Document Log5mgbj0eRNnzdzmGoZ1aDd7
mgwwpjugiJSiju ..JU'IJIJTipW
mgtm
ANSI C107.1-1974
guidelines for handling and disposal of capacitor- and transformer-grade askarels containing polychlorinated biphenyls
C107.1-1974
STLCOPCB4086620
-J-:'ftW^a 'itt^vrtfif^~*^'^*^`**-'*~*
rVMfei^.TvSMihSV.,
J ANSI
C107.1-1974
American National Standard Guidelines for Handling and Disposal of Capacitor- and Transformer-Grade Askarels
Containing Polychlorinated Biphenyls
Secretariat
National Electrical Manufacturers Association
Approved January 9, 1974
American National Standards Institute, Inc
0SW 7,W
STLCOPCB4086621
American National Standard
An American National Standard implies a consensus of those substantially concerned with its scope and provisions. An American National Standard is intended as a guide to aid the manu facturer, the consumer, and the general public. The existence of an American National Stan dard does not in any respect preclude anyone, whether he has approved the standard or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standard. American National Standards are subject to periodic review and users are cautioned to obtain the latest editions.
CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of the American National Standards Institute require that action be taken to reaffirm, revise, or withdraw this standard no later than five years from the date of publication. Purchasers of American National Standards may receive current information on all standards by calling or writing the American National Standards Institute.
j
j
ii
Published by American National Standards Institute 1430 Broadway, New York, New York 10018
Copyright 1974 by American National Standards Institute, Inc All rights reserved.
No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publisher. Printed in the United States of America A1 Ml 074/6
i; 1 s'
i
1
(
,,. DSW 357894
l
STLCOPCB4086622
Foreword (This Foreword is not a part of American National Standard Guidelines for Handling and Disposal of Capaci tor* and Transformer-Grade Askarels Containing Polychlorinated Biphenyls, C107.1-1974.)
Recognizing that the polychlorinated biphenyls present in askarels were being identified as envi ronmental pollutants and the urgent need for procedures and guides for their safe use and dis posal, the Board of Directors of the Power Equipment Division of the National Electrical Manu facturers Association (NEMA) in June 1970 appointed a committee to review the general problem and propose recommendations. In September 1970, the NEMA board approved, as recommended by the committee, the sponsorship of an American National Standards Commit tee for the use and disposal of askarels in electrical equipment.
American National Standards Committee Cl07 was established in April 1971. NEMA was desig nated as the secretariat. An organizational meeting was held on September 14, 1971. Mr W. B. Papageorge, Monsanto Company, was appointed chairman. Committee members included repre sentatives of capacitor and transformer manufacturers, utilities, governmental departments and agencies, and maintenance and disposal service companies. A steering committee and two sub committees -- one to develop guidelines for the capacitor industry, the other for the transfor mer industry -- were established.
The scope and primary objective of the committee was designated as the development of: Pro cedures and guides for the safe use, maintenance, and disposal of askarel and askarel-soaked materials used in electrical equipment.
Additional objectives proposed were as follows:
(1) To serve as a source for technical information and advice for federal, state, and local
authorities and for the information of all others concerned.
(2) To encourage the development of suitable disposal facilities and maintain a list of their
capabilities and locations, for the information of all concerned.
'
(3) To serve as the advisory group for U.S. participation in the International Commission on
Rules for the Approval of Electrical Equipment (CEE), the International Electrotechnical Com
mission (IEC), the Pan American Standards Commission (COPANT), the International Confer
ence on Large High Tension Electric Systems (CIGRE), and other international organizations.
The final draft of the guidelines was completed in late November 1972. NEMA issued the guide lines as an Official Standards Proposal in January 1973. It was submitted to the American National Standards Institute for approval as an American National Standard and was approved by the Standards Institute on January 9,1974.
Suggestions for improvement of this standard will be welcome. They should be sent to the American National Standards Institute, 1430 Broadway, New York, N.Y. 10018.
This standard was processed and approved for submittal to ANSI by American National Stan
dards Committee on Use and Disposal of Askarel and Askarel-Soaked Materials in Electrical
Equipment, Cl07. Committee approval of the standard does not necessarily imply that all com
mittee members voted for its approval. At the time it approved this standard, the Cl07 Com
mittee had the following members:
,
W. P. Papageorge, Chairman A. M. Salazar, Secretary
Organization Represented
Name ofRepresentative
Certified Ballast Manufacturers Association................................................................ N. R. Clark
A. Pozefsky
Chem-Trol Pollution Services Inc.................................................................................Louis E. Wagner
Doble Engineering Company............................... .. ....................................................... A. L. Rickley Electrical Utilities Company.......................................... ........................ ..................... A. O. Hauser
E. M. Moore (Alt)
Electric Light and Power Group.................................................................................... F. R. Lengefeld
H. A. Onishi
J. J. Cawley (Alt)
DSW 357895
STLCOPCB4086623
. S r-^. \ ; J :
.
Organization Represented
-
Electronic Industries Association............................ Environmental Protection Agency............................ General Services Administration............................... Gilbert Associates Inc ........................................... Institute of Electrical and Electronics Engineers, Inc Monsanto Company................... 7...........................
National Bureau Of Standards.................................. National Electrical Manufacturers Association....
Rollins-Purle, Inc................................................................................ Tennessee Valley Authority................................................................ U.S. Department of Agriculture, Rural Electrification Administration U.S. Department of the Army . . . . ................. .................................
Name ofRepresentative
Arnold S. Doty Kenneth J. Hood Charles C. Travis R. J. Schatz E. L. Rabb W. P. Papageorge P. G. Benignus (Alt) Stanley P. Wasik K. C. Chang W. S. Grogan R. D. McClain H. R. Rowe Ken McGee (Alt) H. A. Alsentzer William R. Nicholas John Leutritz, Jr D. M. Crabtree
(
|
i
i: I1 i: i
< e 'j
\ i
i
i
SW 357896
STLCOPCB4086624
9 Contents SECT,0N
PAGE
1. Scope.................................................................................................................................... 7
2. General Information.............................................................................................................. 2.1 General.......................................................................................................................... 2.2 Benefits.......................................................................................................................... 2.3 Risks. . . ........................................................................................ 2.4 Alternatives......................................................................... 2.5 Interdepartmental Task Force on PCBs.....................................................
7 7 7 7 8 8
3. Capacitor Guidelines..............
8
3.1 General.......................................................................................................................... 8
3.2 Capacitor-Grade Askarel.......... ..................................................................................... 9
3.3 Plant Housekeeping and Employee Safety .................................................................. 9
3.4 Control of Water Effluents.......... ............................................................................... 11
3.5 Scrap-Disposal Procedures....................................
12
3.6 Labeling...................... ..................... ........................................................................ - - 13
. 4. Transformer Guidelines.............................................. ....................................................... 13
4.1 General..........................
13
4.2 Specific Guidelines....................................
15
5. References . .. .......................................... ............................ ......................................
17
5.1 References to the Text.................................................................................................... 17
5.2 General References.........................................................................
17
6. Revision of American National Standards Referred to in This Document........................ 18
Table 1 Typical Properties of Aroclor 1016............................................................. .............. 9
Appendixes
Appendix A Disposal Services........................................................
19
Appendix B Analytical Procedures and Laboratory Service Organizations........................ 20
Bl. General........................................................................................................................20
B2. Laboratories.................................................................................................
20
B3. An Analytical Procedure for the Determination of Airborne PCBs...........................20
, B4. Analysis of Water and Sediment for PCBs.........................................
31
Figures
Fig. Bl Aroclor 1016 Electron Capture Chromatogram............................................ 21
Fig. B2 Comparison of Electron Capture Chromatograms for
Aroclor 1221, 1242, 1248, 1254, and 1260 .................................................... 22
Fig. B3 Aroclor 1221 Electron Capture Chromatogram........................
23
Fig. B4 Aroclor 1242 Electron Capture Chromatogram.................................................24
Fig. B5 Aroclor 1248 Electron Capture Chromatogram................................................. 25
. Fig. B6 Aroclor 1254 Electron Capture Chromatogram..................................... .'... 26
. - Fig. B7 Aroclor 1260 Electron Capture Chromatogram................................................. 27
Fig. B8 Sampling Train..............................................
28
Fig. B9 Calculating Column Efficiency......................................................................... 30
Fig. B10 Calculating the Tailing Factor............................................................................30
DSW 357897
STLCOPCB4086625
American National Standard Guidelines for Handling and Disposal of Capacitor- and Transformer-Grade Askareis Containing Polychlorinated Biphenyls
I. Scope
This standard establishes guidelines for the safe use, maintenance, and disposal of askarel and askarel-soaked material used in capacitors and transformers.
2. General Information
2.1 General. The term "askarel" generally describes a broad class of nonflammable synthetic chlorinated hydrocarbon insulating liquids widely used in capaci tors, transformers, reactors, and accessory equipment operated at power frequencies.
Askareis consisting of or containing polychlorinated biphenyls (PCBs) have been used in many applications for more than 40 years, but only recently was evidence discovered that PCBs are widely dispersed in the envi ronment. Systematic investigations of the biological effects of PCBs have been undertaken within the past few years to establish the effects of specific formula tions upon specific species. Some studies have shown that PCBs may be an environmental contaminant. Simultaneously, significant steps have been taken by U.S. industry to limit further releases of PCBs to the environment.
PCBs have been used in three broad types of applica tions for the past 40 years, as follows:
(1) "Open-ended" applications; for example, in paints, specialty inks, paper coatings, plastics, etc
(2) "Nominally closed" applications; for example, as the working fluid in hydraulic or heat-transfer sys tems
(3) "Closed electrical system" applications, specifi cally as the insulating fluid in certain kinds of trans formers and capacitors1 *
'Hie Monsanto Company is the sole U.S. producer of PCBs. It has discontinued supplying the material for all applications given in 2.1(1) and 2.1(2).
Evaluations of the benefits, risks, and alternatives involved in the continued use of PCBs in closed electri cal systems are summarized in 2.2 through 2.4.
2.2 Benefits. Askarel-filled transformers do not bum or sustain fire under conditions of internal electrical arcing.
Askarel-filled power and industrial capacitors are significantly smaller, more reliable, more durable, and safer than oil-filled capacitors. As a result, askareis have supplanted mineral oils in more than 90% of the power and industrial capacitors made today. Over the past few decades most of the equipment that incorporates such capacitors has been designed to take particular advan tage of the size, safety, and reliability benefits of askarel capacitors (for example, many types are today less than 14% of the size of equivalent oil capacitors and have a life expectancy of 10 to more than 20 years).
Various federal, state, and local codes, therefore, re quire their continued use in or adjacent to public, com mercial, and industrial buildings, which locations pre sent the greatest potential danger to life and property.
2.3 Risks. In the United States, medical records over a nearly 40-year period show that the only adverse health effects experienced by U.S. workers exposed to askareis, either during the manufacture of these liquids or of electrical equipment containing these liquids, have been limited to occasional cases of nonchronic chloracne or other temporary skin lesions or irritations.
Askarel-filled transformers and capacitors are de livered to customers as sealed units from which there is no escape of askarel under normal operation. Although certain types of equipment failures can permit loss of some askarel to the environment, transformer failures are limited to approximately 0.02% of the units in ser vice per year. With respect to capacitors, such losses are limited to approximately 0.02% of the askarel put into service per year. In addition, limited amounts of PCBs can get into the environment during the manufac ture, delivery, improper use, maintenance, repair, and disposal of transformers and capacitors.
7
DSW 357898
STLCOPCB4086626
AMERICAN NATIONAL STANDARD C 107.1-1974
Specific control measures have been instituted by individual manufacturers and are supplemented and strengthened by national standards and procedures such as this standard, which provides information to prevent the inadvertent loss of PCBs to the environ ment at all stages from initial askarel manufacture through ultimate disposal.
2.4 Alternatives. For technical and local and national code reasons, it would be impossible to replace most askarel-filled transformers now in service with oil-filled units of equivalent ratings without major construction changes that would be required to compensate for the fire resistance of the askarel-filled units. For certain applications and locations, dry-type transformers may replace askarel-filled transformers.
For new installations, although many of the fore going limitations would still apply, building and instal lation design provisions could be made to accommo date the use of oil-filled, open dry-type, or sealed drytype transformers, provided that necessary technical, code, physical size, and cost considerations are prop erly evaluated.
The principal alternative to askarels for capacitors is mineral oil, but such replacement would return capac itor technology to its pre-1932 level and would necessi tate the redesign and replacement of such widely used equipment as fluorescent light fixtures and racks for power and induction-heating capacitors, which could not now accommodate the increased size of oil capaci tors while maintaining their present ratings.
