(511))
2. EXPLAIN HOW THE FANS ARE CONTROLLED. (AO(501) & AO(521))
3. PHYSICALLY LOCATE THE FOLLOWING ON THE ABOVE LISTED PUMPS.
A. FIELD SWITCH B. MAIN SWITCH GEAR C. SUCTION AND DISCHARGE BLOCK VALVES D. BLEED E. SEAL PURGE (IF APPLICABLE) F. TEMPERATURE TRANS (IF APPLICABLE)
4. PHYSICALLY LOCATE THE FOLLOWING ON THE ABOVE LISTED FANS ITEM-1
A. FIELD SWITCH B. MAIN SWITCH GEAR C. VIBRATION TRANSMITTER/PROBE
5. STATE HOW THE FANS ARE CONTROLLED.
DO 0147P0 CONFTDFNTT Al
COOLING TOWER 1020 PROCESS FAMILIARIZATION
( CONTROL AND SENSING SCHEMES
PURPOSE: TO GIVE YOU A GOOD UNDERSTANDING OF THE CONTROL AND SENSING SCHEMES THE CT-1020 AREA, INCLUDING LOCATION AND PURPOSE OF KEY INSTRUMENTATION.
RESOURCES: P&ID'S, EXPERIENCED PERSONNEL
REQUIRED LEVEL OF PERFORMANCE: 100% CORRECTI.
OBJECTIVES:
1. EXPLAIN THE FUNCTION OF THE FOLLOWING CONTROLLERS AND HOW THEY OPERATE.
A. AO(512) T-1020 LEVEL CONTROL VALVE ' B. AO(511) VALVE TO OUTFALL OR TO T-510 C. AO(502 ) PROCESS H20 MAKE UP D. DO(513) HCL SUPPLY TO T-1020 E. DO(504 ) 3 WAY VALVE TO OUTFALL OR T-510
2. PHYSICALLY LOCATE THE FOLLOWING INSTRUMENTATION AND EXPLAIN THEIR FUNCTION. ALSO, STATE THE CONTROL VALVE THEY ARE ASSOCIATED WITH .
A. AI(506) T-1020 LEVEL B. AI(516) T-1021 LEVEL C. All 504,514) CT-1020 SUMP LEVEL D. AI(581 ) AIR INLET TEMP. FOR FAN CT-1020 A E. AI(591 ) AIR INLET TEMP. FOR FAN CT-1020 B F. AI(583) PROCESS H20 RETURN TEMP. G. AI(592 ) CT-1020 SUMP TEMP. H. AI(505 ) CT-1020 RETURN HEADER ORGANIC ANALYZER I. AI(526) FLOW TO OUTFALL J. AI(512) PROCESS H20 MAKE UP FLOW TO CT-1020 K. AI(503,513,523 ) P-1020 A/B/C AMPS L. AI(515 ) CT-1020 PH ANALYZER M. AI(525) CT-1020 PUMP DISCHARGE PRESSURE ?* N. AI ( 521 ) T-102(? LEVEL
3. DRAW A DETAILED DIAGRAM OF THE SYSTEM,INCLUDING ALL CONTROLLERS AND INSTRUMENTATION IN ITEMS *1 AND *2
DO 014771 OONFTDFNTTAt
COOLING TOWER 1020 CONTROL AND SENSING SCHEMES
(MOD V OPERATIONS)
PURPOSE:
TO GIVE YOU A GOOD UNDERSTANDING OF THE MOD CONTROL AND SENSING SCHEMES THE CT-1020 AREA. UPON COMPLETION'YOU SHOULD BE ABLE TO START UP THE SYSTEM USING THE MOD AND EXPLAIN WHAT TAKES PLACE IN EACH STEP.
RESOURCES: P&ID'S, EXPERIENCED PERSONNEL
REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT
OBJECTIVES:
1..WITHOUT USING THE ENGLISH LANGUAGE, BE ABLE TO SUMMARIZE WHAT OCCURS IN EACH STEP, USING THE STEPPING DIAGRAM.
2. START UP CT-1020 ON THE MOD AND EXPLAIN WHAT IS TAKING PLACE.
3. EXPLAIN ANY GIVEN ALARM.
4. USING THE MOD DEMONSTRATE ENERGIZING A FAN
5. DEMONSTRATE HOW TO SHUT THE SYSTEM DOWN USING THE MOD 6. CHANGE ANY GIVEN SETPOINT.
7. USING THE MOD DEMONSTRATE HOW TO SWAP MP-1020'S.
8. BE ABLE TO ANSWER ALL THE QUESTIONS ON THE COOLING TOWER SIMULATION SCRIPT
DO 0147?? CONFTDFNTTAl
COOLING TOWER 1020 PROCESS FAMILIARIZATION
( AREA HAZARDS & PROTECTIVE MEASURES
PURPOSE: TO FAMILIARIZE YOU WITH THE HAZARDS AND PROTECTIVE MEASURES TO REDUCE THOSE HAZARDS IN YOUR AREA.
RESOURCES: S&LP, EXPERIENCED PERSONNEL, SAFETY PROCEDURES
REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT
OBJECTIVES:
1. STATE THE CHEMICAL HAZARDS ASSOCIATED WITH CT-1020,CL-1020, T-1020 & T-1021
2. STATE THE HAZARDS OF ROTATING EQUIPMENT
3. STATE THE ELECTRICAL HAZARDS ASSOCIATED WITH CT-1020.
4. STATE ENVIRONMENTAL PROBLEMS AND ACTIONS TO BE TAKEN IN EVENT OF THE FOLLOWING SPILLS:
A. HCL
B. CHLORINE
C. TREATMENT CHEMICALS
5. STATE THE PROTECTIVE EQUIPMENT REQUIREMENTS FOR MAINTENANCE ON THE FOLLOWING.
A. HCL TANK AND LINES B. CL2 LINES C. CHEMICAL ADDITION LINES
00 014773 OONFTDFNTTAI
COOLING TOWER 1020 PROCESS FAMILIARIZATION
OPERATING DISCIPLINE
(
PURPOSE:
TO GIVE YOU A GOOD UNDERSTANDING OF OPERATING PARAMETERS OF THE MAJOR EQUIPMENT IN YOUR AREA. THE PROBLEMS ASSOCIATED WITH THE PROCESS BEING OUT OF OPERATING . PARAMETERS.
RESOURCES: EXPERIENCED PERSONNEL, OPERATING MANUALS,MOD 5 PROGRAM
REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT
OBJECTIVES:
1. STATE THE NORMAL OPERATING PARAMETERS OF THE FOLLOWING.
A. AI(506) T-1020 LEVEL B. AI(516 ) T-1021 LEVEL C. AI(504,514 ) CT-1020 SUMP LEVEL D. AI(581 ) AIR INLET TEMP. FOR FAN CT-1020 A E. AI(591 ) AIR INLET TEMP. FOR FAN CT-1020 B F. AI(592 ) CT-1020 SUMP TEMP. G. AI(505 ) CT-1020 RETURN HEADER ORGANIC ANALYZER H. AI(526) FLOW TO OUTFALL I. AI(515 ) CT-1020 PH ANALYZER J. CONDUCTIVITY K. HCL CONCENTRATION L. CALCIUM
2. STATE THE RESULTS OF HIGH OR LOW PARAMETERS AND THE RESULTS IF IT REMAINS HIGH OR LOW. STATE WHAT ACTION YOU WOULD TAKE TO BRING THESE BACK TO WITHIN NORMAL OPERATING PARAMETERS.
