CHAPTER 38
1965 Guide And Data Book
d. A plate valve formed at a ring with some part of the valve
structure clamped. A full {date is sometimes used with two or
more seta of slots arranged is circles. By clamping the renter of
the plate a force b provided for *lr>rig the valve. Most problems
in nng valve design are connected with the shape of ute valve
during operation. Unlees the shape b known the stresses cannot
be calculated. Every effort b therefore being made to shape back
stops or valve supports so that they will limit the stresses. As an
example, it can be seen that a simple ring with four spokes to a
clamped hub will have a:combination oi bending and twisting
during normal opening. If there are uneven gas forces in addition,
stieases can go far Beyond the values
for normal
operation. Various methods.have been used to produce better
defined movement of the valve. Wave-shaped backstops nw^H.
with the spoke-ring transition points will limit the stress concen
tration where the spokes join the ring. A full clamping across a
diameter will .produce a motion similar to a cantilever reed and
curved bach stone are usually provided for thi type. Other coo-,
structiona provide a large number of support fingers, almost Hire
gear teeth, so that the deflection b nearly the shape of a flat cone.
Npuiy ring valves are provided with relief arrangement' to
avoid damage during liquid slugging. * The relief ts usually
obtained by using a heavy spring to hold the valve assembly in
place.
Capacity Control
j :'
A perfect capacity control system would have the following
operating ehaxacterirficB:
.\
1. Continuous adjustment to load. ~ 2. Same efficiency for full or partial load.
3. Full load efficiency should not be affected by the mechanism. 4. Capacity control should not affect compressor reliability.
Not aB of these benefits can be had in the
machine
Capacity control may be obtained by: controlling suction
pressure by throttling, controlling.discharge pressure, return
ing discharge gas to suction, adding re-expansion volume,
changing the stroke, opening a cylinder discharge port; to
suction while closing the port to discharge manifold, reducing
compressor speed, and closing off cylinder inlet.
The most commonly used are the opening of the suction
valves by some external force, hot gas bypassing discharge
to suction within compressor and hofgas bypassing external
to the compressor.
,
Valve Plates
, ..
Valve plates are usually made of cast iron or steel. Where floating ring valves are used, the valve seats 'are usually hardened to resist the severe impact. Designs em ploying reed valves fixed at one end, or ring valves held at the center do not usually require hardened valve seats.
Crankcase Heaters
Migration of the refrigerant back to the oil in the com
pressor crankcase always 'exists. To
the migration
during shutdown, crankcase heaters should be employed!
Crankcase beaters should keep the crankcase temperature
at least 20 F above the rest of the system but well below'the
breakdown temperature of the oil.
,
Cylinder Cooling
.. Cylinder cooling is accomplished by means of air, water and refrigerant. This can be done by finning the crankcase and/or cylinder heads for.air cooling or by providing, flow passages in the heads for refrigerant or water cooling."Cylinder cooling means are always employed on ammonia'compressors and on some,Refrigerant 22 installations to maintain the dis charge temperature below 300 Fto prevent oil breakdown. Temperatures in excess of 300 F can cause refrigerant break down and should be avoided. Temperatures as measured should be 300 F at the discharge valve guide or 275 F on 'the discharge line immediately following the service valve.
Oil Cooling
CHI cooling is always employed oh ammonia,compressors and where warranted on Refrigerant 22 applications. OQ
coolers are normally of the water to oil type. Refrigerant to oil or air to oil coolers are also used. The naiimnm operating oil temperature,that will insure adequate seal cooling in open compressors is 160 F and bearing cooling in hermetic com pressors is approximately IK) F.
APPLICATION Motor Protection,
The purpose of the protection system is to keep the motor
from overheating or drawing excessive operating currents. As
a second function, it will alert the operator to abnormality
which then can be corrected before further damage occurs.
The system"should comply with the National ElectricCdde
which will not allow the motor to draw,current in
0f
140 percent of full load current. This maximum current occurs
at a torque point well beyond the normal full load torques and
is selected to allow eafecbntinuous operation up to that point.