The cost of askarel liquids is about five to ten times more than mineral oil. Thus, long before there were any environmental concerns about PCBs, there was a strong economic incentive to find other, less expensive insulating liquids with the desirable characteristics of askarels. Since the 1930s at least ten major chemical or electrical companies have invested large amounts of time and money in this search, all with no success. Al though potential substitutes that are more costly than askarels (such as fluorinated liquids) have also received some consideration, little is known about either their electrical performance or possible ill effects upon the environment. There are today no fluids that can be used as a direct replacement for askarels.
2.5 Interdepartmental Task Force on PCBs. An in depth study of PCBs has recently been completed by five Executive Branch Departments of the federal gov ernment. This Interdepartmental Task Force on PCBs issued their report, entitled Polychlorinated Biphenyls and the Environment, in May 1972.2 The following1
1 Available from the National Technical Information Service, U.S. Department of Commerce, Springfield, Va 22151.
8
conclusion is quoted from page 4 of this report: "The use of PCBs should not be banned entirely.
Their continued use for transformers and capacitors in the near future is considered necessary because of the significantly increased risk of fire and explosion and the disruption of electrical service which would result from a ban on PCB use. Also, continued use of PCBs in transformers and capacitors presents a minimal risk of environmental contamination. The Monsanto Company, the sole domestic producer, has reported voluntarily eliminating its distribution of PCBs to all except manufacturers of electrical transformers and capacitors."
Reference should be made to the Interdepartmental Task Force Report for additional information and con clusions.
3. Capacitor Guidelines
3.1 General. The environmental effects of askarels are
under in-depth study by governmental and other agen
cies. Askarels have been considered relatively harmless
to humans based on about 40 years of safe industrial
usage. There has been no known instance of human in
jury when they were used under the normally accepted
precautions and conditions of handling in both manu
facturing and user applications.
Traces of askarels are being found in the environ
ment and in fish and bird life. The long-term genetic
and ecological effects are not yet completely under
stood. For these reasons, care should be taken to con
tain askarels and minimize their entry into the environ
ment.
There are two general classes of askarels used by the
electrical industry. The higher chlorinated grades are
the more persistent in nature. Because of their high de
gree of nonflammability, they are used in transformers
where personnel safety is of paramount importance.
Capacitor-grade askarel has a lower degree of chlori
nation (composed primarily of the 3-chlorine isomers
of biphenyl) and a higher degree of biodegradability.
Generally, it has not been found in animal life. It is
used in capacitors, where the extreme degree of non
flammability required in transformers is of less impor
tance.
Although capacitor- and transformer-grade askarels
both contain members of the PCB family, they do differ
in composition, degree of biodegradability, persistence
in nature, electrical stability, chemical stability, and
degree of nonflammability (both are recognized as non
flammable). It is for these reasons that Section 3 of this
standard is intended to apply to capacitor-grade askarel.
DSW 357899
).
1
f
|
\
i
1
STLCOPCB4086627
AMERICAN NATIONAL STANDARD C 107.1-1974
Table 1 Typical Properties of Aroclor 1016
Property
Color Condition Specific Gravity at 25/15.5C Acidity (mg KOH/g)
Moisture Refractive index at 25C Inorganic (free) chlorides
Pour point
'
Dielectric constant (1000 Hz at 100C)
Resistivity (500 V dc at 100C, 0,1-inch gap) Hydrolysis stability test (as chlorides) Thermal stability test (as chlorides)
Distillation range (corrected) 10% distilled by weight 90% distilled by weight
Higher-Boiling Homologues
Sulfates
Dielectric strength at 2SC
Flash point, Cleveland open cup
Fire point
Corrosion test (6 hours at 210C with bright aluminum foil), change in weight of aluminum
Viscosity at 100F (SUS)f Specific heat at 25C
'
Coefficient of expansion
Fixed chlorine
Power factor at 100C, 60 Hz Bulk Drums
Test Method (See Note) APHA*
ANSI C59.68-1965 (R1973) [2] ANSI Z11.131-1964 (R1974) [3] ANSI Z11.59-1958 (RI971) [4]
.ASTM D 1817-66 (1972) [5] ANSI C59.55-1963 (R1973) [6] ANSI Z11.5-1966 (R1972) [7] ANSI C59.22-1967 (R1973) [8] ANSI C59.51-1965 (R1973) [9] ANSI C59.106-1970 [10] ANSI C59.111-1970 [11] ANSI A37.9-1974 [12]
ASTM D 3303-74 [1] ANSI C59.2-1974 [13] ANSI C59.19-1968 (R1973) [14] ANSI Z11.6-1973 [15]
'-
ANSI Z11.2-1956 (R1971) [16] --
ANSI C59.57-1963 (R1973) [17] Carius Munch [18]
Typical Values 40, max Clear 1.362-1.372 0.010, max
35 ppm, max 1.6215-1.6235 0.05 ppm, max -14C or lower 4.70-4.90 500 X 10* n cm, min 0.5 ppm, max 0.4 ppm, max
323C, min 356C, max 0.4%, max None 35 kV, min 338F, min None to boiling point 0.0%
71-81 0.30 0.00068 cm3/cm/C 41.3 0.5%
1%, max 4%, max
NOTE: Numbers in brackets refer to correspondingly numbered test methods in 5.1, References to the Text. "American Public Health Association. tSaybolt Universal seconds.
3.2 Capacitor-Grade Askarel. In September 1971 a
maximum concentration acceptable in any capacitor
new grade of capacitor impregnant, Aroclor 1016, was
impregnant. Aroclor 1242 and 1254, previously used
made available to the industry. This new grade contains as impregnants, do not meet this requirement and
a typical concentration of 0.4% by weight of the higher should no longer be used in capacitors designed and
boiling homologues of the chlorinated biphenyls. (See
manufactured For alternating-current applications.
ASTM D 3303-74 [1] ,)3 Aroclor 1016 replaces Aroclor
Aroclor 1016 has the same Underwriters' Labora
1242, which previously was the major capacitor impreg tories, Inc, nonflammability rating as Aroclor 1242. Its
nant and contained around 7% of the higher-boiling
typical properties are given in Table 1.
homologues (the more persistent in nature). This 0.4% level of the higher-boiling homologues should be the1
3.3 Plant Housekeeping and Employee Safety. The procedures and limits given in 3.3 are intended to be
d minimum requirements to be met by manufacturers
1 Numbers in brackets refer to corresponding numbers in 5.1,
and users of capacitors containing askarel. Handling,
References to the Text.
control, and disposal procedures are given, together
DSW 357900
9
STLCOPCB4086628
jrtr>iW)
a,'} - "r
m\
i\
AMERICAN NATIONAL STANDARD C107.1-1974
with exposure limits and indicated antidotes and clean
up procedures.
3.3.1 Material. Askarel for use in capacitors should
consist of homologues and isomers of chlorinated bi
phenyl with the concentration of the higher-boiling
homologues at about 0.4%. (See ASTM D 3303-74 [1].)
Aroclor 1016 is considered to be the standard impreg-
nant meeting these requirements.
Commonly used solvents include benzene, kerosene,
acetone, trichloroethane, trichloroethylene, and perchlo-
roethylene. Typical vapor pressure data for Aroclor
1016 are:
0C = 0.001 mmHg
25C = 0.006 mmHg
.
150C = 4.3 mmHg
200C = 29.0 mmHg
At 25C and 760 mmHg pressure, saturated air con
tains approximately 0.09 mg/1.
NOTE: 1 mg/I = 90.0 ppm (v/v) I ppm (v/v) = 0.011 mg/1
3.3.2 Bulk Fluid Shipment, Receiving, and Transfer. Shipment of askarel from point of manufacture to point of receiving should be done in closed containers such as rail tank cars, truck tanks, marine or barge tanks, or sealed drums. Containers should be labeled as to con tents and carry a label cautioning against loss of fluid to the open environment. Containers used to transport askarel should not be used for storage or to transport other material without being completely cleaned of all traces of askarel. (Cleaning procedures must take cogni zance of precautions against excessive exposure and of the need for proper disposal of contaminated cleansing solvents and materials as set forth in 3.5). Transfer from shipping containers to processing systems should be through closed piping or tubing with appropriate valves, pumps, etc. Provision should be made for trap ping and disposing of fluid lost by leakage or spills from the transfer system and from the storage containers.
Drums to be retired from use should be cleaned be fore crushing, delivery to scrap dealers, or other dispo sal. Contaminated cleaning fluids and materials should be disposed of as indicated in 3.5.
3.3.3 General Safety Precautions. Although it is generally accepted that exposure to capacitor-grade askarel is not hazardous provided that simple precau tions are taken, exposure should still be avoided.
3.3.3.1 Vapors. The odor of askarel is noticeable well below the maximum air concentrations considered safe. Up to 1.0 milligram per cubic metre of air has been determined to be the maximum safe level of expo sure during an 8-hour workday. (See reference [19].) The procedure for performing the necessary analyses is10
10
contained in Section B3 of Appendix B. This procedure or its equivalent should be used.
Breathing vapor or fumes from heated askarel should be avoided. Provisions should be made for adequate ven tilation and regulation of manufacturing operations to avoid open exposure to askarel (especially at tempera tures of 55C or higher). The gases produced when aska rel is decomposed by very high temperatures (such as that of an electric arc) in the presence of air or organic insulating materials contain a high percentage of hydro gen chloride, and small percentages of carbon dioxide, carbon monoxide, and oxygen. Minute concentrations of this combination of gases are very unpleasant and ir ritating, thus giving ample warning of their presence. If exposure to high concentrations of askarel is necessary under emergency conditions, an approved gas mask or self-contained breathing apparatus should be worn. Such exposure should be under the surveillance of other personnel capable of effecting rescue in case of an accident. If the odor of askarel is detected by the person wearing protective equipment, he should imme diately go into fresh air. All gas masks, respirators, and replacement parts should have U.S. Bureau of Mines approval and be maintained on a regular schedule in accordance with the manufacturer's recommendation.
3.3.3.2 Liquid. In contrast to the situation in which mineral insulating oils are handled, there is vir tually no fire hazard in handling askarel. A limited sol vent action (similar to that for paint thinner) on the fats and oils of the skin with prolonged contact may lead to drying and chapping of the skin. As with insu lating oil, some people are allergic to askarel, and con tinued exposure may result in skin irritation. Both the liquid and vapor are moderately irritating to eye tissue.
Operating procedures should be such as to minimize or eliminate contact with askarels. Use of eye protec tion is recommended. The use of porous gloves that can absorb and retain askarels is to be avoided. Barrier creams4 or resistant glovess should be used if contact is unavoidable. Use of enclosed transfer and handling equipment, processing equipment, and mechanical washers reduces direct contact.
Medicinal washes or mild detergents followed by the application of cold cream will reduce the irritation re sulting from the contact of an open cut or abrasion with askarel.
Safety glasses with side shields or a face shield should be worn when handling askarels. If liquid aska- * *
4 For example, PI.Y No. 9 Gel (Milburn Company, Detroit, Mich), or Kerodex No. 71 (Ayerst Laboratories, New York, N.Y.), or the equivalent.
* For example, Edmont -- Solvit 5-352 (Mersick of Bridgeport, Bridgeport, Conn), or the equivalent.
DSW 357901
f.
ir> fa t
t
t V i,
?t S:
ii I J
- ?* \*
j
STLCOPCB4086629
mm
mi
AMERICAN NATIONAL STANDARD C 107.1-1974
rel contacts the eyes, the eyes should be irrigated imme other filters
diately with large quantities of running water for 15
(6) Saturated wastes (paper, rags, etc)
minutes and then examined by a physician. (A drop of
(7) Saturated, spent gasket materials
castor oil has been found to reduce irritation.)
(8) Askarel-contaminated vacuum pump oils
Persons developing a skin irritation or respiratory
(9) Askarel-contaminated stream jet vacuum system
tract irritation while working with askarels should be
condensates
placed under the supervision of a physician.
3.3.6 Miscellaneous Procedures. Other safety con
Ingestion or swallowing of askarels is not generally
siderations include the following:
regarded as a problem of the industry. Should acciden
(1) Spills by leakage from finished capacitors should
tal ingestion occur, a physician should be consulted.
be cleaned up promptly by means of absorbent media,
Hands should be washed with warm water and soap be
which should then be moved to containers provided for
fore eating, drinking, smoking, or using toilet facilities.
that purpose within the containment area, and later dis
3.3.4 Manufacturing Housekeeping. Manufacturing
posed of properly.
equipment and operating procedures should safeguard
(2) Askarel wastes should never be disposed of
against loss of askarels to the environment through
down effluent drains or sewers. The utmost care must
proper containment and disposal procedures.
be exercised to prevent accidental loss by these avenues
Enclosed systems of sealed piping, properly gasketed to the environment.
joints, valves, containers, and processing chambers
(3) Capacitors failing tests or otherwise designated
should be used for any portion of the operation where
for disposal must be controlled and handled in accor
askarel temperatures may exceed 55C. Enclosure
dance with the intent of the procedures given in
should preferably extend to all other portions of the
3.3.6(1) and 3.3.6(2), finally being disposed of by one
system insofar as practicable.
of the means outlined in 3.5.