3. EXPLAIN HOW HIGH COOLING TOWER TEMPERATURE AFFECTS PLANT OPERATIONS AND EFFICIENCY.
4. EXPLAIN WHAT THE FOLLOWING IS USED FOR AND THEIR PARAMETERS.
A. HCL B. PHOSPHATE C. CL2
(38K)
5. LIST THE TRIPS FOR THE FOLLOWING EQUIPMENT: SEE MOD 5 CODE
A. FA-1020 A/B/C B. CT-1020
00 014774 OONFTDFNTTAI
COOLING TOWER 1020 SPECIAL SKILLS
4 ------------------------------------------------------------------------------------------------------------------------------
PURPOSE: TO ALLOW YOU TO DEMONSTRATE YOUR ABILITY TO PERFORM TASKS IN A LOGICAL AND SAFE SEQUENCE, USING ESTABLISHED JOB PROCEDURES.
RESOURCES: PROCEDURES, EXPERIENCED PERSONNEL,LAB SAMPLE PROCEDURE
REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT
OBJECTIVES:
1. GIVEN ANY OF THE FOLLOWING JOB PROCEDURES/CHECKLIST DEMONSTRATE/SIMULATE IN THE FIELD COMPLETING EACH TASK IN A LOGICAL SAFE MANNER.
' A. B. C. D. E. F. G. H. I.
ADDING BETZ CHEMICAL (38K) TO CT-1020 UNLOADING BETZ TRUCKS CONTAINING COOLING TOWER CHEMICALS MAKING A COOLING TOWER ENTRY DEMONSTRATE LINING UP SYSTEM FOR START UP DEMONSTRATE SWAPPING PUMPS (FIELD) LINE UP T-1021 DEMONSTRATE STARTING AND STOPPING A FAN ADJUST CL2 FLOW TO CL-1020 ADJUST 38K TO COOLING TOWER WATER SMALL METERING PUMP
2. DEMONSTRATE RUNNING THE FOLLOWING SAMPLES FOR THE COOLING TOWER SYSTEM.
A. PHOSPHATE B. CL2 C. PH D. CONDUCTIVITY E. CALCIUM
3. LIST THE STEPS (IN SEQUENCE) NECESSARY TO MAKE THE FOLLOWING EQUIPMENT READY FOR MAINTENANCE:
A. COOLING TOWER 1020 B. FA-1020 A/B/C C. P-1022 D. P-1020 A/B/C
4. DEMONSTRATE THE PROPER PROCEDURE FOR CLEARING THE PROCESS LINES FOR MAINTENANCE.
A. HCL LINES B. CL2 LINES
D Ol4?pt-
COOLING TOWER 1020
( OPERATIONS ROUTINE CHECKLISTS
PURPOSE: TO FAMILIARIZE AND ALLOW YOU TO DEMONSTRATE COMPLETING ROUTINE CHECKLISTS IN YOUR AREA.
RESOURCES: EXPERIENCED PERSONNEL, ROUND SHEETS, OPERATING MANUALS REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT OBJECTIVES: 1. DEMONSTRATE MAKING A ROUND USING CT-1020 ROUND SHEET, EXPLAINING
EACH ITEM AND ITS IMPORTANCE.
Do D'O/vo
rDr/v
COOLING TOWER 1020
( OPERATIONS CAPACITY & EFFICIENCY PURPOSE: TO FAMILIARIZE YOU WITH THE CAPACITY AND EFFICIENCY IN THE COOLING TOWER AREA. REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT* 1 OBJECTIVES: 1. STATE HOW EACH OF THE FOLLOWING AFFECT EFFIECIENCY. A. HEADER LEAK B. SLUDGE BUILD UP IN THE SUMP C. PITCH ON THE FAN BLADE D. 30 DEGREE OUTSIDE TEMPERATURE DROP OR RISE E. EXCESS COOLING TOWER BLOWDOWN
DO 014707 rONFTDFNTTAI
COOLING TOWER 1020 OPERATIONS
( EMERGENCY PROCEDURES
PURPOSE: TO FAMILIARIZE YOU WITH EMERGENCY CONDITIONS AND PROCEDURES IN THIS AREA.
RESOURCES: EMERGENCY STARTUP & SHUTDOWN PROCEDURES, PLANT PERSONNEL, REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT1 OBJECTIVES: 1. GIVEN AN EMERGENCY SITUATION AND SHUTDOWN PROCEDURE IN THIS
AREA, SIMULATE (IN SEQUENCE) SHUTTING THE AREA DOWN. EXPLAIN WHAT IS OCCURRING IN EACH STEP. INCLUDE PRECAUTIONARY MEASURES SUCH AS WASHING OUT AND PURGING EQUIPMENT. YOU WILL BE TESTED ON THE FOLLOWING:
A. LOSE FA-1020 A B. LOSE P-1020 C. FIRE D. LOW WATER LEVEL IN SUMP 2. YOUR AREA HAS JUST EXPERIENCED A POWER FAILURE. EXPLAIN YOUR ACTIONS. (POWER IS STILL OFF). YOUR ANSWER SHOULD BE STEP-BY-STEP.
DO 014708 OONFTDFNTT Al
COOLING TOWER 1020 PROBLEM ANALYSIS
PURPOSE: TO ALLOW YOU TO DEMONSTRATE YOUR ABILITY TO HANDLE ABNORMAL SITUATIONS (UPSETS) WHEN THEY OCCUR IN YOUR AREA.
RESOURCES: PROCEDURES, EXPERIENCED PERSONNEL, OPERATING MANUALS
REQUIRED LEVEL OF PERFORMANCE: 100% CORRECT
OBJECTIVES:
1. LIST THE SEQUENCE OF STEPS YOU WOULD TAKE IF THE FOLLOWING CONDITION WERE TO OCCUR.
A. ORGANICS APPEAR IN SAMPLE B. PH LOW OR HIGH C. CHLORINE IS TOO HIGH OR LOW
D. CONDUCTIVITY IS TOO HIGH E. PHOSHATE IS TOO HIGH OR TOO LOW F. PLUGGED CHLORINATOR
12/91 GR/CB
CT1020MD.IPT
oo 0147C9 OONFTDFNTTAI
AREA
ACIDSAFE.CMP
___
CONTRACTOR
_____________
MINIMUM SAFETY EQUIPMENT REQUIRED IN C.M.P. ACID AREAS
MEASUREMENTS WALK - THRU
WORKING ON
C-202 BTMS.
E-212 H2S04 T/C RACK T--900 C-650 C-210
C-200 / C-201 BTMS. C-202 DECKS P-301 S
C-S10 / R--ECO
SLICKER SUIT / GOGGLES / RUBBER BOOTS, GLOVES
SAME AS ABOVE SAME AS ABOVE SAME AS ABOVE SAME AS ABOVE SAME AS ABOVE
GOGGLES GOGGLES GOGGLES
GOGGLES
FULL ACID SUIT
SAME AS ABOVE SAME AS ABOVE SAME AS ABOVE SAME AS ABOVE SLICKER SUIT / GOGGLES RUBBER BOOTS, GLOVES SAME AS ABOVE FULL ACID SUIT SLICKER SUIT / GOGGLES RUBBER BOOTS. GLOVES SAME AS ABOVE
* A r'JLL ACID SUIT IS REQUIRED TO DO ANY TYPE OF WORK ON GROUND LEVEL AROUND
H2S0*i ACID RUMPS. ANY DEVIATION FROM THIS REQUIRES PLANT SUF'T. APPROVAL.