During normal operations, motor temperatures will be
relatively low even at the maximum current point of the sys
tem. However, in selecting a protection scheme recognition
of conditions where high temperatures exist'ia spite'of .low
currents must be made. Conditions which create this state
are: (i) loss of motor coolant (refrigerant charge loss), (2)
low suction pressure and high superheat at the'compressor,'
and (3) blockage of the device feeding refrigerant to the evapo rator.
Whereas the National Electric Code defines maximum cur
rent, no dear indication of allowable maximum motor tem
perature is made. Hence, the selection is dependent on the design of the compressor, the motor insulation system, ro-
frigerant, oil and required range of operation. Another criterion for selection is that of response, i.e., the
time that elapses from the Banning of the unsafe condition to
the actual operation of the device. If the time is extremely short, difficulties in starting may occur. If too long, a burnout
on locked rotor would happen. Thus there is an optimum range of trip response for a given current. At a stalled condition a
2 second minimum and a 10 second maximum are considered adequate for conventional protectors.
One somewhat special application is the use of the protec
tive device as a normal operating control. Refrigerator and
room air-conditioning motors, for instance, will not generally
start agaihst'full load and are taken off the line by the pro
tector, then immediately restarted automatically until
pressures have equalized" to a level allowing a proper start'
This scheme has a low initial cost, but has the disadvantage of
not distinguishing between normal operation and trouble.
The specific types of motor protection now in common use are:
1. Current Sensitive Overloads: These remove the compressor
from the line when a riven current is reached. Depending on the type, all are more or less sensitive to the surrounding ambient
rature and it must be considered when the.selection is In hermetic .compressors where suction gas refrigerant is
employed as a motor coolant, the ratio of starting current to full load amps is relatively small and the heating rise rate at the stalled condition high The trip current, therefore, must be rela
tively, high and the response rate short to adequately anticipate
the stalled motor temperatures. This device then would have a response rate close to the 2 second minimum mentioned above.
2. Temperature Sensing Switch: Presently these are available in hermetically sealed cases and can be buried in the motor
windings. These devices are used strictly to keep the motor below a predetermined maximum temperature during running opera
tion. Generally they do not respond to a rapid temperature rise quickly enough to offer locked rotor protection.
i*
Compressor
641
a Temperature and Current Combination Devices: These are mflable m hermetically or non-hermetically seeded packages. Spatially temperature sensing, the source of the temperature
fnbe either motor current as carried by the device or a heat ""aerating condition such as loss of refrigerant charge. The nonferrnetic devices must be mounted on the external casing and as aSiDrovide marginal overbeating protection particularly in the Mse of the internally spring-mounted compressors. The hennetiliUv sealed devices can be mounted directly on or in the windings! Depending on their rating, they can break line current directly or, bv handling a fraction of line current, operate a holding coil. ^4. Temperature, Current, and Rise Rate Combination Devices: These devices in addition to sensing current and temperature --snood to motor rue rates. The trip time during locked rotor will vurv inversely u the motor temperature rise rate. They employ
frcrfhnniwd or solid state components. In their present state, these
aza being applied on large motors in the control circuit.
Liquid Return to Compressor .
a compressor is not designed for, nor can it be made-to* large quantities of liquid without eventual damage to
parts." Primarily, the compressor pistons move too rapidly;' the velocity of the flow through the' suction and discharge! valve is purposely designed high. Therefore, if liquid enters the*' cylinder, it will almost act as a solid mass and cause incoor: eeivably High damaging forces upon all parts.
It is not sufficient to put a trap in the suction line to catch, this liquid, unless there are means to get rid of it! Eventually
the trap will fill and the liquid will come into the cylinder anyway. It is, of course, best to evaporate the liquid in the evaporator by controlling the liquid feed.
During shutdown, many things continue to happen inside' a system. The refrigerant in the condenser and receiver will; try to flow toward the source of low pressure and tempera-! tore. The flow will come through the expansion device and: ako try to pass the discharge valves in the compressor. When; gas enters the evaporator it condenses due to the temperature; prevailing there. This liquid in the evaporator can build up. and become a potential hazard when it returns to thecom-; pressor during start-up.
. This problem can be solved:
1. By controlling refrigerant charge in the system so that the' quantity returning to the low side during shut down is small. '
2. By using suction accumulators that, provide space where a! liquid mass can be delayed and broken up. This accumulator may" be the compressor itself if it has sufficient volume to hold the. entire system charge without slugging.
