Document Lp4r9zKELYy0Lvz79G5OXV5RX
HEATING VENTILATING AIR CONDITIONING CUIDE 1942
Table 5.
100Thermal Expansion of Pipe in Inches per
ft*
(For superheated steam and other fluids refer to temperature column)
I - - - --
Saturated Steam
Pressure
VIanccuhuam
of H*.
Pounds Tem perature
Sgujuv Degrees Inch f Fahren
Gage
heit
Eponqation m Inches pen 100 rr moil -20 F op
Saturated Steam
CastIron Pipe
Steel Pipe
Pipe
[Pressure
Copper Kpe
Pounds Per
fperatorel
Square Inch
Gage
Degrees Fahren
heit
Elongation ik Incues red iqq pt peom --20 F up
CastIron Pipe
Steel ,ym*htJ
&
29.39 28.89 27.99 26.48 24.04 20.27 14.63 6.45
2.5 10.3 20.7 34.5 52.3 74.9 103.3 138.3 180.9 232.4 293.7 366.1 451.3 550.3
-20
0
20 40
60 80 100 120 140
160 180 200 220 240 260
280 300 320 340
360 380 400 420
440 460 480
000
0.127 0.145 0.152
0.255 0.293 0.306
0.390 0.430 0.465
0:518 0.593 0.620
649 0.725 0.780
0.787 0.898 0.939
0.926
1.051
1.055 1.209
1.110 1.265
1.200 1.368 1.427
1.345 1.528 1.597
1.495 !1.691 1.778
1.634 1.852 1.936
1.780 2.020 2.110
1.931 2.183 2.279
2.085 2.350 2.465
.233 2.519 2.630
395 2.690 2.800
2.543 2.862 2:988
700 3.029 3.175
.859 3.211 3.350
3.008 3.375 3.521
182 3.566 3.720
345 3.740 3.900
511 3.929 4.096
.683 4.100 4.280
0 | 664. 500
0.2041 795. 520
0.442J 945. 540
0.655 Jlll5.3| 560
0.88811308.,, 580
1.100 (1525.3 600
1.338(1768.3 620
1.570 (2041. ,, 640
1.794(2346.3 660
2.008 (2705
680
2.255 13080
700
2.500
720
2.720
740
2.960
760
3.189
780
3.422
800
3.665
820
3.900
840
4.145
860
4.380
880
4.628
900
4.870
920
5.118
940
5.358
960
5.612
5.855 i
980 1000
3.847
4.020 4.190 4.365 4.541
725 4.896 5.082
5.260 5.442 5.629
5.808 006
6.200 6.389, 6.587
6.779 6.970
7.176 7.375
570
7.795 -. .989 8.
.200 8.
8.406 9.
8.617 9.
250 ,464
662
4.477 6.110 4.677 6.352 4.866 6.614 5.057 6.850 5.268 7.123 5.455 7.388 5.660 7.636 5.850 7.893 6.067 8.153
6.260 8.400 6.481 8.676 6.673 8.912 6.899 9.203 7.100 9.460 7.314 9.736
7.508 9.992 7.757 10.272
7.952 10.512
'8.195 10.814'
8.400 II.175 8.639 III. 360
8.867 11.625 9.089 11.911
9.300 12.180 9.547 12.473
9.776 12.747
From Piping Handbook, by Walker and Crocker. This table1gives the expansion from --20 F to the
temperature in question. To obtain the amount of expansion between any two temperatures take the difference between the figures in the table for those temperatures. For example, if a steel pipe is installed
at a temperature of 00 F and is to operate at 300 F, the expansion would be 2.519 -- 0.593 ** 1.926 in.
has been found to give reasonably good results and is deemed to. be sufficiently accurate for most heating work.
Fig. 1 shows several types of expansion bends commonly used for taking up thermal expansion. The amount of pipe, L, required in each of these bends may be computed from Equation 2.
6.16 yDt
where
L = length of pipe, feet. D = outside diameter of the pipe used, inches.
AA -- the amount of expansion to be taken up, inches.
(2)
This formula, based on the use of mild-steel pipe with wall thicknesses not heavier than extra-strong, assumes a maximum safe value of fiber
stress of 16,000 lb per square inch. When square type bends are used, the width of the bend should not exceed about two times the height. It i
is
348
CHAPTER 18. PIPE, FITTINCS, WELDING
further assumed that the corners are made with screwed or flanged elbows or with arcs of circles having radii five to six times the pipe diameter. Use of welding elbows with radii of 1J4 times the pipe diameter will decrease the end thhists somewhat but will raise the fiber stress correspondingly.
All risers must be anchored and safeguarded so that the difference in length when hot from the length when cold shall not disarrange the normal and orderly provisions for drainage of the branches.
Proper anchoring of piping is especially necessaiy with light-weight radiators, to allow for freedom of expansion in order that no pipe strain will distort the radiators. When expansion strains, from the pipes are
Offset U bend
Fig. 1. Measurement of L on Various Pipe Bends
permitted to reach these light metal heaters they usually emit sounds of distress which are exceedingly troublesome.
PIPE THREADS
All threaded pipe for heating and ventilating installations uses the American Standard taper pipe thread which is made with a taper of 1 in 16 measured on the diameter of the pipe so as to secure a tight joint. 1 Thre1ads oIf fittingI s are tapped to the same taper. The number of threads per inch varies with the different pipe sizes. All threaded pipe should be made up with a thread paste suitable for the service under which the pipe is to be used.
HANGERS AND SUPPORTS
Heating system piping requires careful and substantial support. Where changes in temperature of the line are not large, such simple methods of support may be utilized as hanging the line by means of rods or perforated strip from the building structure, or supporting it by brackets or on piers.
When fluids are conveyed at temperatures of 150 F or above, however, hangers or supporting equipment must be fabricated and assembled to permit free expansion or contraction of the piping. This can be accom plished by the use of long rod hangers, spring hangers, chains, hangers or supports fitted with rollers, machined blocks, elliptical or circular rings of larger diameter than the pipe giving contact only at the bottom, or trolley hangers. In all cases, allowance should be made for rod clearance to permit swinging without setting up severe bending action in the rods.
For pipes of small size, perforated metal strip is often used. For horizontal mains, the rod or strip usually is attached to the joists or steel work of the floor above. For long runs of vertical pipe subject to con siderable thermal expansion, either the hangers should be designed to
349