Irlrc^r' tv ) * TO DO WORK ON INSTRUMENTAT101)/ IN AREAS REQUIRING A FULL ACID SUIT TO BE
WORN, THE THIN RUBBER GLOVES/ARE PERMITTED.
revised: 10/90 L. London
/t-A_S
00 014730 OONETDENTIAI
II. OBJECTIVES A. TO HAVE YOU BECOME VERY FAMILIAR WITH THE OPERATION OF THE COMBUSTIBLE GAS/ OXYGEN METERS. ALSO, TO MAKE YOU AWARE OF THE METERS' LIMITATIONS. B. TO BECOME PROFICIENT AT TEACHING OTHERS WHAT THEY NEED TO KNOW TO OPERATE THE METERS CORRECTLY.
I
DO 014731 f ONFTDFNTTAl
III. ABOUT THE METER (actually two meters in one)
A. OXYGEN -
ELECTROCHEMICAL FUEL CELL THAT DEVELOPS A VOLTAGE WHICH IS PROPORTIONAL TO THE OXYGEN CONCENTRATION OF THE GAS PASSING THROUGH THE CELL. THE CELL IS DEPLETED OR USED UP AS OXYGEN MEASUREMENTS ARE MADE.
B. COMBUSTIBLE -
CATALYTIC BEAD IN CELL WHOSE TEMPERATURE IS CHANGED BY THE AMOUNT OF COMBUSTIBLESAS IN THE SAMPLE. AS THE TEMPERATURE IS CHANGED. ITS' RESISTANCE CHANGES. UNBALANCING ONE LEO OF A WHEATSTONE BRIDGE CIRCUIT COMPARED TO A SECOND BEAD WITHOUT CATALYST THAT WILL NOT REACT TO THE COMBUSTIBLE GAS. THIS TYPE OF CELL REQUIRES SOME OXYGEN (1 OX) FOR SUCCESSFUL OPERATION.
j
DO 014730 rONFTDFNTTAI
I
;
00 0TA733 conft^nttA
IV. TERMS
A. LEL (LOWER EXPLOSIVE LIMIT - The least concentration of a combustible gas in air that will ignite
B* VAPOR DENSITY - The weight of a Ras as compared to air.
C. OXYGEN DIFICIENT OR RICH ATMOSPHERE The combustible gas sensor requires at least 10* oivRen and a maximum of 2V* oxygen to work accurately
i
i
OO 014734 CONFIDFNTTAl
OXYGEN DEFICIENT ATMOSPHERES & YOU
OKY6FM IN AIR UPPROX. 21Z NORMAL)
12 - 18%
AT RFST SIGNS K SYMPTOMS
BREATHING & PULSE RATE INCREASED; COORDINATION POOR.
10 - 12%
DEEP, FAST RESPIRATION; GIDDINESS; POOR JUDGEMENT; LIPS BLUE.
8 - 10%
NAUSEA; VOMITING; INABILITY TO MOVE FREELY; UNCONSCIOUSNESS; ASHEN FACE.
6-8%
8 MINUTES - 100% FATAL 6 MINUTES - 50% FATAL 4 MINUTES - ALL RECOVER WITH TREATMENT
4% COMA IN 40 SECONDS; CONVULSIONS; RESPIRATION CEASES.
0% INDIVIDUAL IMMEDIATELY BECOMES UNCONSCIOUS; WILL RECOVER ONLY IF
GOOD AIR IS IMMEDIATELY AVAILABLE
WARNING: THE WARNING SYMPTOMS OF AN ATMOSPHERE DEFICIENT IN OXYGEN ARE COMPLETELY INADEQUATE AND, ALTHOUGH, A TRAINED OBSERVER MAY, WHEN ALERT, RECOGNIZE THE INCREASE IN PULSE AND RATE OF BREATHING IN TIME TO RETURN TO GOOD AIR, THE AVERAGE INDIVIDUAL FAILS TO RECONIZE THE DANGER UNTIL HE IS TOO WEAK TO SAVE HIMSELF. ESPECIALLY WHERE THE RETURN TO GOOD AIR INVOLVES CLIMBING STAIRS OR A LADDER.
LEAN MIXTURE -
aeter hind rises to i reading
EXPLOSIVE MIXTURE -
meter hand rises to reading in alarm zone (201 and above)
in 10.
in <0
y Ww
--------
no
1LEL
100
RICH MIXTURE -
meter hand goes full scale and then falls to zero or belov
D0 01473ft 0ONFT0FNTTAI
PRE-USE CALIBRATION CHECK OF BIO MARINE 902 t GASTECH GX-3 COMBUSTIBLE GAS/02 MONITORS
1 l' CHECK UNITS WITH HOSE & PROBE CONNECTED.
1 2. CHECK FILTER 6 WATER TRAP. SHOULD BE CLEAN AND DRY.
1 3` CHECK BATTERY VOLTAGE. NEVER CALIBRATE ANY METER WHILE PLUGGED INTO THE CHARGER.
1 4* CHECK PUMP FLOW AND ALARM.
1 5. CHECK OXYGEN READING IN AIR. SHOULD BE 21%. IF NOT, ADJUST TO READ 21%.
1 6. CHECK COMBUSTIBLE GAS ZERO. IF NOT ZERO, ADJUST TO READ ZERO.
1 7. INTRODUCE CALIBRATION GAS (2.5% METHANE IN AIR). COMBUSTIBLE
GAS METER SHOULD GO UPSCALE TO 2.5% ON BIO MARINE UNITS OR TO
55% LEL ON GASTECH UNITS. IF READING IS INCORRECT, ADJUST
WITH GAS SPAN POT TO OBTAIN PROPER READING. THE SPAN POT FOR
BIO MARINE UNITS IS LOCATED ON TOP CONTROL PANEL. THE SPAN
POT FOR THE GASTECH GX-3 UNIT IS LOCATED IN THE FRONT CHAMBER,
SPAN POT #3.
|
1 8* IF UNITS CANNOT BE ADJUSTED PROPERLY, OR IF YOU FEEL THE UNIT IS NOT OPERATING CORRECTLY, DO NOT USE IT. TAG THE UNIT AND SEND IT TO THE CENTRAL INSTRUMENT $HOP FOR A THOROUGH CHECKOUT AND REPAIR.
PRE-USE CALIBRATION CHECK OF GASTECH 1214SMP COMBUSTIBLE GAS/02 MONITOR
1 1` CHECK UNITS WITH HOSE & PROBE CONNECTED.
2. CHECK FILTER & WATER TRAP. SHOULD BE CLEAN AND DRY.
3. PRESS RED "POWER" SWITCH TO TURN UNIT ON. THE'STATEMENT "GASTECHTOR ON - TAKE TO GAS FREE AREA" WILL SOUND AND DISPLAY
WILL BLINK. THE UNIT DISPLAY WILL CONTINUE TO BLINK FOR A TWO
MINUTE WARM-UP PERIOD.
4. AFTER THE TWO MINUTE WARM-UP PERIOD HAS ELAPSED, THE STATEMENT "PRESS ADJUST BUTTON" WILL SOUND. PRESS THE BLACK ADJUST BUTTON.
UNIT SHOULD THEN READ 20.9% 0, and 0 COMBUSTIBLES. ANYTIME THE
ADJUST BUTTON IS PRESSED THEREAFTER, THE UNIT WILL DISPLAY THE
NUMBER OF BATTERY HOURS REMAINING.