3. By applying heat to any point where liquid is undesirable;
A crankcase heater is very effective in this respect. Since it
is only necessary, to make the compressor temperature slightly,
higher than the temperature of the rest of the system a heater
.of low wattage can be used. It is finding more and more use
with the extensive application of condensing units placed
outdoors in split systems with large' refrigerant charges.1
Heating of the crankcase also keeps the lubricating oil nearly,
undiluted so that the bearings receive, at least for a short
period, pure oil at full pressure when the compressor starts.
Remember that the heater is effective "only during shut*'
down and that proper siring of the system and feeding device,
properly sized charge or the use of an accumulator are required
to insure normal operation after startup.
..
For .details of design and application to prevent .liquid
return, see Chapters 76 to 80, 1964 Guide And Data Book.
Heat Exchangers ;
A heat exchanger in the suction return gas.will aid system performance and assure return of dry gas to the compressor.
Good design of the exchanger is essential to avoid excessive pressure loss,- trapping of oil' insure efficient transfer of heat. The velocity of the gas through the exchangers must begreat enough to insure oil return at all operating conditions.
For details of design and application, see Chapters 76 to 80 of the 1964 Guide And Data Book.
Automatic Oil Separators
Oil separators are used to insure oil return to the compressor crankcase and in some cases to prevent oil from entering the evaporator. They are recommended for use in systems where tiie oil is not miscible with the refrigerant (Ammonia, and Refrigerant 13 in particular).
With the halocarbons, the low oil circulation rate of the modem compressor and proper design of the systems has eliminated the ute of oil separators in all except a few cases.
Parallel Operation
Parallel operation of compressors presents many difficulties
in. connection with oil return from the evaporator, and oil
level in the crankcases. The development in recent years has
been towards multiple, completely independent refrigerant
circuits which have the same benefits as parallel operation
(low starting current, high efficiency at partial loads) and
none of its disadvantages. It gives better control and the
added cost of multiple lines can be less than the cost of cross-'
controls for the parallel system.'
With a number of compressors operating in parallel, the
returned oil must be properly apportioned between the com
pressors. Fig. 4 shows the method most widely used. Line A
connects the top of the crankcase and equalizes the pressures'
above the oil, while line B connects to a point just above the
oil level and insures a normal level in each crankcase. When1
these lines are of sufficient size, little variation in level between'
units will be noted. In addition to these connections, the high-pressurc sides of
the lubrication pump can be cross-connected so that" if one'
pump ceases to function due to failure, oil pressure can be'
maintained in both compressors. - A* central reservoir for collecting return oil and level control'
ttimih (such as float valves) to feed oil to the various crank
cases, may also be used. For details of Herign and application, see Chapters 76 to 80
of the 1964 Guide And Data Book.
"'
Protective Devices
Compressors are provided with one or more of the following
devices for protection against abnormal .conditions and to'
comply with various codes.
,. -
1. Over current protection as required by the National Electric>
Code.
`
2. High pressure protection as required - by Underwriter*?
Laboratory and per ARI Standards and ASA B9.1, Safety Code.'
This may include:
a. A high pressure cutout. b. A to low ride internal relief valve or rupture member.
c. A relief valve or rupture member on the compressor with
gimilflx to those used oq other pressure vessels.
3. High temperature control devices to protect against motor'
overheating and oil breakdown.
' a. Motor over temperature protective devices which were
... discussed in section on Motor Protection.
b\ .To protect against oil and refrigerant breakdown a limit t
switch is
used to. stop the compressor when
discharge temperatures exoeed safe values. Discharge-
temperatures may reach unsafe values at high pressure
ratios or at partial compressor loads.
; ---<; ,-
c. .OQ temperatures sometimes are controlled on large.com-
" pressors where separate ofl coolers are employed.;' d. Whi- frarlrrAHe heaters are used to maintain a minimum'
' crankcase temperature, a thermostat is sometimes used;
to limit the maximum ofl temperature.
- 4. Low pressure protection may be provided for:" -.
**
" a. Suction gas. Many,compressors are limited to a minimum1 suction pressure'and-a'protective switch' is' provided."3