Document LpKegQ9OepX2y3OajxdQMryvg

458 CHAPTER 18 1956 Guide Btu per lb coal, and for other heating values of coal they must be multiplied by.the ratio of 12,000 divided by the heating value of fuel used. Example 6: A building in Scranton, Pa. has a calculated heat loss of 240,000 Btu per hr based on an inside design temperature of 70 F and an outside design tempera ture of --10F. What will be the estimated normal seasonal anthracite or coke consumption for heating if 13,000 Btu per lb fuel is burned in a hand-fired boiler, with automatic control, at a seasonal efficiency of 80 percent, and what part of the total will be used during November, December, and January? Solution: From Table 6, U is 0.0444 of coal or coke per 1000 Btu per hr heat loss per degree-day. Correcting for the outside design temperature of --10 F from Table 3, the value of U is 0.875 X 0.0444 = 0.0389. From Table 2, D is 621& and from the problem, N is 240. Substituting in Equation 4, F = 0D389 X 240 X 6047 = 56,500 lb. Fuel used over any period is, according to the theory of the degree-day, propor tional to the number of degree-days during the period. From Table 2, the average numbers of degree-days for November, December, and January in Scranton are 693, 1057 and 1141 respectively, a total of 2953. The yearly total is 27,000, so that during these three months the estimated consumption is 2R91 ~ X 56,500 = 27,000 lb. Estimating Steam Consumption In estimating steam consumption the efficiency is generally assumed at 100 percent. If for low-pressure steam an average heating value of 1000 Btu per pound of steam is used, no correction is necessary. In comparing values from different cities, correction should be made for design tempera ture (see Table 3) when the unit figures are in terms of heat loss but not when the values are in terms of building volume or floor space. Where the heat loss is calculated in Btu per (hour) (degree difference in temperature) the simple Equation 5 may be used: H X 24 X D 1000 (5)' where F = pounds of steam required'for estimate period. H = calculated heat loss, Btu per (hour) (degree difference). 24 = hours in one day. D = number of degree-days for the period of estimation. 1000 = Btu delivered per pound of steam condensed. In this method the number of degree-days automatically takes care of average inside and outside temperature difference. When degree-days are taken from Table 2, an average inside temperature of approximately 70 F is assumed throughout the period. If an average inside temperature other than approximately 70 F is to be used, the number of degree-days should be obtained for the new base. Example 7: An eight-story building in Pittsburgh is operated with a daytime temperature of 70 F. The calculated heat loss is 10,500 Btu per (hr) (degree temper ature difference). What is the estimated average yearly steam consumption for building heating? Solution: Since the average inside temperature is approximately 70 F, the degree- Estimating Fuel Consumption for Space Heating 459 days from Table 2, based on 70 F may be used. Therefore, from Table 2, Pittsburgh has 5048 degree-days per normal season. Inserting in Equation 5: = 10,500 X 24 X 5048 = 1272,000 lb of steam. 1000 Consideration has been given to the difference in steam utilization of different types of buildings, and Table 7 shows actual average units for these various types. These figures were obtained from operating results in 896 buildings located in all sections of the United States. Being aver ages, and for small, groups in each type, the figures may need considerable modification to allow for local variations. It should be especially noted that the steam used for heating water for service is not included in the values given in Table 7. Table 7. Steam Consumption op Buildings with Various Types op Occupancy* Type or Building No. Bldgs Average Volume Heated Space 1000 Cu Ft Steam for Heating Lb per DD per 1000 ' Cu Ft Average Eouks or Occupancy Office..................................................... Office and Bank............ Office and Printing.......... Office and Theater Office and Stores or Shops........... Bank........................ Department Store............................................. Stores......... Loft......... . Warehouse.............................. ' 334 49 :8 : 26 63 24 Olftrt .... 1615 flOO 3400 0* 112 , 0.385 Hotel and Club............ Apartment or Residence theater.............. . . Game'*. .. Manufacturing.................... 73 I7tf5 1425 . 22 0 482 19 i?tn Church.................... Hospital........................................... School....................................... Municipal or Federal............... i^>dge. Gym, Hall or Auditorium.................. Miscellaneous................... 8 15 12 . . * 880 ----- --------------------------------------------- ---------------------------------------------- 1.194 n'nnn * Principles of Economical Heating, National Association of Building Owners and Managers 13.2 11.7 11.1 10.4 10.0 . 9.4 22.3 12.9 21.4 9.5 22.0 11.5 15.6 12.4 . 21.4 u. .. o.uiv. in a miaueiimia wimi a Dealing system designed to maintain 70 F inside in 0 F weather has 250,000 eu ft of heated space. What would be the estimated average yearly steam consumption of purchased steam for heating? Solution: According to Table 7, a store would use 0.624 lb of steam per degree-day per 1000 cu ft heated space. From Table 2, Philadelphia has 4523 degree-days per normal year. Inserting in Equation 4: F = 0.624 X 250 X 4523 = 706,000 lb of steam. Degree-Day as an Operating Unit The degree-day is also widely used as a means of comparing the efficiency of the fuel consumption of one period with another for the same building. Since the fuel consumption is proportional to the weather (degree-days), and since the periods to be compared may not have the same weather con ditions, the comparison can be made only after the fuel consumptions have been computed on a comparable weather basis, that is, upon the actual number of degree-days occurring for a given month and year in the city under consideration Since fuel consumption'is proportional to the number