00 014737
5. CHECK PUMP FLOW.
OONFTDFNTTAI
6. INTRODUCE CALIBRATION GAS (2.5% METHANE IN AIR). METER SHOULD READ 55% LEL. IF NOT, ADJUST SPAN POT LOCATED ON SIDE OF UNIT AND MAKE METER READ 55%.
7. IF UNIT CANNOT BE ADJUSTED PROPERLY, OR IF YOU FEEL THE UNIT IS NOT OPERATING CORRECTLY, DO NOT USE IT. TAG THE UNIT AND
cpwn TT TO THE CENTRAL INSTROMEUT SHOP F0R A THOROUGH CHECKOUT
CHECKING FOR COMBUSTIBLE GAS IN INERT BACKGROUND USING SPECIAL FITTING ON STANDARD EXPLOSION METER
1. Calibrate unit without special fitting using 2.5X Methane In air cal. gas. Combustibles should read 55X LEL. If not, adjust span so that meter does read 55X LEL. Oxygen should read 2IX.
2. Put special fitting on unit and Introduce cal. gas again (2.5X Methane In air). Combustibles should read approximately 27.5X LEL. Oxygen should read 2IX.
3. Put 2.5X Methane In Nitrogen In unit. Combustibles should read about 27.5X LEL. Oxygen should read approximately I0.5X.
4. THE UNIT IS NOW READY TO BE USED.
5. After a line has been checked with a standard (without fitting) meter
and the line has less than IOX oxygen, you would then use the special
meter (with fitting) and check the line for combustibles.
f
6. Always be aware of your oxygen reading when using the meter with the fitting on it. Your oxygen reading can tell you many things. For example, the oxygen reading taken without the fitting must differ from oxygen reading taken with the fitting in place.
NOTE: ANY COMBUSTIBLE GAS READING OBSERVED WHILE USING THE UNIT MUST BE MULTIPLIED BY TWO TO OBTAIN THE ACTUAL XLEL.
2.5X Methane In Air
DO 014738 OONFTDFNTTAI
ONLY TRAINED AND CERTIFIED PERSONNEL ARE ALLOWEDT(
USE
DO 014739 CONFIDENT! Al,
THE ONLY WAY TO TELL IF
AN LXPLOSIfAETER IS GOOD IS T(
PASS A CALIBRATED GASTHRU 11
..
DO 014740 OONFTDFNTTAI
MAN! WHAT IS THAT STUFF?
HE-X>
t
PERSONNEL CHOSEN AS SAFETY OBSERVERS SHOULD BE FAMILIAR
VJITH COMPOUNDS FOUND IN "WE PLANT AND PLANT PRODUCTS
... ARE THEY
FLAMMABLE ? HEAVIER OR LIGHTER THAN AIR? TOXIC? CORROSIVE
T>0 01474-]
OONFTDFNTTA!
METERS ARE NOT MSI&NED TO TAKE LIQUID SAMPLES
VIIK'D "DIRECTION
r~rn
r> WHEN ACTING AG SAFETY OBSERVER
o Z) 2o
n^ 2 NJ
Always look for potential hazards
H -Ei
--< U>
FROM SURROUNDING AREAS
CAUflON
MITAO&EN "PAD iNUSff Ion FLAM HEM*
METERS SHOULD NOT BE USED TO MEASURE COMBUSTIBLE GAS IN
ATMOSPHERES THAT ARE OXYGEN
DEFICIENT
'
^roV?4'' F*TTA,
'--GAS TECT-ORR CRAZEEE TAKE TO BLASSS AREA
TETRA ETHYL LEAD OR SILICON
COMPOUnDS POISON COKBUSTIBLE r.a* QCMQfYRR
^ONFTDFNTT
BE" ALERT!
2*10 PM THU. , 26 APR., 1990
PAGE 1
SPECIFICATIONS CATALOG
PROFILES
10 - 2000
PROFILE #* DETERMINANT #* DESCRIPTION*
LOU SPEC* HIGH SPEC*
102
1 DIMETHYL ETHER 2 METHYL CHLORIDE 3 METHANOL
103
I DIMETHYL ETHER 2 METHYL CHLORIDE 3 METHANOL 4 UT* HCL
109
i METHYLENE CHLORIDE 2 UINYLIDENE CHLORIDE 3 TRANS 4 M4 CAREON TET
5 CHLOROFORM . a AMYLENE 7 CIS
8 BRCLME 9 A-DI
H1 PPM HCL
10.00
2 0.00
: - rr5 m
PPM HCL
10.00
l FF'M WATER
80 . j0
METHANE
10.00
4 EThYLENE
2 00
ETHANE
2.0 0
6 ACETYLENE
2 00
7 DIMETHYL ETHER
1o 3 0
8
METHYL CHLORIDE
9 8 0 C 0 0.0
1 020UoC .
9 UINYL CHLORIDE
2 5.0 0
i 0 METHANOL
10 0 0
i 1 METHYLENE CHLORIDE
50,00
12 ETHYL CHLORIDE
50.0 0
i 3 FREON 12
1.00
14 PROPANE/BUTANE
/w\ ,, J"n' -I /. f r I 1;/1y/
1
METHYLENE CHLORIDE
930000,0
1020000.
2 ETHYL CHLORIDE
5.00
3 METHYL BROMIDE 4 UINYLIDENE CHLORIDE 5 ALLYL CHLORIDE 6 TRANS
5.00 5 0.00
5.00 60 , 'J 0
D 014747 ^ONFTDrNTTA!
112 113 114 1i 1 i/ 112
118
2io pm ' ihu , 26 "Hpk . , ~iyyu
SPECIFICATIONS CATALOG
DETERMINANT #*
7 8 9 10
1 2 3 4 5
DESCRIPTION*
: > /.
y
Tel------------------- -------
CHLOROFORM
Ml/01
A-DI/M4
<?* c.
METHYLENE CHLORIDE A-DI CHLOROFORM CIS M4
|-HbL 4
PROFILES
10 - 2000
LOW SPEC* HIGH SPEC*
1 , 00 50.00
5.00 5.00
*0,0 K.<
2.0000
. 0050 . 0025
.0100 ,ro 10.0000
1 2 3 `4 " 5 6
1 2 3 4 6
PPM CHLORINE METHYLENE CHLORIDE A-Di CHLOROFORM CIb 114
T~ 'T~
METHYLENE CHLORIDE a-d: L ;i L 0 K' oi` u hi t1 CIS M4 PPM CHLORINE
600.00
1500.00 . 0200 .6)5^
. 0005
600.00
. 0200 .0150
. 0005 1500.00
1 PPM Uh^ER 2 PPM HCL
20.00 5.00
1 methylene CHLORIDE
0.00
50.00
UINYLIDEnE CHLORIDE
0 . 00
10.00
3 TRANS
6.00
10.00
4 M4 CARBON TET
0.00
200.00
3 CHLOROFORM
980000.0
1020000.
6 AMYLENE
7 CIS
0.00
30 00
8 BRCLME
ISO . 00
250.00
9 A-DI
0.00
2 5.00
10 PPM WATER
0.00
2 5.00
11 PPM HCL
10.00 S.c
12 PPM CHLORINE
1 . METHYLENE CHLORIDE.