Containment provisions should be established around
all askarel processing areas to ensure against inadvertent 3.4 Control of Water Effluents. The industry goal is to
loss to sewer systems by spillage, leakage, or other un
eliminate askarel in plant water effluent streams. How
controlled conditions or events.
ever, it is recognized that existing drain systems in
Spills of askarel should be removed promptly by
capacitor manufacturing plants are probably contami
means of absorptive material, such as sawdust, or
nated as a result of past practices, and askarel traces
trapped and removed by pumping or other suitable
may continue to show up in effluent streams for some
means.
time. However, the level should continue to decrease
Waste fluids containing askarel not suitable for recon with the proper containment of askarel wastes and no
ditioning or reuse should be collected (by means of
further discharges into drain systems. Other sections of
traps, drip pans, trays, etc) from the various parts of
this standard provide that no askarel wastes of any kind
the manufacturing and processing area (including
be disposed of in any water effluent streams and that
washers or other cleaning devices). Disposal should be
accidental spills be prevented from getting into such
made in accordance with 3.5.
streams.
Wiper rags, clothing, and other extraneous materials
3.4.1 Concentration Limits. The 1972 Environmen
saturated with askarels should be collected within the
tal Protection Agency proposals are to keep PCB levels
containment area for properly controlled laundering or
in rivers and lakes below 0.01 part per billion. This is
disposal (see 3.5).
currently under review by the EPA and standards are
3.3.5 Disposal of Askarel Wastes. Methods for dis
expected to be promulgated in 1974. Plant effluent
posal of liquids and saturated solids generated by the
streams should be managed and controlled in a manner
manufacturing operation should be in accordance with
anticipating these government standards.
those outlined in 3.5, and should include (but not be
3.4.2 Monitoring Streams. On a regular basis con
limited to) the following wastes:
sistent with plant situations, all effluent streams should
(1) Contaminated liquid askarel that is unsuitable
be analyzed. The procedure for performing the neces
for reclaiming as a dielectric fluid
sary analyses is contained in Section B4 of Appendix B.
(2) Liquid askarel from solvent operations or water
This procedure or its equivalent should be used.
and detergent type washers
3.4.3 Methods for Minimizing Effluent Stream Con
(3) Saturated earth or other absorbent media from
tamination. The ideal approach is to isolate totally all
filtering operations
effluent streams that could be contaminated with aska
(4) Saturated sawdust or other absorptive materials
rels during manufacturing processes and prevent them
from spills
from being discharged from the plant. Carbon adsorp
(5) Saturated filters from vapor-control devices and
tion, limestone beds, and solvent extraction are tech
.
DSW 357902
,,
STLCOPCB4086630
AMERICAN NATIONAL STANDARD C107.1-1974
niques that can be applied to reduce the askarel content of effluent streams. These techniques may be most use ful in cleaning up water used in plant processing and to permit recycling.
3.5 Scrap-Disposal Procedures. The manufacture and use of capacitors involve processes that produce askarelsaturated solids and liquids containing or composed en tirely of askarel, which should be disposed of as wastes. Specific sources of these materials are described through out this standard. They may be placed into three cate gories:
(1) Capacitor units impregnated with askarel, pro duction and field rejects
(2) Manufacturing process liquid wastes containing askarel
(3) Solid waste purposely or accidently saturated with askarel
Disposal should be done in a manner that is consis tent with proper concern for the environment and minimizes any release of askarels to the environment.
3.5.1 Disposal of Capacitor Units. Scrap capacitor units can be generated during manufacturing processes or during field service.
Production rejects are those capacitors that are re jected after the impregnation process in the course of production by the capacitor manufacturer. They may be rejected for mechanical or electrical reasons, or be cause of obsolescence.
Field rejects are those units that are rejected or, for other reasons, are to be scrapped after shipment from the plant where they were manufactured.
3.5.1.1 Production Rejects. Rejected capacitors in capacitor manufacturing plants represent a concen tration of askarel. It is important that their disposition be made in a manner consistent with proper concern for the environment. Therefore, capacitors should be disposed of only in supervised dry landfill sites that meet all applicable state requirements.
Care should be exercised to ensure that no loss of liquid will occur during transportation to the disposal site.
Incineration of scrap capacitors in facilities designed to accept such solids should provide an alternative means of disposal as such services become available in the future.
3.5.1.2 Field Rejects. Small capacitors (defined as containing less than 2 pounds of askarel) are practi cally always used as components in other electrical or electromechanical equipment. Typical examples of large quantity usage of such capacitors are in fluores cent lamp ballasts and residential air conditioning equip ment. Failure of such capacitors may result in scrap- ' ping of the device of which it is a part (as in a fluores
cent ballast) or replacement and scrapping of the indi
vidual capacitor (as in a room air conditioner). How
ever, the majority of such capacitors do not fail in
service, but are scrapped as a result of wearing out or
obsolescence of the devices in which the capacitors are
used as components. Thus, the matter of disposal is
characterized by a low concentration of small quantities
of askarel throughout the country and, indeed, through
out the world. Fortunately, the nature of the devices
and equipment in which such capacitors are used is
such that they are normally disposed of in dry landfills
as a matter of convenience. Since it is impractical at
present to exercise any meaningful control over the dis
position of the bulk of such devices and equipment, it
is imperative that askarel used for impregnating small
capacitors be limited to the recently introduced type,
which contains a typical concentration of 0.4% of the
higher-boiling homologues. (See ASTM D 3303-74 [ 1 ].)
Large capacitors (those incorporating more than 2
pounds of askarel) should be disposed of according to
the procedure for production rejects (see 3.5.1.1).
3.5.2 Disposal of Liquid Wastes. All waste askarel
or liquid wastes containing askarel should be disposed
of in accordance with one of the procedures given in
3.5.2.1 through 3.5.2.3.
3.5.2.1 Incineration. Present knowledge indicates
that proper incineration must involve a suitable balance
between dwell time and temperature in the incinerator
plus oxygen availability and, finally, suitable scrubbers
to remove the HC1 that will be formed; for example,
2-second dwell time at 2000F and 3% excess oxygen
in stack gas, or 1.5-second dwell time at 2700F and
2% excess oxygen in stack gas.
These facilities should meet the applicable require
ments of the state in which they are located, and
should control effluents within the limits set forth in
this standard.
3.5.2.2 Toxic and Hazardous Waste Disposal
Sites. Certain landfill sites have been classified by state
governments and the federal government as suitable for
the disposal of toxic and hazardous liquids. Where such
approved sites exist, they may be used for the disposal
of liquid wastes described in this standard. (See Appen
dix A.)
3.5.2.3 Packaging and Shipment
3.5.2.3.1 Transportation to the disposal facili
ty should be in containers that will prevent leakage and
accidental loss of askarel to the environment.
.
3.5.2.3.2 Containers should be labeled as to
contents and precautions relative to loss to the environ-
ment.
3.5.2.3.3 Containers used for this purpose
should not be used for any such materials or retired
from service until they are completely cleaned. Any
12
2 gj $ g
{
t I; ! 1: ?1 1^
I`
.
e* i1
M
STLCOPCB4086631
. \ ; .#,1
<10 C Q
AMERICAN NATIONAL STANDARD C107.I-1974
solvents used in cleaning these containers will be conlaminated with askarel and should be disposed of ac cording to the same procedures described in 3.5.2.
3.5.3 Disposal of Solid Wastes. (See 3.5.1 for scrap capacitors.) All solid wastes that have been saturated with askarel should be disposed of by the following procedure:
(1) The saturated wastes should be placed into leakproof containers and transported to a supervised dry landfill site meeting state requirements. Alterna tively, they can be disposed of by incineration in state-approved facilities.
(2) Solid absorbents used for spills can be disposed of uncontained in the supervised dry landfill site; trans port to the site should be in closed containers. Alterna tively, incineration can be used in accordance with 3.5.2. (See Appendix A for a listing of facilities.)
3.6'Labeling. Capacitor units vary greatly in size and in end use or application. Small capacitor units are fre-
qii'eiitly applied as a component of another piece of Equipment, such as a fluorescent lighting ballast, a road
way or area lighting luminaire, a motor, etc. In such
applications a label on the capacitor unit referencing
approved disposal procedure would not normally be
visible when the piece of equipment is disposed of.
For the foregoing reasons the methods of providing
'disposal instructions for small capacitors and large ca
pacitors are treated separately in 3.6.1 and 3.6.2,
respectively.
^"'3.6.1 Small Units. Small capacitors are defined as W5se that contain askarel in quantities up to about 2
podrfds each and in which the free liquid does not ex-
0.4pound. They are hermetically sealed in metal-
fiBucases: Such capacitors are applied as a component
pftl large piece of equipment. Attaching a label to such
`iqdipmeht referencing this standard or describing dis-
poSal'procedures would be of limited practical value.
Large Units. Large capacitor units are defined
S\horse that contain more than 2 pounds of askarel.
nit:'Capacitor manufacturer should affix a label in a
cohspicuous place, referencing this standard or de
Scribing disposal procedures consistent with it. This
should contain, as a minimum, the following inforrfiration:" laDCAUT10N: This capacitor contains a polychlori
nated biphenyl (PCB). To avoid possible environmental
contamination, it should be disposed of only in super
vised dry landfill areas meeting state requirements or in
Incineration facilities designed for disposal of PCBs.
'See"American National Standard C107.1 -1974 for fur
ther Information. Copies are available from American ^itiSnal Standards Institute, 1430 Broadway, New
H>Ork:(N.Y. 10018.
Nsiior.-.
.
`Sort.. N.% , .
4. Transformer Guidelines
4.1 General 4.1.1 Types of Transformer Askarels.6 Askarels of
various compositional types are currently in use (for the general properties and types, see ASTM D 228373a [20]). Under arcing conditions, the gases produced, though predominantly consisting of noncombustible hydrogen chloride, can contain varying amounts of combustible gases depending upon the askarel type.
4.1.2 Safety Precautions. Based on about 40 years of safe industrial usage, askarels have been considered as relatively harmless materials to humans. There has been no known instance of human injury when askarels are used under the normally prescribed conditions of precaution and handling.
Although it has been generally thought that expo sure to askarels is not hazardous provided that simple precautions are taken, exposure should still be avoided or minimized.
4.1.2.1 Vapors. The odor of askarel is noticeable well below the maximum safe air concentrations. De pending upon the composition of the askarel used, from 0.5 to 1.0 milligram per cubic metre of air has been determined to be the upper safe level of expo sure during an 8-hour workday. (See reference [19].) The procedure for performing the necessary analyses is contained in Section B3 of Appendix B. This proce dure or its equivalent should be used.
Breathing vapor or fumes from heated askarels should be avoided. High concentrations of vapors can cause irritation of the eyes, nose, throat, and upper re spiratory tract. Provisions shall be made for adequate ventilation and regulation of manufacturing operations to avoid open exposure of hot askarels (55C or higher). The gases produced when askarel is decomposed by very high temperatures (such as that of an electric arc) in the presence of air or organic insulating materials contain a high percentage of hydrogen chloride, and small percentages of other gases. Minute concentrations of this combination of gases are very unpleasant and irritating, thus giving ample warning of their presence. If exposure to high concentrations of askarels or its arced products is necessary under emergency conditions, an approved gas mask of the organic canister type, or self-contained breathing apparatus, must be worn. Such exposure should be under the surveillance of other per sonnel capable of effecting rescue in case of accident. If the odor of askarel or its arced products is detected
`The following trademarks are among those employed by elec trical manufacturers to designate the askarels used in their products: Asbestol.Chlorextol, Inerteen, No-Hamol, Pyranol, and Saf-T-Kuhl.
DSW 357904
STLCOPCB4086632
AMERICAN NATIONAL STANDARD C107.1-1974
by the person wearing protective equipment, he should immediately go into fresh air. All gas masks, respirators, and replacement parts should have U.S. Bureau of Mines approval and be maintained on a regular schedule in ac cordance with the manufacturer's recommendation.
4.1.2.2 Liquid. In contrast to the situation in which mineral insulating oils are handled, there is no fire hazard in handling askarels. A limited solvent ac tion (similar to that for paint thinner) on the fats and oils of the skin with prolonged contact may lead to dry ing and chapping of the skin. As with insulating oil, some people are allergic to askarel, and continued expo sure may result in skin irritation. Both the liquid and vapor are moderately irritating to eye tissue.
