Document M41N87aQrD6ynKV19O6Y6Rk7a
American Society of Heating and Ventilating Engineers Guide, 1934
Chapter 24--Gravity Warm Air Systems
7. Size of furnace necessary to supply the warm air required to overcome the heat loss from the building. This she should include square inches of leader pipe area which furnace must supply. It is also desirable to call for a minimum bottom fire-pot diameter in inches, which is the nominal grate diameter.
8. Area and dimensions.in inches of chimney and smoke pipe. If an unlined chimney
is to be used, that fact should be made .clear.
The heat loss calculations should be made in accordance with the procedure outlined in Chapter 7, taking into consideration the trans
mission losses as well as the infiltration losses.
SIZES OF LEADER PIPES
In a gravity circulating warm-air furnace system the size of the leader
to a given room depends upon the temperature of the warm air entering
the room at the register. A reasonable air temperature at the registers
must, therefore, be chosen before the system can be designed. The
National Warm Air Heating Association has approved an air temperature
of 175 F at the registers as satisfactory for design purposes. At this tem
perature, the heat-carrying capacity (heat available above 70 F) per
square inch of leader pipe per hour for first, second or third floors is shown
by Fig. 1 at 175 F to be 105, 170 and 208 Btu respectively. For average
calculations, the values 111, 166 and 200 will simplify the work and may
be satisfactorily substituted for these heat-carrying capacities. If H
represents the total heat to be supplied any room, the resulting equations
\are:Leader areas for first floor, sqqare inches = H = approximately 0.009//
(1)
\
Leader areas for second floor, square inches = ^H = approximately 0.006/7 (2)
Leader areas for third floor, square inches = ^ - approximately 0.005/7 (3)
In designing for a lower warm-air register temperature, say 160 F, the factors 111, 166 and 200 become 80, 140 and 166 (Fig. 1 at 160 F), and
the resulting equations are:
Leader areas for first floor, square inches =
= approximately 0.012//
(4)
Leader areas for second floor, square inches = H = approximately 0.007H (5)
Leader areas for third floor, square inches = H -- approximately 0.006//
(6)
, These equations are applicable to straight leaders from 6 to 8 ft in
length. . Longer leaders must be very thoroughly covered or else the
vertical stacks must be increased in area as discussed under wall stacks.
If some provision is not made for these longer leaders, the air tempera
ture may be much lower than anticipated and the room will not be
properly heated.
- --- .
While Fig. 1 takes care of the drop in temperature in straight leaders
up to 8 ft in length connected to stacks having about 75 per cent the
319