On 74748 CONF T0FNTJAI
2*10 PM THU . , '26 ' HVK . , ivyu
SPECIFICATIONS CATALOG
PROFILE #* 113
DETERMINANT #
2 3 4 5 6 7 8 9 10 11 12 13
DESCRIPTION*
C - `pi /tr/n ;
TRANS A-DI CHLOROFORM TCE METHYL CHLORIDE UINYL CHLORIDE CIS EDC M4 B-TRI UNSYM-TET SYM-TET
1 19
1 PPM UATER 2 PPM HCL
1 WT-2 HCL 2 DIMETHYL ETHER 3 METHYL CHLORIDE 4 METHANOL
r noc
PROFILES
10 - 2000
LOU SPEC* HIGH SPEC*
1.8000 M'
80.00 7.00
)# +3
123 124
1 WTH HCL 2 DIMETHYL ETHER 3 METHYL CHLORIDE 4 METHANOL
_ * ^; *
*
1 METHYL CHLORIDE
2 METHANOL
3 METHYLENE CHLORIDE
4 M4 CARBON TET
3 CHLOROFORM
6 UTY HCL
1 DIMETHYL ETHER 2 METHYL CHLORIDE 3 METHANOL
'
1 WTX H2S04 2 DIMETHYL ETHER 3 METHYL CHLORIDE 4 METHANOL
\% 4* 3s3 1 ff'*'
S ft*'
0&L *7^ f^rrv
vo'/0 -- ys /C
DO 014749 OONFTDFNTTAI
SMPLP01 UNIT
1
2:14 PM THU., 26 APR., 1990
SAMPLE POINTS
2 C202 BTMS 3 C610 REFLUX 10 C 840 BTMS 11 C 850 OVH 12 C 802 REFLUX 13 C 802 BTMS 14 T 803 A 15 T 803 B 16 C 803 BTMS 17 C 806 OVH 18 C 806 BTMS 19 Ml FORWARD 20 C 200 21 C 201 22 C 610 BTMS 23 C 650 BTMS 24 D 650 25 C 210 BTMS 26 T 104 A 27 T 104 B 28 T 814 29 T 511 30 T 514 31 T 804 A 32 T 804 B 33 T 100 34 T 101 35 T 103 36 T 1050 37 T 810 38 T 808 39 T 805 40 T 806 A 41 T 806 B 42 T 102 43 T 303 44 T 1010 45 T 251 46 D 455 47 Ml TRUCKS 49 M2 TRUCKS 50 R 750 CONDENSATE 51 M3 TRUCKS 53 M2 BARGES 54 M3 BARGES 55 METHANOL BARGES 56 CHO STANDARD 57 CHI STANDARD 58 CH2 STANDARD 59 CH3 STANDARD
PAGE 1 DISPLAY UNIT CODE
PROFILE
12 13 1 10 1 11 1 12 1 13 1 14 1 15 1 16 1 17 1 18 1 19 1 20 1 21 1 22 1 23 1 24 1 25 1 26 1 27 1 28 1 29 1 30 1 31 1 32 1 33 1 34 1 35 1 36 1 37 1 38 1 39 1 " 40 1 41
1 42 1 43 1 44 1 45 1 46 1 47 1 49 1 50 1 51 1 53 1 54 1 55 1 56 1 57 1 58
1 59
102 103 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 149 150 151 153 154 155 156 157 158 159
DO 014750 OONFTDFNTTA!
SMPLP01
UNIT 1 CMP 1 CMP
THU ., 26 APR., 1990
SAMPLE POINTS
60 CH4 STANDARD 61 Ml R/C HEEL SAMPLE 1 62 Ml R/C HEEL SAMPLE 2 63 Ml R/C HEEL SAMPLE 3 64 Ml R/C HEEL SAMPLE 4 65 Ml R/C HEEL SAMPLE 5 66 Ml R/C HEEL SAMPLE 6 67 CH5 STANDARD 68 CH6 STANDARD 69 CH7 STANDARD 70 CH8 & 9 STANDARD 71 Ml R/C FNL SAMPLE 1 72 Ml R/C FNL SAMPLE 2 73 Ml R/C FNL SAMPLE 3 74 Ml R/C FNL SAMPLE 4 75 Ml R/C FNL SAMPLE 5 76 Ml R/C FNL SAMPLE 6 78 CH10 STANDARD 79 CH11 STANDARD 80 CH11 STANDARD B 81 M2 R/C FNL SAMPLE 1 82 M2 R/C FNL SAMPLE 2 83 M2 R/C FNL SAMPLE 3 84 M2 R/C FNL SAMPLE 4 91 M3 R/C FNL SAMPLE 1 92 M3 R/C FNL SAMPLE 2 93 M3 R/C FNL SAMPLE 3 94 M3 R/C FNL SAMPLE 4 95 M3 R/C FNL SAMPLE 5 96 M3 R/C FNL SAMPLE 6 99 RECHARGE H20 MACHINE
PAGE 2 DISPLAY UNIT CODE
prof;
1 60 1 61 1 62 1 63 1 64 1 65 1 66 1 67 1 68 1 69 1 70 1 71 1 72 1 73 1 74 1 75
1 76 1 78 1 79 1 80 1 81 1 82 1 83 1 84 1 91 1 92 1 93 1 94 1 95 1 96 1 99
160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 178
179 0
181 182 183 184 191 192 193 194 195 196
200
DO 0147M CONFTDFNTT Al
P
Mb F L,L 0 1 '
i K C i' i l_ Yt : I 02 10Y
10 9
.1 .. .
2:10 F'M THU , 2 <5 APR., 1990 SPECIFICATIONS CATALOG
DETERMINANT # = DESCRIPTION:
PAGE 1
PROFILES
10 - 2000
LOU SPEC' HIGH SPEC:
3 DIMETHYL ETHER 2 METHYL CHLORIDE 3 METHANOL
1 DIMETHYL ETHER 2 METHYL CHLORIDE 3 METHANOL 4 WT'K HCL
1 METHYLENE CHLORIDE 2 UINYLIDENE CHLORIDE 3 TRANS 4 M4 CARBON TET [/ CHLGROFCRM c AMY LINE
C1S fj BRCLME
A - DI
/' X > F'M `HCL
10.00
20.00
Ai> 30. *>
- FTTi HCL
10.00
F PM WATER
SO . 00
METHANE <4 ETHYLENE
10.00 2 00
El H A i\ E
2 . OU
0 ACETYLENE
2 00
/ DIMETHYL ETHER
10,00
b
METHYL CHLORIDE
9 8 0 0 0 0.0
1 0 2 0 0 0 C.
9 UINYL CHLORIDE
2 5.0 0
1 'J METHANOL
10.00
, 1 METHYLENE CHLORIDE
b 0.0 0
1 4 ETHYL CHL.OF IDE
5 0.0 0
i 3 FREON 12
1,03
PROPANE/BUTANE
1
METHYLENE CHLORIDE
980000.0
1020000.