Operating procedures should require avoidance of contact with any askarels. The use of porous gloves that can absorb and retain askarels is to be avoided. Re sistant gloves and aprons of the neoprene, polyethylene, or fluoroelastomer' type should be used if contact is unavoidable. In case of spillage on the clothing, the clothing should be removed as soon as practical, the skin washed, and the clothing laundered.
Medicinal washes or mild detergents followed by the application of cold cream will reduce the irritation re sulting from the contact of an open cut or abrasion with askarel.
Safety glasses with side shields or a face shield should be worn when handling askarels. Eyes that have been exposed to liquid askarel should be irrigated immediately with large quantities of running water for 15 minutes and then examined by a physician if the irritation persists. (A drop of castor oil has been found to reduce irritation.)
Persons developing a skin irritation or respiratory tract irritation while working with askarels should be placed under the supervision of a physician.
Ingestion or swallowing of askarels is not generally regarded as a problem of the industry. Should acciden tal ingestion occur, a physician should be consulted. Hands should be washed with warm water and soap before eating, drinking, smoking, or using toilet facili ties. '
4.1.3 Transport Container Marking. Any container, such as tank cars, tank trucks, drums, cans, etc, used to transport transformer askarels, new or used, should be labeled with the following:
CAUTION: This product contains polychlorinated biphenyls (PCBs). Care should be taken to prevent entry into the environment through spills, leakage, use, vaporization, or disposal of liquid or containers. Avoid prolonged breathing of vapors or mists. Avoid contact with eyes or prolonged contact with skin. If skin con-* 14
7 For example, Viton.
14
tact occurs, remove by washing with soap and water.
Following eye contact, flush with water. In case of
spillage onto clothing, the clothing should be removed
as soon as practical, skin washed, and clothing laun
dered.
4.1.4 Receiving, Handling, and Storage of Askarels.
Askarels are shipped in tank cars, tank trucks, steel
drums, metal cans, and test-sample containers. When
received, all containers should be inspected for leaks.
4.1.4.1 Storage Tanks. Storage tanks should be
erected so that inspection can be made for leaks or
spills. Construction should be such that inadvertent
leakage or spills are prevented from reaching streams
and sanitary or storm sewers.
4.1.4.2 Tank Cars and Tank Trucks. All bulk
shipment equipment should be inspected for leaks im
mediately upon receipt. Drain pans must be provided
to prevent spillage from unloading hoses and connec
tions. Askarel liquid collected in drain pans should be
placed in drums labeled "SCRAP ASKAREL" for dis
position.
4.1.4.3 Steel Drums, Cans, and Test-Sample Con
tainers. On delivery, all such shipments should be care
fully inspected for leaks. The containers should be
stored indoors in an area especially selected for this
purpose. A curb should enclose the area to provide a
basin for containing the askarel from one or more con
tainers should the containers be damaged. The area
must not have a drain that is connected to a sanitary
or storm sewer.
If an indoor storage area is not possible, the con
tainers should be stored under a lean-to.
.
4.1.5 Control of Water Effluents. The industry goal
is to eliminate askarel in plant water effluent streams.
However, it is recognized that existing drain systems
from manufacturing plants, repair shops, and installa
tion sites may be contaminated as a result of past prac
tices. Other sections of this standard provide that no
askarel wastes of any kind be disposed of in any water
effluent streams and that accidental spills be prevented
from getting into such streams.
4.1.5.1 Concentration Limits. The 1972 Environ
mental Protection Agency proposals are to keep PCB
levels in rivers and lakes below 0.01 part per billion.
This is currently under review by the EPA and stan
dards are expected to be promulgated in 1974. Plant
effluent streams should be managed and controlled in
a manner anticipating these government standards.
4.1.5.2 Monitoring Streams. All plant effluent
streams should be monitored on a regular basis, consis
tent with plant situations. The procedure for perform
ing the necessary analyses is contained in Section B4
of Appendix B. This procedure or its equivalent should
be used.
DSW 357905
(
ti iI t \I I)
mViimii iH-11
STLCOPCB4086633
finrAihi
--------V-'h-
AMERICAN NATIONAL STANDARD 007.1-1974
4.1.5.3 Methods for Minimizing Effluent Stream Contamination. The ideal approach is to isolate totally all effluent streams that could be contaminated with askarels during manufacturing processes and prevent them from being discharged from the plant.
4.1.6 Disposal Procedures and Services 4.1.6.1 Sources of Materials Requiring Special
Handling and Disposal Procedures. Liquids containing PCBs and solids containing or contaminated with PCBs may be obtained from any of the following sources: transport containers, transformer manufacturing pro cesses, in-test failures, liquids contaminated beyond reclamation, in-service transformer leaks and failures, askarel-filled transformers scrapped for any reason, etd.
4.1.6.2 Classification for Disposal of Materials Containing PCBs. In general, there are three types of materials requiring disposal: liquids, burnable solid materials containing PCBs, and nonburnable solid mate rials contaminated with PCBs.
4.1.6.2.1 Liquids. Liquids containing PCBs requiring disposal by high-temperature incineration may consist of the following:
(1) PCBs contaminated with mineral oil. (2) Mineral oil contaminated with PCBs. (3) Nonreclaimable contaminated transformer askatels, arced askarels, askarels from manufacturing spills, Snd sump accumulation, etc, rich in PCBs, and askarels from holding basins, drip and drain pans, washings, sam ple jars and containers, etc.
4.1.6.2.2 Burnable Solid Waste Materials Con taining PCBs. These materials can be disposed of by hightemperature incineration and consist of cellulosic mateBdls, rags, pressboard, wood, sawdust, fuller's earth in Btilk or in cloth bags, blotter papers, nitrile or cork gas kets, etc.
4.1.6.2.3 Nonburnable Solid Waste Materials fe&htaining, or Contaminated with, PCBs. These mateHals may consist of coil structures, steel, copper, alufninum filter units of the steel mesh construction type, l^karel drums, cans, etc.
Materials of this nature should be allowed to drain Mth the liquid collected in drip pans, etc. Further refnoval of adhering PCBs can be accomplished by wash ing or solvent extraction with kerosene or other ap proved washing liquids such as perchloroethylene or iricholoroethylene. Accumulated liquids can be dis posed of as indicated in 4.1.6.2.1. Solid materials may Be handled as normal scrap.
4.1.6.3 Shipment of Scrap Liquids for Disposal. All liquid scrap material should be placed in appropriate 'metal transport drums, properly labeled, for shipment
"a company offering an acceptable disposal service. 4.1.6.4 Shipment of Burnable Solid Waste Mate-
'Containing PCBs for Disposal. Material of this type
should be placed in open-head drums with suitable clo sures and with the drum properly labeled for shipment to a company offering an acceptable disposal service.
4.1.6.5 Liquid and Solid Waste Disposal Service Organizations
4.1.6.5.1 General. Disposal of askarels and askarel-soaked materials should be accomplished by means in which there is no significant release of askarel to the environment. At present, disposal is accomplished by carefully controlled incineration of liquids and soaked software, and by controlled landfill burial of apparatus and other hardware from which askarel has been previously drained and washed.
Present knowledge indicates that proper incineration must involve a suitable balance between dwell time and temperature in the incineration plus oxygen availability and, finally, suitable scrubbers to.remove the HC1 that will be formed; for example, 2-second dwell time at 2000F and 3% excess oxygen in stack gas, or 1.5second dwell time at 2700F and 2% oxygen in stack gas.
These facilities should meet the applicable require ments of the state in which they are located and should control effluents within the limits set forth in this stan dard.
Controlled landfill or deep-well disposal can be used where permitted by federal, state, and local regulations.
4.1.6.5.2 Costs. In addition to the normal costs of collecting scrap liquids and solids for disposal, additional costs borne by the owner of such scrap in clude shipping containers, cost of transport to the dis posal service organization, and a disposal fee usually based upon a per-gallon or per-pound charge.
4.1.6.5.3 Disposal Services. Organizations offering disposal services are listed in Appendix A, including their location, facilities available, types of material handled, and disposal procedures used. Speci fic shipping directions, disposal procedures, and costs should be obtained from the organization.
4.2 Specific Guidelines 4.2.1 Plant Housekeeping. It is necessary to assume
that in filling equipment with askarel, and during fur ther handling of this equipment, an askarel spill may occur. Therefore, it is necessary to provide facilities and a procedure for cleanup to prevent contamination.
4.2.1.1 Askarel Filling Area 4.2.1.1.1 The location of the askarel filling
area should be adjacent to the test area and final ship ping area to minimize the danger of damage of units during handling.
4.2.1.1.2 The main manufacturing area for filling equipment with askarel should be provided with impervious surface floors or suitable basins so con-
DSW 357906
15
STLCOPCB4086634
l
AMERICAN NATIONAL STANDARD C107.1-1974
structed that any inadvertent leakage or spills are pre vented from reaching streams, sanitary sewers, or storm sewers. All askarel-handling equipment, such as pumps, hoses, etc, shall be of the askarel-resistant type.
4.2.1.1.3 Drip pans shall be provided for hose connections and filling valves.
4.2.1.2 Special Containers for Scrap Materials 4.2.1.2.1 Drums labeled "SCRAP ASKAREL"
should be available for handling all spilled and waste askarel from sumps, failed units, drip pans, sample jars, etc.
4.2.1.2.2 Open-head drums with suitable clo sures and labeled "SCRAP BURNABLE ASKAREL WASTE" should be available for handling contaminated cellulose insulation, rags, paper pressboard, wood, gas kets, sawdust, etc.
4.2.1.2.3 Separate containers for handling steel, copper, and aluminum, each adequately marked, shall be provided for the components of contaminated core and coil assemblies. These containers are required for the various materials when repairing or scrapping assemblies.
4.2.1.2.4 Containers for supplies of material for absorbing small askarel spills or cleanup of larger spills should be provided.
4.2.1.3 Conditioning of Askarels 4.2.1.3.1 Askarel Conditioning Equipment.
Hie conditioning unit should be located either in the storage tank area or in the main transformer manufac turing area for filling with askarel.
4.2.13.2 Fuller's Earth. Conditioning of new askarel or recycled askarel requires fuller's earth treat ment. The spent fuller's earth in cartridges or bags, when replaced, should be allowed to drain thoroughly over drip pans to remove as much liquid askarel as pos sible. The cartridge units of steel mesh construction should be placed in the "STEEL CONTAMINATED WITH ASKAREL" container for disposition. Cloth bags filled with fuller's earth should be placed in the "SCRAP BURNABLE ASKAREL WASTE" container for disposition.
4.2.1.4 Teardown of Units for Repair or Scrap 4.2.1.4.1 Drain all askarel from the unit either
into a holding tank for reuse or into the drum labeled "SCRAP ASKAREL" for disposition, and then allow sufficient time for all of the askarel to drain from the core and coils.
4.2.1.4.2 Remove the core and coil assembly from the transformer. Sufficient absorbent material should be placed on the floor to absorb any askarel fluid that still drips from the transformer.
4.2.1.4.3 Place all materials in the appropriate calvage containers during the dismantling for later dis position.
16
4.2.1.4.4 All used materials, including rags, sawdust, tape, etc, regardless of quantity, shall be put into the appropriate containers for disposition.
4.2.2 Transformer Labeling 4.2.2.1 New Transformers. All new transformers
that contain PCBs shall have a label of adequate durabil ity, permanently and prominently attached to the tank by the manufacturer, giving adequate warning and in structions. A suggested label includes the following:
CAUTION: The insulating liquid in this transformer contains polychlorinated biphenyls (PCBs). Care should be taken to prevent entry into the environment. In case of malfunction or leaks, consult the instruction manual or the manufacturer.
4.2.2.2 In-Service Transformers. The transformer manufacturer should make available suitable labels with a similar warning as shown in 4.2.2.1 for use on exist ing transformers.
4.2.3 Information for Transformer Users 4.2.3,1 General. Askarel-filled transformers are
delivered to customers as sealed units from which there is no escape of askarel under normal operation. Although certain types of equipment failures can permit loss of some askarel to the environment, such cases are extreme ly rare.
4.23.2 Transportation and Receiving. Immedi ately upon receipt of the equipment and following any transportation or handling accident that could affect the integrity of the tank, bushings, or radiators, the transportation vehicle, tank, and fittings should be examined for any leakage or spillage that may have occurred in shipping. If leakage is evident, the cause should be corrected and the spillage soaked up with absorbent materials such as sawdust, followed by a cleanup of the affected area with rags soaked with kero sene or other approved solvent such as perchloroethylene or trichloroethylene. All materials used should be collected for proper disposition as described in 4.1.6.
4.2.33 Installation and Periodic Inspection. Fol lowing installation, the unit should again be inspected for any damage or leakage. It is recommended that periodic in-rservice inspections be made for any leaks.