ETHYl chloride
5 . 00
*/ METHYL BROMIDE
5.00
4 UINYLIDENE CHLORIDE
50.00
b ALLYL CHLORIDE
5.00
6 TRANS
60.00
00 014750 C.ONFIOFNTTW
rib.'U-o:
2=10 PM THU, 26 APR , , 1990 SPECIFICATIONS CATALOG
DETERMINANT #: DESCRIPTION:
PAGE 2 PROFILES 10 - 2000
LOU SPEC: HIGH SPEC
7 fCE b CHLOROFORM 9 Ml/Ul 10 A-DI/M4
1 . 00 50.00 5,00
5.00
SO,
1C
1 METHYLENE CHLORIDE
.0050
2 A-DI
.0025
3 CHLOROFORM 4 CIS
.0100 ,V?ro
5 M4
2,0000
10.0000
1 PPM CHLORINE
600.00
1500.00
2 METHYLENE CHLORIDE
.0200 . ClS
3 A L) 1 '
4 CHLOROFORM
5 CIS
.0005
6 M4
1 M 11 H Y L E N E CHLORIDE,
. 0200 ,OiFo
/ A-0I
t> L:1 l 0 A i,! DRM 4 CIS M4
.0005
6 fPM CHLORINE
600 , 00
1500.00
L PPM WrlTER 2 PPM HCL
2 0.00 5 . 0C
1 MLiHYlENE CHLORIDE
0 , 00
50 . 00
*
UINYLIDENE CHLORIDE
0 , 00
10.00
3 TRANS
6.00
10.00
- M4 CARLDN TET
0.00
200 . 00
5 CHLOROFORM
980000.0
1020000,
6 AMYLENE
7 CIS
0.00
30.00
b BRCLME
150.00
250.00
9 A-DI
0.00
2 5.00
10 PPM WATER
0,00
25.00
1 1 PPM HCL
10.00
S.t
1 2 PPM CHLORINE
1 METHYLENE CHLORIDE
014750 rNFTOFNTTA|
--------- ........... - --- --------------------------------------- _ -----------
mspecoi
2=10 PM THU , 26 APR., 1990 SPECIFICATIONS CATALOG
PAGE 3
PROFILES 10 - 2000
F'Kui-'ILE ft* 1 13
DETERMINANT #
2 3 4 3 6 7 8 9 10 11 12 13
DESCRIPTION'
r"
TRAMS fl-Dl CHLOROFORM TL'E METHYL CHLORIDE UINYL CHLORIDE CIS EDC M4 B-TR] UNSYM-TET SYM-TET
LOU SPEC' HIGH SPEC' 1.8000 /, 0*>l
J 1?
1 PPM WATER 2 ' PPM HCL
80.00 7.00
120
1 WTfT HCL V DIMETHYL ETHER 3 METHYL CHLORIDE
4 METHANOL
)g t* A3
i. 1 1 UT* HCL / DIMETHYL. ETHER 7 methyl chloride <4 MET i i h i i u i.
+* 3v3
/2 14 METHYL CHLOKjUF. V METHANOL
METHYLENE CHLORIDE
4 M4 CARBON TET V, CHLOROFORM
6 WT* HCL
) f>fy^ Sff**
12 124
1 DIMETHYL ETHER 2 METHYL CHLORIDE 3 METHANOL
i
1 UT'/, H2S04 2 DIMETHYL ETHER 3 METHYL CHLORIDE 4 METHANOL
OrtL *7 fprr\
D0 014754 OONFTDFNTT Al
Ltd
2=10 PH THU. 26 APR., 1990
SPECIFICATIONS CATALOG
KUHLt #i 125
DETERMINANT #
DESCRIPTION: ; -' _/
UTS HCL
PAGE 4 PROFILES 10 - 2000
LOU SPEC: HIGH SPEC
?
MS**-*-
j1
6 2 B 9 / 10 / 11 11 `.1 3
J4
IF
METHANE ETHYLENE ETHANE ACETYLENE DIMETHYL ETHER METHYL CHLORIDE UINYL CHLORIDE METHANOL METHYLENE CHLORIDE ETHYL CHLORIDE FREON 12 PROPANE/BUTANE PPM UA7ER PPM HCL UISUAL APPERANCE
980000.0 U/U
10.00 5 00 5.00
10.00 10.00 1020000. 50.00 50.00 50.0 0 50.00
1 . 00
80.00 7 . 00 U/U
MCI HAN[
10.00
ETHYLENE
5 . 00
ETHANE
5.00
4 ACETYLENE
10,00
i., DIMETHYL El HER
10.00
t
h E T H Y L CHLORIDE
980 0 00.0
10 2 0 U 0 0 .
OINYL CHLORIDE
5 0.00
M E T H AIIJ L
50 . 00
ML I H YL L N [ CHIP P J. DL
5 0.00
ETHYL CHLORIDE
50 . 00
F KL0N 1 2
1.00
PROPANE/BUTAND
1. PPM UATER
80,00
.1 i PPM HCL
7 . OC
1 F UISUAL APPERANCE
U/U
U/U
1 METHANE
10.00
2 ETHYLENE
5*. CO
3 ETHANE
5 . 00
4 ACETYLENE
10.00
3 DIMETHYL ETHER
10.00
6
METHYL CHLORIDE
980000.0
1020000.
7 UINYL CHLORIDE
5 0.00
B METHANOL
50 , 00
9 METHYLENE CHLORIDE
5 0.00
i 0 ETHYL CHLORIDE
5 0.0 0
DO 014755 OONFTDFNTTAI
115 F' r L 0 1
2=10 PH THU. 26 APR., 1990
SPECIFICATIONS CATALOG
PAGE 5 PROFILES 10 - 2000
PROFILE #= DETERMINANT #* DESCRIPTION*
LOU SPEC* HIGH SPEC*
128 1 1 FREON 12 12 PROPANE/EUTANE 13 PPM WATER 14 PPM HCL 15 UISUAL APPERANCE
U/U
1 . 00
80.00 7.00 U/U
129
1 METHANE
10.00
2 ETHYLENE
5,00
3 ETHANE
5.00
4 ACETYLENE 5 DIMETHYL ETHER
10.OC 10.00
6
METHYL CHLORIDE
960000.0
1020000.
2 UINYL CHLORIDE
50.00
B METHfiNOL
..
50,00
METHYLENE CHLORIDE
'
50.00
iu
ETHYL CHLORIDE
'
\ 1 FREON 12
50,00 1.00
i 2 PROPANE/EUTANE
PPM WATER
80,00
PPM HCL
7,00
J 5 UISUAL APPERANCE
U/W
U 'U
O O
oo
1 METHANE
10,00
Jlo `-71
/ ETHYLF NE
ETHANE
5.00
z ACETYLENE n. DIMETHYL ETHER
1 0 , C0 10,00
6
METHYL CHLCPIDF
980000 , 0
1020000,
i UINYL CHLORIDE
A METHANOL Q METHYLENE CHLORIDE
5 0.00 50 . 00
L i' ETHYL CHLORIDE
5 0.00
1 1 FREON 12
1 . 00
1 2 PROPANE/EUTANE
1 PPM WATER
80 00
14 PPM HCL
7 . 00
1 5 UISUAL APPERANCE
U/U
U/U
17i
1 Ml/Ul
.0005
2 METHYL BROMIDE
. 0030
3 ETHYL CHLORIDE
,0100
4 PROPYLENE OXIDE
. 0001
5 UINYLIDENE CHLORIDE
.0100
6
METHYLENE CHLORIDE
98.0000
102.0000
0 01.4 756 ^onftdfnttai
MCPLL01 Ph'Uh LE 131
17
2:10 PH THU. 26 APR., 1990
SPECIFICATIONS CATALOG DETERMINANT #: DESCRIPTION:
PAGE 6
PROFILES
10 - 2000
LOU SPEC: HIGH SPEC
7 TRANS 0 A-DI 9 CHLOROFORM 10 CYCLOHEXANE 11 TCE 12 PPM WATER 15 PPM HCL 14 COLOR READING 15 UISUAL APPE.RANCE
.0250 Clear
. 0200 .0010 .0100 , 0350 .0001 75.00
5.00
5. C Tear
1 Ml /VI
. 0005
2 METHYL BROMIDE
.0030
ETHYL CHLORIDE
.0100
4 PROPYLENE OXIDE
. 0001
VINYL I DENE CHLORIDE` '
.01(0
ME r H Y l E(1E CHLORIDE-
90.0000 102.00/0
TRAN 0
.0/00
A-D1
,0010
CHlORCFORM
.0100
(} CYClOHEXANC
.0250
. 0350
TCE . 000 1
PPM WATER
7 5,00
1 3 PPM HCL
5.00
C 01_ 0 R R E A DIN G
5,
1 VISUAL AfTfRfiMCE
Clear
Clear
1 '11/01
. 0003
- MLll.lL BkOMIDE
.0030
El MIL CdlORIDE
.0100
/ ERCIPYLELL O^IDE
.000 1
UINYLIDENE CHLORIDE
, 01 u C
t
METHYLENE CFlGRIDE
9B , 00u C
102.00.0
/ TRANS
. 0200
A-DI
.0010
y C H L 0 R L. F G R1
.0100
i 0 CYCLOHEXANE
.0200
. C400
l: T LE
.0001
i / PPM WATER
75.00
1 3 PPM HCL
5.00
14 COLOR READING 1 5 UISUAL APPERANCE
Clear
5. Clear
1 Ml/Ul
2 METHYL BROMIDE
.0005 . C 0: 5 0
DO 014757 OONFTDFNTIAl
S P 11 0 I r R U! I L. L tl : i: '~i
: 31
2 = 10 PM THU. , 26 APR., 1990
SPECIFICATIONS CATALOG
DETERMINANT # = DESCRIPTION:
3 ETHYL CHLORIDE 4 PROPYLENE OXIDE 5 VINYLIDENE CHLORIDE 6 METHYLENE CHLORIDE 7 TRANS ti A-DI 9 CHLOROFORM 1 0 CYCLOHEXANE 1 1 TCE 12 PPM WATER 13 PPM HCL 14 COLOR READING 15 UI5UAL APPERANCE
J Ml/VI 2 METHYL BROMIDE 3 ETHYL CHLORIDE i PROr-YLENE OXIDE
VINYLIDENE CHLORIDE 4 METHYLENE CHLORIDE V TRANS !.i A - D 1
CHLOROFORM CYCLOHEXANE - j TCE i J. PPM Wf-TEF 1 4 PPM F'L_ i 4 C D L 0 R R E A D .1 N G j - VISUAL APPERANCE
PAGE 7
PROFILES
10 - 2000
LOW SPEC* HIGH SPEC
.4000 97.0000
. 0200
Clear
.0100 . 6000 ' .0100 1015.000 . 0200 .0010 .0100 . 0400 . 0001 7 5.00
5.00 5.
C 1 ea r
1 . 5000 96,5000
. 0200
Clear
.0005 .0030 .0100 1 . G000 ,0100 10 0.00 0 0 . 0200 ,001 0 .0100 . 0400 , OOOl 75 . C 0
5 . 00 5
Clear
137
1 METHYLENE CHLORIDE
/ ETHYL CHLORIDE
METHYL BR0M1DL
/; U1NYLIDENE CHLORIDE
5 TRANS
L CHLOROFORM
7 Ml/01
0 AMYLENE
9 PPM WATER
75.00
10 COLOR READING 1 1 VISUAL APPERANCE
Clear
5.
Clear
12 PPM HCL
5.00
1 Ml/Vl
,0005
r
Oi N^r%
mspl.coi
2=10 F'M THU. 26 APR,, 1990
SPECIFICATIONS CATALOG DETERMINANT #: DESCRIPTION:
PAGE S
PROFILES
10 - 2000
LOU SPEC: HIGH SPEC
2 METHYL BROMIDE
. 0030
3 ETHYL CHLORIDE
.0100
4 PROPYLENE OXIDE
.4000
.6000
5 UINYLIDENE CHLORIDE
.0100
6
METHYLENE CHLORIDE
98,0000
102.0000
2 TRANS
. 0200
& A-D I
.0010
9 CHLOROFORM
.0100
10 CYCLOHEXANE
. 0200
. 0400
1 1 TCE
. 0001
12 PPM HATER
7 5.00
13 PPM HCL
5.00
14 COLOR READING
5,
15 UI5UAL APPERANCE
C lear
Clear
1 Ml/01
. 0003
'l METHYL BROMIDE
. 0030
ETHYL CHLORIDE
.0100
*\ PROPYLENE OXIDE
1.5000
1 . 8000
:> OINYLIDLNE CHLORIDE
.0100
(,
M E T11Y >,, E1! E CHLORIDE
96.5000
100.0000
/ TRAN0
. 0200
j fl " J *
.0010
y CEIL OF: OF URM
.0100
j v C YCLOHEXANE
. 0200
. 040 0
1 5 TIE
. 000 1
11 F' F'M CATER
7 5.00
i ! P PM HLL i<, COLOR READING
k
X * 0 1OUAL APPERANCE
Clear
C lear
Oo
uT
j M1 / 0 1
. 0003
. METHYL BROMIDE
.0030
3 ETHYL CHLORIDE
.0100
4 PROPYLENE OXIDE
. 00C1
3 UINYLIDENE CHLORIDE
.0100
6
METHYLENE CHLORIDE
98.0000
102.OOOU
7 TRANS
. 0200
b A-DI
.0010
9 CHLOROFORM
.0100
10 CYCLOHEXANE
. 0200
. 0400
11 TCE
. 0001
12 PPM WATER
7 5,00
1 3 PPM HCL
5.00
14 COLOR READING
5,
no 0 7 4 ~7 S <9 OOtyp
Td^NT JAJ
SPL.iLO 1 F'ROrlLE
2:10 PM THU. 26 APR., 1990
SPECIFICATIONS CATALOG DETERMINANT #: DESCRIPTION
PAGE 9 PROFILES 10 - 2000
LOU SPEC: HIGH SPEC*
15 VISUAL APF'ERANCE
Clear
C1ea r
METHYLENE CHLORIDE
200.00
0 INYLIDENE CHLORIDE
100.00
TRANS
20.00
4 M4 CARBON TET
250.00
5 CHLOROFORM
980000.0
1020000.
6 AMYLENE
10.00
20.00
7 CIS
e BRCLME
8 0,00 300.00
9 A-D I
100.00
: o PPM WATER
50.00
4 1 PPM HCL
10.00
1 2 COLOR READING
, 10 .
J '? VISUAL APPERANCE
Clear
Clear
1 METHYLENE CHLORIDE
200.00
U INYL I DENE LhL0R I DE
100.00
TRANS
2 0,00
M4 CARBON TET
2 5 0.0 0
C H _ 0 R` 0 F 0 R M
980000 . 0
1020000.
AMYLENE
10.00
2 0.00
r Is G0 . 00
EPC LME
500.00
A-DI
100.00
F PM * AT E F:
5 0.0 0
PPM HE!
K . 0C
i C 0 L n R P E f, D 1 N G
10 .
j . 0 I 5 Li H L A i1 E R f: N C E
C 1 ear
C 1 cl r
METHYLENE CHLORIDE
l OINYlIDENE CHLORIDE ? TRANS
200 . 00 20 . 00 20 . 00
4 M4 CARBON TET 5 CHLOROFORM
980000,0
250 00
1020000.
6 AMYLENE
10.00
20,00
7 CIS
80.00
Li BRCLME
300.00
9 A-DI
100.00
1 0 PPM WATER
5 0.00
1 1 PPM HCL
10.00
1 2 COLOR READING
10 .