4.23.4 Filling, Filtering, or Drying Askarel. Most askarel units are shipped with the proper amount of askarel, but if it becomes necessary to top off a unit, the manufacturer's instructions should be followed.
If it is necessary to dry an askarel unit or to treat an askarel unit with fuller's earth, instructions should be followed. When filtering or conditioning askarel, all of the precautions previously described for drip pans, proper disposal of filter media, etc, apply.
4.23.5 Sampling. It is common practice to sampie askarel from a transformer for periodic maintenance testing. As previously described, such samples should be
DSW 357907
(
f
j
'ir . t
L .` i! ;;
iI
STLCOPCB4086635
M'
AMERICAN NATIONAL STANDARD C107.1-1974
I taken in a manner to avoid any contamination of the
Specific Resistance (Resistivity) of Electrical Insulating
environment. Washings should be collected for proper
Liquids, C59.51-1965 (R1973) (ASTM D 1169-64
disposal. Field and laboratory test samples, washings,
(1973))
etc, should also be collected for proper disposal. 4.2.3.6 Transformer Disposal. The ultimate dis
posal of an askarel-filled transformer may be accom plished in either of two ways:
(1) Complete drainage and dismantling with the
[10] American National Standard Method of Test for Hydrolyzable Chlorine Compounds in Chlorinated Aro matic Hydrocarbons (Askarels), C59.106-1970 (ASTM D 1820-65 (1971))
proper disposal of the askarel and askarel-soaked com
[HI American National Standard Method of Test for
ponents as described in 4.1.6.
Thermal Stability of Chlorinated Aromatic Hydrocar
(2) Disposition of askarel transformers by means of
bons (Askarels), C59.111-1970 (ASTM D 1936-64
junk or scrap dealers. This should be avoided unless a
(1971))
transformer is first drained, followed by soaking the interior with a suitable solvent. Accumulated liquids and washings are to be disposed of as described in 4.1.6.
[12] American National Standard Method of Test for Distillation of Road Tars, A37.9-1974 (ASTM D20-72)
[13] American National Standard Methods of Testing
Electrical Insulating Oils, C59.2-1974 (ASTM D 117-71
(1973))
5. References
[14] American National Standard Method of Test for
Dielectric Breakdown Voltage of Insulating Liquids
5.1 References to the Text
Using Disk Electrodes, C59.19-1968 (R1973) (ASTM
tH Standard Method of Test for Rapid Gas Chroma
D 877-67 (1971))
tographic Estimation of Higher Boiling Homologues of
[15] American National Standard Method of Test for
Chlorinated Biphenyls for Capacitor Askarels, ASTM
Rash and Fire Points by Cleveland Open Cup, Z11.6-
D 3303-74
1973 (ASTM D 92-72, IP 36/67)
[2] American National Standard Method of Test for
[ 16] American National Standard Method of Test for
Specific Gravity of Askarels, C59.68-1965 (R1973)
Saybolt Viscosity, Z11.2-1956 (R1971) (ASTM D 88-
(ASTM D 1810-63 (1973))
56(1973))
[31 American National Standard Method of Test for Neutralization Number by Color-Indicator Titration, Z11.131-1964 (R1974) (ASTM D 974-64 (1973), IP 139/65)
[17] American National Standard Method of Test for Coefficient of Thermal Expansion of Electrical. Insu lating Liquids of Petroleum Origin, and Askarels, C59.57-1963 (R1973) (ASTM D 1903-63 (1973))
[41 American National Standard Method of Test for Neutralization Number by Potentiometric Titration, Z11.59-1958 (RI971) (ASTM D 664-58 (1968), IP 177/64)
[51 Standard Method of Test for Density of Rubber Chemicals, ASTM D 1817-66 (1972)
[18] MUNCH, R. H. Measuring the dissipation factor, dielectric constant, and resistivity of liquids. Insulation/ Grcuits, vol 16, Mar 1970, pp 46-49.
[191 Chlorodiphenyls. Hygienic Guide Series. West mont, N.J.: American Industrial Hygiene Association, Jan-Feb 1965.
[61 American National Standard Method of Test for Inorganic Chlorides in Askarels, C59.55-1963 (R1973) (ASTM D 1821-63 (1973))
[20] Standard Specification for Chlorinated Aromatic Hydrocarbons (Askarels) for Transformers, ASTM D 2283-73a
[71 American National Standard Method of Test for
5.2Genera] References
Pour Point of Petroleum Oils, Z11.5-1966 (R1972) (ASTM D 97-66 (1971), IP 15/67)
Aroclor Polychlorinated Polyphenyls (Biphenyls), Technical Bulletin O-FF/IR. St. Louis: Monsanto In
[81 American National Standard Method of Test for
dustrial Chemicals Company, Nov 1971.
Power Factor and Dielectric Constant of Electrical
0 Insulating Liquids, C59.22-1967 (R1973) (ASTM D 924-65 (1973))
DRINKER, C. K. Further observations on the possible systemic toxicity of certain of the chlorinated hydro carbons. Journal ofIndustrial Hygiene and Toxicology,
PI American National Standard Method of Test for
vol 21, 1939, pp 155-159.
DSW 357908
17
STLCOPCB4086636
AMERICAN NATIONAL STANDARD 007.1-1974
DRINKER, C. K.; WARREN, M. F.; and BENNET, G. A. The problem of possible systemic effects from certain chlorinated hydrocarbons. Journal ofIndustrial Hygiene and Toxicology, vol 19, 1937, pp 283-311.
ELKINS, H. B. The Chemistry ofIndustrial Toxicology. New York: John Wiley & Sons, Inc, 1959.
GREENBURG, L.; MAYERS, M. R.; and SMITH, A. R. The systemic effects resulting from exposure to certain chlorinated hydrocarbons. Journal of Industrial Hygiene and Toxicology, vol 21, 1939, pp 29-38.
Threshold Limit Values for Chemical Substances and Physical Agents in the Workroom Environment. Cincin nati: American Conference of Governmental Industrial
Hygienists, 1973.
TREON, J. F.; CLEVELAND, F. P.; CAPPEL, J.; and ATCHLEY, R. W. The toxicity of the vapors of Aroclor 1242 and Aroclor 1254. American Industrial Hygiene Association Quarterly, vol 17,1956, pp 204-213.
6. Revision of American National Standards Referred to in This Document
When the American National Standards referred to in
this document are superseded by a revision approved by
the American National Standards Institute, Inc, the re
vision shall apply.
,
\i 1\ 1I
<5
i$ ( \
DSW 357909 I
STLCOPCB4086637
> m.J a**
A nnanrl lYOC (These Appendixes are not a part of American National Standard Guidelines for Handling and Disposal of
MPP wllU IavO Capacitor- and Transformer-Grade Askarels Containing Polychlorinated Biphenyls, C107.1-1974, but are
included for information purposes only.)
Appendix A Disposal Services
In addition to the supervised dry landfill sitgg that may be used for the disposal of askarel-containing scrap, the following additional known facilities and services have been established, and others may be available.*
Chem-Trol Pollution Services, Inc P.O. Box 200 1550 Balmer Road Model City, N.Y. 14107 Phone: 716 754-8231
,
This organization has facilities and services capable of handling:
(1) Liquids. Askarels .alone or mixed with solvents or oils. I&posal by.high-temperature.incineration-
(2) Solids (software). Askarel-soaked compounds, rags cartons, absorbing earths, etc. Disposal by incinera tion or scientific landfill.
(3) Solids (hardware). Capacitors, transformer tanks, cores, askarel-soaked metals. Disposal by scientific land fill. Has solvent extraction capability.
Monsanto Company 800 North Lindbergh Boulievard
St. Louis, Mo 63166 Phone:314 694-3352
.
This organization has facilities and services capable of handling askarel liquids alone or mixed with other oils or solvents by high-temperature incineration. Liquid is pumped through a gun with atomizing steam into incinerator. Temperatures are maintained at 2000F2500F with auxiliary natural gas. Exit gases are quenched to 180F by .contact with water. Gas is then passed through a high-energy venturi scrubber for re moval of particulates. Before exhausting to air (110F),
gases are passed through a packed column scrubber to remove HC1.
Nuclear Engineering Company Eastern Division P.O. Box 146 Morehead, Ky 40351 Phone: 606 784-6611
Nuclear Engineering Company Disposal Division Sheffield, 111.61361 Phone: 815 454-2624
This organization provides containerization, trans portation, and disposal services of all liquids and solids (including hardware). Disposal is in controlled chemical and scientific landfill area. Licensed by Atomic Energy Commission for radioactive waste disposal. The organi zation also has two West Coast locations, in the states of California and Washington.
Rollins Environmental Services, Inc P.O. Box 2349 Wilmington, Del 19899 Phone: 302 658-8451
This organization has facilities and services capable of handling:
(1) Liquids. Askarel alone or mixed with solvents or oils. Disposal is by high-temperature incineration.
(2) Solids (software). Askarel-soaked compounds, rags, cartons, absorbing earths, etc. Disposal is by incin eration at combustion temperatures up to 2500F. In cineration gases are scrubbed, and entrained solids are removed before exhausting to air.
Rollins Environmental Services maintains disposal facilities in the following areas:
*The listing given herein is representative of some of the sources that provide this service, .and is not presumed to be complete. Any other organizations that wish to be listed should notify the Standards Institute so that they may be included in the next -edition of this standard.
Philadelphia/Camden: Rollins Environmental Services, Inc
Route 322 Logan Township Bridgeport, N.J. 08014
DSW 357910
19
STLCOPCB4086638
APPENDIX
Baton Rouge: Rollins Environmental Services, Inc Scenic Highway & West Cheatham Lane Scotlandville East Baton Rouge Parish, La 70807
Houston: Rollins Environmental Services, Inc Tidal Road & Highway 134 Deer Park, Tex 77536
Appendix B Analytical Procedures and Laboratory Service Organizations
Bl. General
Analytical procedures for determining PCBs in air, water, and sediments are given in Sections B3 and B4.
B2. Laboratories
The following laboratories are representative of those offering services for PCB analyses:*
Cams Chemical Corporation 1375 Eighth Street La Salle, 111. 61301 Phone:815 223-1500
Limnetics, Inc. (Subsidiary of Cams Corporation) 6132 West Fond du Lac Avenue Milwaukee, Wis 53218 Phone:414 461-9500
Gollob Analytical Service Corporation 47 Industrial Road Berkeley Heights, N.J. 07922 Phone: 201 464-3331
33. An Analytical Procedure for the Determin ation of Airborne PCBs
B3.1 Scope. This procedure is based on techniques used by the Monsanto Industrial Chemical Company
`The listing given herein is representative of some of the sources
that provide this service, and is not presumed to be complete.
Any other organizations that wish to be listed should notify the
Standards Institute so that they may be included in the next
edition of this standard.
---- -
>
for the isolation and determination of PCBs in water, soil/sediment, and biological materials. Absolute con firmation of PCB structures is not obtained with this method. Where needed, additional structure proof should be obtained using techniques such as mass spec trometry for further identification of gas chromatog raphy fractions.
B3.2 Principle. Airborne PCBs are absorbed in toluene by drawing the air through one or more fritted bubblers or impingers in cylinders filled with toluene. After a suitable amount of air is sampled, the scrubbing solvent is diluted or concentrated, and interfering components, if present, are removed by chemical treatment and column absorption chromatography. The amount and type of PCBs present are determined by electron cap ture gas chromatography (EC/GC).
B3.3 Reagents (1) Hexane: Pesticide grade. (2) Toluene: Pesticide grade. (3) Sodium sulfate: Anhydrous, granular, analytical
reagent (AR) grade. Heat at 400C for 1 hour prior to use.
(4) Alumina adsorption: For chromatographic anal ysis, 80/200 mesh. Heat at 400C for a minimum period of 4 hours and deactivate with 5% (w/w) distilled water.
For alumina column preparation fill a chromatographic column with hexane up to the point where the reservoir joins the column, and push a glass wool plug to the bot tom with a glass rod. In a 50-ml beaker measure 35 ml (about 30 grams) of deactivated alumina, and pour this slowly into the column. Tap or vibrate the column to settle the alumina, and top the alumina with 2 to 3. cm of anhydrous sodium sulfate. Wash the column with 50 to 100 ml of hexane prior to the addition of the sample.