1 3 VISUAL APPERANCE
Clear
C 1 ea r
METHYLENE CHLORIDE
200.00
mspe.cc 1
2*10 FM THU. 26 RPR., 1990
PAGE 10
SPECIFICATIONS CATALOG
PROFILES 10 - 2000
!' R 0: IlE #* DETERMINANT #* DESCRIPTION
LOU SPEC* HIGH SPEC
14 3
2 UINYLIDENE CHLORIDE
100.00
3 TRANS
20.00
4 M4 CARBON TET
250.00
5 CHLOROFORM
980000.0
1020000,
6 AMYLENE
10.00
20.00
/ CIS
80.00
8 BRCLME
300.00
9 A-DI
100.00
10 PPM UATER
50.00
1 1 PPM HCL
10.00
12 COLOR READING
10 .
13 UISUAL APPERANCE
Clear
Clear
14
1 METHYLENE CHLORIDE
-200.00
UIN Y LIDE N E CHLORIDE
100.00
T RANS
20.00
M4 CARBON TET
250.00
CHLOROTORM
980000.0
1020000.
'j AP1YLENE / CIS
10.00
20.00
eo, oo
brclm:
300.00
A- DI
100.00
.1 0 PPM UATER
5 0.00
1 1 PPM HCL
10.00
J / COLOR READING
10 .
U1SUAL AF'PE RANGE
C Tear
Clear
1 E "! H A N 0 L
METHANOL 3 PPM WATER
a PPM IICL
.0100
200.00 15.00
i a/
1 ETHANOL L. METHANOL 3 PPM UATER 4 PPM HCL
1 METHANE 2 ETHYLENE 3 ETHANE 4 ACETYLENE 5 DIMETHYL ETHER 6 . METHYL CHLORIDE
.0100
200,00 15.00
980000,0
10.00 5.00 5.00
10.00 10.00 1020000 .
00 014761 C'ONF IDFNTT Al
rir.F't col
2*10 PM THU. , 26 APR . , 1990
SPECIFICATIONS CATALOG
PROFILE #s DETERMINANT #> DESCRIPTION:
j47
7 OINYL CHLORIDE 8 METHANOL 9 METHYLENE CHLORIDE 10 ETHYL CHLORIDE J1 FREON 12 12 PROPANE/BUTANE 13 PPM WATER 14 PPM HCL 15 UOL, y. NITROGEN 16 OISUAL APPERANCE 17 SHIPPED ? 1 B SEAL NUMBER 1 9 SEAL NUMBER 2 0 SEAL NUMBER 21 SEAL NUMBE R
PAGE 11
PROFILES 10 - 2000
LOU SPEC: HIGH SPEC:
50.00 50.00 50.00 50.00
1 .00
80.00 7.00 2.00
7.
O
oo
1 Ml/01
.000 5
... METHYL BROMIDE .? ETHYL CHLORIDE
.0100
I'-i PROPYLENE OXIDE i-., UINYLIDENE CHLORIDE
, 0001 .010 0
d
METHYLENE CHLORIDE
98 . 0000
102.0000
7 TRANS
, 0200
8 A-DI 9 CHLOROFORM
.0010 .0100
1 0 CYCLOHEXANE
. 0200
. 0400
1 1 TOE
. 0001
J PPM WATER
7 5.00
1 3 PPM FILL
5.00
C0L CR READING l r. OISUAL APPERANCE
S 1 ear
5. Clear
1 d SHIPPED
i 7 SEAL NUMBER
18 SEAL NUMBER
19 SEAL NUMBER
20 SEAL NUMBER
21 TRAILER tf
i 30
1 PPM SULFITE 7 PPM PHOSPHATE 3 CONDUCTIUITY READING
13 1
METHYLENE CHLORIDE
200.00
UINYLIDENE CHLORIDE
100.00
DO 01 47,~> CONFTDFNTIAI
mspl.co 1
2 = 10 F'M THU. 26 ftpR., 1990
SPEC IFI CAT IONS CATALOG
PROFILE #= DETERfllNANT #s DESCRIPTION*
15L
3 TRANS
4 M4 CARBON TET
b CHLOROFORM
6 AMYLENE
7 CIS
b BRCLME
9 A-DI
10 PPM WATER
11 PPM HCL
12 COLOR READING
13 VISUAL APF'ERANCE
14 SHIPPED ?
15 SEAL NUMBER
J, t> SEAL NUMBER
17 SEAL NUMBER
i O J. u
SEAL NUMBER
PAGE 12 PROFILES 10 - 2000
LOU SPEC* HIGH SPEC
980000,0 10.00
Clear
20.00 250.00 1020000.
20.00 80,00 300.00 100,00 50.00 10.00
10 . Clear
] m / vi
. 000 5
METHYL BROMIDE
.0030
ETHYL CHLORIDE
.0100
<4 P Fv 0 D Y L E N E OXIDE r VINYLIDFNE CHLORIDE
. 0001 .0100
P
METHYLENE CHLORIDE
96.0000
102.0000
TRANE
.0200
ft - L I
.0010
CHLUROrORM
. 0 1 OU
J U C Y l L 011E X ft Pi E
. 0200
, 04 0 0
1 1 TEE
. CC 0 1
PPM UftTER COMP 1
PPM WATER COMP 2
PRIM WATER COMP 3
3 5 PPM HCL COMP i
J u PPM HCL LUni' / I > PPM HCL COMP 3
COlOR COM?' 1
COLOR COMP 2
2 0 COLOR COMP 3
2 J VISUAL APF'ERANCE 2/ S H I P P E D ?
C 1 ee r
C 1 eci r
2 3 BARGE ID #
1 METHYLENE CHLORIDE 2 VINYLIDENE CHLORIDE 3 TRANS 4 M4 CARBON TET
200.00 100.00
20.00 250,00
00 0147^3 ^ONFTDFNTTA!
P Ei C 0 1
2=10 PM THU. 26 APR., 1990 SPECIFICATIONS CATALOG
FF r 1 1-1 *1 = DETERMINANT #: DESCRIPTION:
i S'i CHLOROFORM AMYLENE CIS BRCLME A-n t
10 PPM WATER COMF 1 11 PPM WATER COMP 2 iZ PPM WATER COMP 3 13 PPM HCL COMP 1 14 PPM HCL COMP 2 10 PPM HCL COMP 3 16 COLOR COMP 1 12 COLOR COMP 2 1C COLOR COMP 3 19 VISUAL. APPFRANCE , 1 SHIPPED ' 2 1 BADGE ID tl
page; 13 PROFILES 10 - 2000
LOU SPEC* HIGH SPEC
980000.0 10.00
1020000. 20.00 80,00
300.00 100.00
Clear
.Clear
1 ETHAN 0L
2 M n T Hi A N 0 L 3 PPM WATER COMP 1
P PM W A T E R COMP P P!'i W AT E R CO 1'.
P P M n C L coi.p .; F1 ^ M H C 1, C CMP 2
P - M F C . COM! ' L Li L .J 1- L <M .' 1 C C 1- " R D vir COLO h C On:' E '. F; C i. ' li
.0100
FT. T F, Y l t M E C rl L. A Di CHLOROr CRM Cl S r, M4
1 METHYLENE CHLORIDE 2 VINYLIDENE CHLORIDE 3 TRANS 4 M4 CARBON TET 5 CHLOROFORM 6 AMYLENE
7 CIS
014764 CNFTDFNT TAl