(5) Distilled water: Extracted with hexane to re-
,i \i
i' (
1
<
DSW 357911 20
STLCOPCB4086639
>
tu (O O Q. cn UJ tr lu >
<
tu cc
9
APPENDIX
NOTE: Instrument: Hewlett-Packard 5750 Detector: `sNi, electron capture Column: 6-mm X 6-foot, 4% XE-60 on 80/100 mesh,
Chromosorb W, HP, AW-DMCS. Column temperature: 200C Injection temperature: 220C Detector temperature: 250C Carrier gas: He, 60 ml/min Purge gas: 10%CH4/argon, 120 ml/min -Pulse interval: 50 us Injection volume: 5 m1 Standard concentration: 1.00 jig/ml Range: 10 Attenuation: 8
AROCLOR 1016
T
I
I
I 1 I I ' "T
T
0 I 2 34 5 6 78 9
MINUTES
Fig. B1 Aroclor 1016 Electron Capture Chromatogram
move hexane-soluble electron capturing impurities. (6) Sulfuric acid: AR grade, specific gravity = 1.84. (7) Potassium hydroxide: AR grade. (8) Ethanol: Formula 2B. (9) Alcoholic potassium hydroxide, 2.5% (w/v): Dis
solve about 12.5 grams of AR grade KOH in 500 ml of ethanol.
(10) Sulfuric acid-water, 9:1 (v/v): Carefully add 270 ml of AR grade sulfuric acid to 30 ml of distilled water in a 500-ml iced beaker.
(11) PCB standards: Aroclor 1016,1221, 1242, 1248,1254, and 1260. (See Fig. B1 through B7.)
B3.4 Apparatus (1) Gas scrubbing bottles, high form, ground-glass
joint, fritted coarse disks. (2) Separatory funnels equipped with ground-glass
stoppers and TFE-fluorocarbon stopcocks; capacities of 125,250, 500, 1000, and 2000 ml.
(3) Kunderna-Danish evaporative concentrators.
500-ml capacity, equipped with three-ball Snyder col umns and graduated 5-ml capacity vials.
(4) Chromatographic columns, glass, 10 inches X 20 mm (OD), with a 5-inch X 50-mm (OD) reservoir at the top, equipped with TFE-fluorocarbon stopcocks.
(5) Flat-bottomed boiling flasks, 125 ml capacity. (6) (iebig condenser, 200 mm in length. (7) Hotplates. (8) Water bath. (9) 10-^1 syringes. (10) Dry-test meter or wet-test gas meter. (11) Laboratory vacuum pump. (12) Rotating vacuum evaporator. (13) Usual laboratory glassware.
B3:5 Sampling. The air to be sampled for airborne
PCBs is drawn through a gas scrubber (or scrubbers)
and a dry-test meter using a laboratory vacuum pump.
See Fig. B8, The sampling flow rate is controlled by
bleeding in air via a needle valve
-'tween the
DSW 357912
21
STLCOPCB4086640
APPENDIX
aw}
\
i
(
Fig. B2 Comparison of Electron Capture Chromatograms for
Aroclor 1221,1242,1248, 1254, and 1260
DSW 357913
c
22 '
STLCOPCB4086641
..T; *.l
APPENDIX
NOTE:
Instrument: Hewlett-Packard 5750
Detector: **Ni electron capture
Column: 6-mm X 6-foot, 4% XE-60 on 80/100 mesh,
Chromosorb W, HP, AW-DMCS
Column temperature: 170C
Injection temperature: 220C
Detector temperature: 250C
Carrier gas: He, 60 ml/min
.
Purge gas: 10% CH4/argon, 120 ml/min
Pulse interval: 50 ps
Injection volume: 5 til
Standard concentration: 1.48 tig/ml
Range: 10
Attenuation: 4
4 *
RELATIVE RESPONSE
AROCLOR 1221
0 I 2 3456 MINUTES
Fig. B3 Aroclor 1221 Electron Capture Chromatogram
DSW 357914
23
STLCOPCB4086642
RELATIVE RESPONSE
APPENDIX
I
8 10
NOTE:
Instrument: Hewlett-Packard 5750
Detector: *3Ni electron capture
Column: 6-mm X 6-foot, 4% XE-60 on 80/100 mesh,
Chromosorb W, HP, AW-DMCS
Column temperature: 190C
Injection temperature: 220C
Detector temperature: 250C
Carrier gas: He, 60 ml/min
Purge gas: 10% CH^argon, 120 ml/min
Pulse interval: 50 (is
Injection volume: 5 jul
Standard concentration: 1.03 ug/ml
Range: 10
Attenuation: 8
(
I
(
AROCLOR 1242
r
I I I " I, I
0 345 6 7 MINUTES
Fig. B4 Aroclor 1242 Electron Capture Chromatogram
il :i '
i
. 24
DSV\/ 357915
STLCOPCB4086643
ft
UJ to Z o Q. to UJ O' UJ
>
jii_u' ii
iI
ifirnfuiiH'-hr~rn.....-'
APPENDIX
NOTE:
Instrument: Hewlett-Packard 5750
Detector: 4,Ni electron capture
Column: 6-mm X 6-foot, 4% XE-60 on 80/100 mesh,
Chromosorb W, HP, AW-DMCS Column temperature: 190C
Injection temperature: 220C
Detector temperature: 250C
Carrier gas: He, 60 ml/min
Purge gas: 10% CH4/argon, 120 ml/min Pulse interval: 50 ps
Injection volume: 5 aiI
Standard concentration: 1,31 Mg/ml
Range: 10
.
Attenuation: 4
0 I 2 3 4 5 6 7 8 9 10 II 12 13 MINUTES
Fig. BS Aroclor 1248 Electron Capture Chromatogram
OSIN 357916
25
STLCOPCB4086644
APPENDIX
t' . .
v
' r *r-? m.t
i
I
NOTE: Instrument: Hewlett-Packard 5750 Detector: `3Ni electron capture Column: 6-mm X 6-foot, 4% XE-60 on 80/100 mesh,
Chromosorb W, HP. AW-DMCS Column temperature: 205C Injection temperature: 220C Detector temperature: 250C Carrier gas: He, 60 ml/min Purge gas: 10% CH4/argon,120 ml/min Pulse interval: 50 fis Injection volume: 5 jil Standard concentration: 1.02 Mg/ml Range: 10 Attenuation: 8
! : 1 , ! '
.j `{ if ji ;j j[ j
RELATIVE RESPONSE
(
15
10
r
01
23456 78 MINUTES
9 10 II 12
Fig. B6 Aroclor 1254 Electron Capture Chromatogram
OSVM 357917
|
j
STLCOPCB4086645
fjhii'iirih
>
iiII Ii
i
=" :> M! t
APPENDIX
NOTE: Instrument: Hewlett-Packard S7S0 Detector: `JNi electron capture Column: 6-mm X 6-foot, 4% XE-60 on 80/100 mesh,
Chromosorb W, HP, AW-DMCS Column temperature: 220C Injection temperature: 220C Detector temperature: 250C Carrier gas: He, 60 ml/min Purge gas: I0%CH4/aigon, 120 ml/min Pulse interval: SO #is Injection volume: S m1
RPI-ATIVF R P !?F8W ^
i! . i
I
i
I
l
I( I| I11tI
I 2 3 4 5 6 7 8 9 10 II 12
MINUTES
Fig. B7 Aroclor 1260 Electron Capture Chromatogram
0
DSW 357918
27
STLCOPCB4086646
APPENDIX
AIR BLEED
SAMPLE
GAS
INLET
*" SCRUBBER(S)
DRY-TEST METER
EXHAUST
Fig. BS Sampling Train
pump and the meter. At the end of the sampling period, the metered gas volumes are corrected for temperature and pressure to cubic metres at 25C and 760 mmHg.
It is important to note that neither the capacity nor the efficiency of the gas scrubber(s) for removal of airbprne PCBs have been experimentally evaluated. For this reason, it is best to minimize the sampling flow rate and maximize the sampling time period to obtain measurable amounts of PBCs. When high flow rates must be employed or a larger capacity may be needed, it is recommended that several gas scrubbers be used in tandem.
It is cautioned that until the efficiency and capacity of the toluene gas scrubber have been experimentally established, this procedure should be used only to measure relative PCB levels sampled under equivalent conditions.
B3.6 Procedure (1) After scrubbing the desired amount of air, re
cord the metered volume, pressure, and temperature. (2) .Quantitatively transfer the scrubbing solvent
to a round-bottomed flask and reduce the volume to approximately 2 ml by rotary vacuum evaporation.
(3) Quantitatively transfer the concentrate to a 30-ml beaker with the aid of several small portions of toluene.
(4) Inject a fraction of a microlitre of the concen trate into the gas chromatograph to check for interfer ences and determine the approximate level of PCBs present. If no interferences are present, dilute or con centrate the sample to a known volume, as determined by the electron capture chromatogram, and proceed with the gas chromatographic analysis.
(5) If interferences are present, proceed with the chemical treatment and column chromatographic cleanup procedures.
(6) Transfer the concentrate to a 125-ml extraction
28
flask with the aid of several small portions of solvent.
(7) Evaporate the concentrate just to dryness with
a gentle stream of dry, filtered air and add 25 ml of
2.5% alcoholic potassium hydroxide.
(8) Add a boiling chip, put a water condenser in
place, and allow the solution to reflux for 45 minutes.
(9) After cooling, transfer the solution to a 250-ml
separatory funnel with the aid of 25 ml of distilled
water.
(10) Rinse the extraction flask with 25 ml of hex
ane and add it to the separatory funnel.
(11) Stopper the separatory funnel and shake vigor
ously for at least 1 minute. Allow the layers to separate,
and transfer the lower aqueous phase to a second sepa-
ratory funnel.
'
(12) Extract the saponification solution with a
second 25-ml portion of hexane. After the layers have
separated, add the first hexane extract to the second
separatory funnel, and transfer the aqueous alcohol
layer to the original separatory funnel.
(13) Repeat the extraction with a third 25-ml por-
tion of hexane. Discard the saponification solution and
combine the hexane extracts.
(14) Carefully add 25 ml of the sulfuric acid solu-
tion (9:1 concentrated sulfuric acid-water) to the hex-
ane extracts.
(15) Stopper the separatory funnel and shake vigor-
ously for at least 1 minute. Allow the layers to separate,
and discard the lower aqueous acid layer. Repeat this
step until the acid layer is colorless.
(16) Wash the hexane with a 25-ml portion of
water. Discard the water wash.
(17) Filter the hexane extract through a 4-inch
funnel, plugged with glass wool that is covered with
a layer of sodium sulfate, into a Kundema-Danish evap-
orative concentrator.
(18) Add a small boiling chip, put the Snyder col-
umn in place, and reduce the hexane volume to less ____
DSW 357919
;
;; I J
:
i
. := j; :; ' If ?j
: = `
j
i =j ;; ;) |j jj 'I \! :f fj
!
j
!
;j
STLCOPCB4086647
Ml
APPENDIX
than 5 ml by heating the apparatus in a 80C to 90C water bath.
(19) After cooling, remove the 5-ml graduated tube and transfer the hexane extract to an alumina adsorp tion column, washing it in with several 5-ml portions ofhexane.
(20) Carefully add 100 ml ofhexane to the column reservoir, and collect the total eluent in either a 250-ml volumetric flask or a Kunderna-Danish evaporative con centrator.
(21) If the column eluent is collected in a volumet ric flask, dilute to volume with hexane, and proceed with the gas chromatographic analysis.
(22) If the column eluent is collected in a KundernaDanish evaporative concentrator, reduce solvent volume, cool, dilute to volume, and proceed with gas chromato graphic analysis.
B3.7 Electron Capture Gas Chromatographic Procedure (1) Instrument: Gas chromatograph (for example,
Hewlett-Packard Model 5750, or the equivalent) (2) Detector: High-temperature 63Ni, electron cap
ture cell (3) Column: 6-mm X 6-foot glass column, 4% XE-
60 on 80/100 mesh, Chromosorb W, HP, AW-DMCS (4) Column temperature: 160C to 190C (5) Injection port temperature: 195C to 215C (6) Detector temperature: 300C (7) Pulse interval: 50 us (8) Flow rates: Helium carrier, approximately 60
ml/min; argon-methane purge, approximately 120 ml/ min
Using EC/GC as the determinative step, inject, in duplicate, 1 to 10 /al of each solution into the chroma tograph. By comparison with standard solutions in jected, in duplicate, under the same operating condi tions, determine the amount and type of Aroclor using the individual or total peak height and area methods.
B3.8 Sample Concentration. Concentration of sample extracts is necessary, prior to cleanup by chromato graphic or chemical means, to reduce sample size and increase sensitivity. The preferred method of concen trating allows minimum loss through volatilization or chemical decomposition and requires a minimum time. The three methods of solvent volume reduction most commonly used are evaporation by exposure to a stream of air, evaporation employing a KundernaDanish evaporative concentrator equipped with a Snyder column, and evaporation under reduced pres sure. All three techniques have been used without en countering any significant losses from volatization or chemical alternation. However, the Kunderna-Danish evaporative concentrator and the stream-of-air methods are easier to use.
B3.9 Column Adsorption Chromatography and Chemi cal Cleanup. Silica gel, a magnesia silica gel,9 and alu mina deactivated with 0%, 1.0%, 1.5%, 2.0%, and 5% water were investigated as adsorbants for the elimina tion of interferences. Alumina (5% water) was found to be more effective and reproducible than either silica gel or a magnesia silica gel.9 The activity of alumina varies with age and lot; therefore, 5% water was added to the alumina, after heating for a minimum of 4 hours at 400C, to ensure a reproducible activity.
Saponification, and subsequent extraction of the sample with sulfuric acid, is an effective way to remove a number of chlorinated hydrocarbon interferences as well as other matrix interferences. PCBs are not affected.
B3.10 Column Performance. Column performance is the key to effective gas chromatographic analysis and, as such, the choice of column materials is particularly important. Ideally, the support employed should be inert, mechanically strong, and of high surface area. Chromosorb W, HP, AVV-DMCS fulfills these require ments and is recommended for this work.
A variety of polar and nonpolar liquid phases have been investigated. The following columns have been found to provide adequate separation, etc, for use in PCB analysis by electron capture: 4% (w/w) DC-200, SF-96, OV-17, SE-30, SE-54, XE-60, Apiezon L, and 6% QF-1. DC-200 and XE-60 or QF-1 have been found to be the most suitable of these liquid phases.
Another important consideration when working . with an extremely sensitive detector and, consequently, low levels of materials is column conditioning. With polar phases such as XE-60 and QF-1, operating a new column overnight at a temperature 25C to 50C higher than that to be used during analysis results in a more stable column. A no-flow conditioning technique is. employed to condition nonpolar columns. The column is purged with carrier gas, heated for 30 minutes at an elevated temperature without carrier flow, and then cooled to room temperature. At the end of this cycle, the carrier flow is resumed and the conditioning is com pleted as in the case of the polar liquid phase. Two pre cautions should be observed: during conditioning, the column should not be connected to the detector, and the maximum safe temperature of the liquid phase should not be exceeded.
Since all liquid substrates bleed to one degree or another and columns eventually degrade, all new col umns should be characterized with two column perfor mance indicators: the number of theoretical plates (AO and a tailing factor (T). p,p'-DDT is employed to check these parameters because it is known to degrade on*
* For example, Florisil.
DSW 357920
29
ypwipWiBPPi^viwa^p^p^wwwwjipjjiawiJiJWt! j jumunuppwiL
>1
~
STLCOPCB4086648
APPENDIX
Iialaiiiuu
THEORETICAL PLATES, N=l6(*/y)2
\i |\
TAILING, T=o/2b
PEAK HEIGHT
Fig. BIO Calculating the Tailing Factor
( I
1
"poor" columns. In this manner, one can determine whether the performance of a new column is satisfac tory and when the column performance begins to fall off. A column is considered good if the number of theo retical plates per foot is of the order of 400 to 500, with tailing factors of 1.0 to 1.3. Calculation of these parameters is shown in Fig. B9 and B10. Additionally, there should be no significant extraneous peaks upon injection of a pure p,p'-DDT standard.
Other chromatographic conditions that can be ad justed are column temperature and flow rates. Al- . though resolution of a mixture increases with decreas ing temperature, a temperature should be chosen that allows the elution of all components within a conve nient time period. The flow rates shown are optimum for a given instrument, column, and detector system. These should be adjusted if better results can be achieved.30
30
Any system of instrument and column suitable for chlorinated pesticide analysis is satisfactory for PCB analysis. The use of the high-temperature 63 Ni electron capture cell is highly recommended. The ability to oper ate at higher temperatures prevents maintenance prob lems due to contamination from high-boiling compo nents. Glass columns also should be employed.
B3.11 Detection and Measurement. Quantitative deter minations employing the electron capture detector are nonstoichiometric measurements made by comparing peak heights or areas for known concentrations with those for unknown compositions. Three variations of the peak height or area quantification procedures have been employed:
Case I. EC gas chromatogram of PCB unknown, unchanged with respect to standard PCB with no evi dence of interferences
DSW 357921
)* I
l
STLCOPCB4086649
iiuiitii ft*
APPENDIX
I Case II, EC gas chromatogram of PCB unknown,
B4.3 Reagents
altered with respect to standard PCB with no evidence
(1) Hexane: Pesticide grade.
of interferences
(2) Acetonitrile: Pesticide grade.
Case III. EC gas chromatogram of PCB unknown,
(3) Sodium sulfate: Anhydrous, granular, analytical
unchanged with respect to standard PCB with evidence
reagent (AR) grade. Heat at 400C for 1 hour prior to
of interference
use.
The amount of PCBs in Case I samples is determined
(4) Alumina adsorption: For chromatographic anal
by preparing a plot of the major peak height or area
ysis, 80/200 mesh. Heat at 400C for a minimum of 4
versus concentration. With Case HI samples, a peak free hours and deactivate with 5% (w/w) distilled water.
from interference is used. When dominant interferences
For alumina column preparation fill a chromato
are present, one or more of the chemical cleanup proce graphic column with hexane up to the point where the
dures is employed.
reservoir joins the column, and push a glass wool plug
In all cases, the response of the electron capture
to the bottom with a glass rod. In a 50-ml beaker mea
detector must be linear for quantitative analysis.
sure 35 ml (about 30 grams) of deactivated alumina,
B3.12 Contamination. In determining PCBs in biologi
and pour this slowly into the column. Tap or vibrate
cal materials by electron capture gas chromatography,
the column to settle the alumina, and top the alumina
laboratory sources of contamination can be a major
with 2 to 3 cm of anhydrous sodium sulfate. Wash the
problem. The samples and extracts should never be
column with 50 to 100 ml of hexane prior to the addi
allowed to come in contact with materials other than
tion of the sample.
" -.; .
glass, TFE-fluorocarbon, or metal. Laboratory glassware
(5) Distilled water: Extracted^with iiexiane to re
should be thoroughly washed with hot, soapy water,
move hexane-soluble electron capturing impurities.
and rinsed with distilled water, acetone, and then hex
(6) Sulfuric acid: AR grade, specific gravity = 1.84.
ane. All equipment should also be rinsed again with
(7) Potassium hydroxide: AR'grade.
hexane just prior to use, and blanks should be frequent
(8) Ethanol: Formula 2B.
I ly carried through all steps of the procedures to ensure against the possibility of contamination.
(9) Alcoholic potassium hydroxide, 2.5% (w/v): Dissolve about 12.5 grams of AR grade KOH in 500 ml of ethanol.
B3.13 Sensitivity
' (10) Sulfuric acid-water, 9:1 (v/v): Carefully add
(1) Concentration: 2 ppb (parts per billion)
270 ml of AR grade sulfuric acid to 30 ml of distilled
(2) Absolute sensitivity: 0.5 X 10~9 gram
water in a 500-ml iced beaker.
(3) Volume injected: 5 pi (4) Final volume of extract: 5 ml
(11) PCB standards: Aroclor 1242, 1248, 1254, and 1260. (See Fig. B2 and Fig. B4 through B7.)
(5) Sample size: 250 ml
B4.4 Apparatus
(1) Separatory funnels equipped with ground-glass
stoppers and TFE-fluorcarbon stopcocks; capacities of
B4. Analysis of Water and Sediment for PCBs
125,250, 500, 1000, and 2000 ml. (2) Kunderna-Danish evaporative concentrators,
B4.1 Scope. This methodology is used by the Monsanto Industrial Chemical Company for the determination of the amount and type of PCBs in water and sediment samples. Absolute confirmation of PCB structures is not obtained with this method. Structure proof can be ob tained using additional techniques such as mass spec trometry to further identify the gas chromatography fractions.
500-ml capacity, equipped with three-ball Snyder col umns and graduated 5-ml capacity vials.
(3) Chromatographic columns, glass, 10 inches X 20 mm (OD) with a 5-inch X 50-mm (OD) reservoir at the top, equipped with TFE-fluorocarbon stopcocks.
(4) Sintered glass filter funnels, 600-ml capacity, 90-mm disk diameter, medium porosity.
(5) Flat-bottomed boiling flasks, 125-ml capacity. (6) Liebig condenser, 200 mm in length.
B4.2 Principle. The PCBs in water and sediment sam
(7) Hot plates.
ples are extracted into an organic solvent. Interfering
(8) Water bath.
components are then removed from the extracts by
(9) Reciprocating variable-speed shaker.
chemical treatment and column adsorption chroma
(10) 10-jd syringes.
tography. The amount and type of PCBs present are
(11) 32-oz all-glass mortars and pestles.
determined by electron capture gas chromatography
(12) 8-inch X 12-inchX 2-inch (2-1/2 qt) heat-
(EC/GC).
resistant glass baking dishes.
DSW 357922
31
STLCOPCB4086650
rite.
APPENDIX
(13) U.S. Standard sieve. No. 30. (14) Usual laboratory glassware.
B4.5 Sampling. It is to be assumed that a rather wide variety of sampling techniques may be employed in col lecting samples submitted for analysis. For this reason, water and sediment samples should be treated as given in B4.5.1 and B4.5.2.
B4.5.1 Water. Where possible, the entire water sam ple, including the container in which it was collected, should be extracted with hexane. With larger samples, where this is not physically possible, the containers should be simply agitated and a 250-ml portion used for the analysis. (See B4.6.)
B4.S.2 Sediment. Any excess water should be de canted, and the entire sediment transferred to a glass baking dish to air-dry at room temperature. The dried material should be transferred from the dish into a mor tar and ground. The ground sediment should be sieved, remixed, and a 250-gram portion taken for analysis. (See B4.7.)
B4.6 Extraction of Water Samples (1) After agitating, transfer the entire aqueous sam
ple or a 250-ml aliquot into a graduated glass cylinder. Record the volume of the sample and quantitatively transfer it to a separatory funnel with distilled water.
(2) Rinse the graduated cylinder with two 50-ml portions of hexane and add each to the separatory fun nel.
(3) Stopper the separatory funnel and shake vigor ously for at least 1 minute. Allow the layers to separate, and transfer the lower aqueous phase to a second separa tory funnel. *
(4) Extract the water sample a second time with a 50-ml portion of hexane. After the layers have sepa rated, add the first hexane extract to the second sepa ratory funnel, and transfer the aqueous layer to the original separatory funnel.
(5). Repeat the extraction with a third 50-ml por tion of hexane. Discard the aqueous layer and combine the hexane extracts.
(6) Filter the combined extracts through a 4-inch funnel, plugged with glass wool that is covered with sodium sulfate. Collect the filtrate in a KundemaDanish evaporative concentrator, add a small boiling chip, put the Snyder column in place, and reduce the hexane volume to less than 5 ml by heating the apparatus in an 80C to 90C water bath. (CAUTION: Solvent vapors must be vented into a hood.)
(7) After cooling, remove the 5-ml graduated tube and transfer the hexane extract to an alumina adsorp tion column, washing it in with several 5-ml portions of hexane.
(8) Carefully add 100 ml of hexane to the column
32
reservoir, and collect the total eluent in either a 250-ml volumetric flask or a Kunderna-Danish evaporative con centrator.
(9) If the column eluent is collected in a volumetric flask, dilute to volume with hexane, and proceed with the gas chromatographic analysis.
(10) If the column eluent is collected in a KundernaDanish evaporative concentrator, reduce solvent volume, cool, dilute to volume, and proceed with the gas chro matographic analysis.
"
B4.7 Extraction of Sediment and Soil Samples (1) Decant off any excess water and transfer the
entire sediment sample to a glass baking dish. Air-dry at ambient temperature (heat should be applied).
(2) When dry, transfer the soil/sediment to a mor tar and grind. Sieve the ground material through a No. 30 mesh sieve and weigh 250 grams (to the nearest 0.01 gram) into a 16-ounce narrow-neck screw-cap (aluminum-foil liner) glass bottle.
(3) Moisten the soil with about 10 ml of water and add 150 ml of acetonitrile. Cap the bottle tightly, and mechanically shake it for a minimum period of 1 hour.
(4) Quantitatively transfer the acetronitrile extract into a 600-ml sintered glass filter funnel containing a 1/4-inch layer of anhydrous sodium sulfate. Collect the filtrate in a 600-ml beaker (vacuum filtration may be necessary).
(5) After the acetronitrile has completely drained into the beaker, wash the bottle twice with 50-ml portions of acetonitrile, adding each wash to the funnel after the previous wash has completely percolated through the sediment.
(6) Quantitatively transfer the extract to a KundernaDanish evaporative concentrator, add a small boiling chip, put the Snyder column in place, and reduce the solvent volume to less than 5 ml by heating the apparatus in an 80C to 90C water bath. (CAUTION: Solvent vapors must be vented into a hood.)
(7) After cooling, remove the 5-ml graduated tube and transfer the concentrate of extracts to a 125-ml extraction flask with the aid of several small portions of solvent.
(8) Evaporate the extract just to dryness with a gentle stream of dry, filtered nitrogen and add 25 ml of 2.5% alcoholic potassium hydroxide.
(9) Add a boiling chip, put a water condenser in place, and allow the solution to reflux for 45 minutes.
(10) After cooling, transfer the solution to a 250ml separatory funnel with the aid of 25 ml of distilled water.
(11) Rinse the extraction flask with 25 ml of hexane and add it to the separatory funnel.
(12) Stopper the separatory funnel and shake it
DSW 357923
'< \
:: ;;
; ;
'
4 ^
: ! j ;; :: > if :: ;1 i1
: j ?; .i; ' jj jI ji j* '> ' I i f j j
STLCOPCB4086651
9 APPENDIX
vigorously for at least 1 minute. Allow the layers to separate, and transfer the lower aqueous phase to a second separatory funnel.
(13) Extract the saponification solution with a sec ond 25-ml portion of hexane. After the layers have separated, add the first hexane extract to the second separatory funnel and transfer the aqueous alcohol
(6) Detector temperature: 300C (7) Pulse interval: 50 #rs (8) Flow rates: Helium carrier, approximately 60 ml/min; argon-methane purge, approximately 120 ml/ min Using EC/GC as the determinative step, inject, in duplicate, 1 to 10 pi of each solution into the chroma
layer to the original separatory funnel. (14) Repeat the extraction with a third 25-ml por
tion of hexane. Discard the saponification solution and combine the hexane extracts.
(15) Carefully add 25 ml of the sulfuric acid solu tion (9:1 concentrated sulfuric acid-water) to the hex ane extracts.
(16) Stopper the separatory funnel and shake vigor ously for at least 1 minute. Allow the layers to separate, and discard the lower aqueous acid layer. Repeat this step until the acid layer is colorless.
(17) Wash the hexane with a 25-ml portion of water. Discard the water wash.
(18) Filter the hexane extract through a 4-inch fun nel, plugged with glass wool that is covered with a layer of sodium sulfate, into a Kundema-Danish evaporative concentrator.
(19) Add a small boiling chip, put the Snyder col umn in place, and reduce the hexane volume to less than 5 ml by heating the apparatus in an 80C to 90C water bath.
(20) After cooling, remove the 5-ml graduated tube and transfer the hexane extract to an alumina adsorp tion column, washing it in with several 5-ml portions of hexane.
(21) Carefully add 100 ml of hexane to the column reservoir, and collect the total eluent in either a 250-ml volumetric flask or a Kundema-Danish evaporative con centrator.
(22) If the column eluent is collected in a volumet ric flask, dilute to volume with hexane, and proceed with the gas chromatographic analysis.
(23) If the column eluent is collected in a KundemaDanish evaporative concentrator, reduce solvent vol ume, cool, dilute to volume, and proceed with gas chro matographic analysis.
B4.8 Electron Capture Gas Chromatographic Proce dure
(1) Instrument: Gas chromatograph (for example, Hewlett-Packard Model 5750, or the equivalent)
(2) Detector: High-temperature 63 Ni, electron cap ture cell
(3) Column: 6-mm X 6-foot glass column, 4% XE60 on 80/100 mesh, Chromosorb W, HP, AW-DMCS
(4) Column temperature: 160C (5) Injection port temperature: 195C
tograph. By comparison with standard solutions in jected, in duplicate, under the same operating condi tions, determine the amount and type of Aroclor using the individual or total peak height and area methods.
The electron capture detector should also be used to guide the isolation procedures. Water and sediment ex tracts can be checked for the presence of PCBs or inter ferences, or both, by injection of microlitre portions of the extracts at various points in the extraction and concentration schemes. In this manner it can be determined whether the sample needs to be concen trated or diluted and whether the cleanup procedures should be employed.
B4.9 Extraction. The extraction of PCBs from water, employing hexane as the extractant, has been found to be quantitative and sufficiently simple and rapid for use as a routine procedure.
The evaluation of this method was based on spiking water samples with standard acetone solutions of PCBs. The spiking method consisted of adding the PCB in 25 to 50 pi of acetone to 500 ml of tap water in a 32ounce narrow-neck screw-cap jar. After the sample was thoroughly mixed, duplicate 225- to 250-ml aliquots were taken and subjected to the proposed sample prep aration and worked up as outlined. The results were quantified by preparing a calibration curve using stan dard hexane solutions of the PCBs used to spike the water samples. The major isomer peak height was used to construct the calibration plot.
The average recovery and deviation achieved sub stantiated the applicability of the method for the quanti tative recovery and analysis of PCBs from water at the ppb-ppm level.
No PCB recovery experiments from spiked sediment and soil samples have been performed. Instead, several of the residual solids representative of some of the types of sediment or soil analyzed were reextracted with hexane/acetone (40:60) in a soxhlet extractor to test for the efficiency of the acetonitrile extraction step. The hexane, after isolation by dilution with dis tilled water, was then carried through the purification steps. Recoveries by soxhlet extraction have indicated that the acetonitrile extraction of PCBs was essentially quantitative in the cases checked.
B4.10 Sample Concentration. Concentration of sample extracts is necessary, prior to cleanup by chromato-
DSW 357924
33
STLCOPCB4086652
APPENDIX
graphic or chemical means, to reduce sample size and increase sensitivity. The preferred method of concen trating allows minimum loss through volatilization or chemical decomposition and requires a minimum time. Hie three methods of solvent volume reduction most commonly used are evaporation by exposure to a stream of air, evaporation employing a Kundema-Danish evapo rative concentrator equipped with a Snyder column, and evaporation under reduced pressure. All three tech niques have been used, and no significant losses from volatilization or chemical alternation have been encoun tered. However, the Kunderna-Danish evaporative con centrator and the stream-of-air methods are easier to use. .
B4.ll Column Adsorption Chromatography and Chemcal Cleanup. Silica gel, a magnesia silica gel,9 and alu mina deactivated with 0%, 1.0%, 1.5%, 2.0%, and 5% water were investigated as adsorbants for the elimina tion of interferences. Alumina (5% water) was found to be more effective and reproducible than either silica gel or a magnesia silica gel,9 The activity of alumina varies with age and lot; therefore 5% water is added to the alumina, after heating for a minimum of 4 hours at 400C, to ensure a reproducible activity.
Saponification, and subsequent extraction of the sample with sulfuric acid, is an effective way to remove a number of chlorinated hydrocarbon interferences as well as other matrix interferences. PCBs are not affected.
B4.12 Column Performance. Column performance is the key to effective gas chromatographic analysis and, as such, the choice of column materials is particularly important. Ideally, the support employed should be inert, mechanically strong, and of high surface area. For these reasons, Chromosorb W, HP, AW-DMCS is recommended for this work.
A variety of polar and nonpolar liquid phases have been investigated. The following columns have been found to provide adequate separation, etc, for use in PCB analysis by electron capture: 4% (w/w) DC-200, SF-96, OV-17, SE-30, SE-54, XE-60, Apiezon L, and 6% QF-1. DC-200 and XE-60 or QF-1 are the most suit able of these liquid phases.
Another important consideration when working with an extremely sensitive detector and, consequently, low levels of materials is column conditioning. With polar phases such as XE-60 and QF-1, operating a new column overnight at a temperature 25C to 50C higher than that to be used during analysis results in a more stable column. A no-flow conditioning technique is em ployed to condition nonpolar columns. The column is
For example, Floiisil.
34
purged with carrier gas, heated for 30 minutes at an elevated temperature without carrier flow, and then cooled to room temperature. At the end of this cycle, the carrier flow is resumed and the conditioning is com pleted as in the case of the polar liquid phase. Two pre cautions should be observed: during conditioning, the column should not be connected to the detector, and the maximum safe temperature of the liquid phase should not be exceeded.
Since all liquid substrates bleed to one degree or another and columns eventually degrade, all new col umns should be characterized with two column perfor mance indicators: the number of theoretical plates (/V) and a tailing factor (7). p,p'-DDT is employed to check these parameters because it is known to degrade on "poor" columns. In this manner, one can determine whether the performance of a new column is satisfac tory and when the column performance begins to fall off. A column is considered good if the number of theo retical plates per foot is of the order of 400 to 500, with tailing factors of 1.0 to 1.3. Calculation of these parameters is shown in Fig. B9 and B10. Additionally, there should be no significant extraneous peaks upon injection of a pure p,p'-DDT standard.
Other chromatographic conditions that can be ad justed are column temperature and flow rates. Although resolution of a mixture increases with decreasing tem perature, a temperature should be chosen that allows the elution of all components within a convenient time period. The temperatures given are optimum for 42% chlorinated biphenyl; temperatures are increased when specifically analyzing for the higher chlorinated biphe nyls; that is, 54%, 60%, etc. The flow rates shown are optimum for a given instrument, column, and detector system. These should be adjusted if better results can be achieved.
Any system of instrument and column suitable for chlorinated pesticide analysis is satisfactory for PCB analysis. The use of the high-temperature 63Ni electron capture cell is highly recommended. The ability to oper ate at higher temperatures prevents maintenance prob lems due to contamination from high-boiling compo nents. Glass columns also should be employed.
B4.13 Detection and Measurement. Quantitative deter minations employing the electron capture detector are nonstoichiometric measurements made by comparing peak heights or areas for known concentrations with those for unknown compositions. Except for sharp peaks, peak area measurements are usually more repro ducible than peak height measurements but are extreme ly time consuming unless a recording integrator is em ployed. However, peak height measurements are as accurate as disk integration of triangulation and if rH<
DSW 357925
i
e
STLCOPCB4086653
f- .\ .
>
peak shape represents a Gaussian curve, the height may be considered independent of the base. Consequently, peak height measurements are generally used. Three variations of the peak height or area quantification pro cedures have been employed.
Case I. EC gas chromatogram of PCB unknown, unchanged with respect to standard PCB with no evi dence of interferences
Case II. EC gas chromatogram of PCB unknown, altered with respect to standard PCB with no evidence of interferences
Case III. EC gas chromatogram of PCB unknown, unchanged with respect to standard PCB with evidence of interference
The amount of PCBs in Case I samples is determined by preparing a plot of the major peak height or area versus concentration. For Case II, a plot is prepared of the total sum of all major peaks versus concentration. With Case III samples, a peak free from interference is used. When dominant interferences are present, one or more of the chemical cleanup procedures is employed.
APPENDIX
In all cases, the response of the electron capture detector must be linear for quantitative analysis.
B4.14 Contamination. In determining PCBs in water, soil, and sediment by electron capture gas chromatog raphy, laboratory sources of contamination can be a major problem. The samples and extracts should never be allowed to come in contact with materials other than glass, TFE-fluorocarbon, or metal. Laboratory glassware should be thoroughly washed with hot, soapy water and rinsed with distilled water, acetone, and then hexane. All equipment should also be rinsed again with hexane just prior to use, and blanks should be frequently carried through all steps of the procedures to ensure against the possibility of contamination.
B4.15 Sensitivity (1) Concentration: 2 ppb (2) Absolute sensitivity: 0.5 X 10"9 gram (3) Volume injected: 5 /rl (4) Final volume of extract: 5 ml (5) Sample size: 250 ml
o
DSW 357926
35 ,
STLCOPCB4086654
American National Standards
The standard in this booklet is one of nearly 5,600 standards approved to date
by the American National Standards Institute, formerly the USA Standards In
stitute.
.
The Standards Institute provides the machinery for creating voluntary stan dards. It serves to eliminate duplication of standards activities and to weld con flicting standards into single, nationally accepted standards under the designa tion "American National Standards."
Each standard represents general agreement among maker, seller, and user
groups as to the best current practice with regard to some specific problem. Thus
the completed standards cut across the whole fabric of production, distribution,
and consumption of goods and services. American National Standards, by reason
of Institute procedures, reflect a national consensus of manufacturers, consumers,
and scientific, technical, and professional organizations, and governmental agen
cies. The completed standards are used widely by industry and commerce and
often by municipal, state, and federal governments.
. .
The Standards Institute, under whose auspices this work is being done, is the United States clearinghouse and coordinating body for standards activity on the national level. It is a federation of trade associations, technical societies, profes sional groups, and consumer organizations. Some 1,000 companies are affiliated with the Institute as company members.
The American National Standards Institute is the United States member of the International Organization for Standardization (ISO), the International Electro technical Commission (IEC), and the Pan American Standards Commission (COPANT). Through these channels American industry makes its position felt on' 1 the international level. American National Standards are on file in the libraries of the national standards bodies of more than 50 countries.
For a free list of all American National Standards, wrltei
-
American National Standards Institute, Inc
1430 Broadway
Now York, N. Y. 1001*
DSW 357927
i
Ii ! i ii
f
STLCOPCB4086655