STATUS REPORT CABLE OIL
TO
DISTRIBUTION LIST
Baber - MBABE H. S. Bergen - HBERG P. G. Benignus - PBENI J. G. Bryant - JBRYA R. Davis - RDAVI J. R. Fallon - JF ALL T. L. Goss age - TGOSS R. H. Munch - RMUNC - JFQ J. R. Pullman - New York W.R. Richard - WRICH R. Weiss - RWEIS J. J. Roder - Chicago
DSW 201796
STLCOPCB4059863
STATUS REPORT CABLE OIL
Our efforts to date to establish an existing product as an electrical transmission cable coolant and dielectric indicate am opportunistic market exists. Cable manufacturers and utilities have expressed interest in our candidate fluids and our expertise in heat transfer and dielectrics. Additional actions to achieve our stated objectives are included in the attached details. Please review these actions and note initiate where indicated.
D. E. Roush lb
DSW 201797
STLCOPCB4059864
STATUS REPORT CABLE OIL
Background The use of underground power transmission cables is increasing in the U. S. Availability and cost of right-of-ways and a growing list of restrictions against overhead utilities are given as the reasons. Insulated cable is buried in pipe to transmit power and costs are as much as 30:1 over conventional pole-type installations. Economics have forced the utilities toward greater electrical carrier capacity in 6 and 8 inch diameter pipe (larger sizes greatly escalate costs) and to achieve greater capacities, it becomes necessary to cool as well as electrically insulate the conductors. It is in the cooled pipe-type power transmission cables that we find a significant market for heat transfer fluids with dielectric capability. Polybutene and refined mineral oils are now used but these fluids have not performed as expected. Therminol 55 as MCS 1072(primarily alkyl benze ie) appears to be the best fluid to fit this growing market.
Project Objective Determine viability of market for heat transfer/dielectric fluids in pipe contained power transmission cables and sell this market on our existing fluids (alkylate H 230 high boiler and ethyl benzenes).
References: J. J. Roder memo to J. R. Fallon, October 12, 1970 and minutes of October 19, 1970 meeting by J. G. Bryant.
DSW 201798
STLCOPCB4059865
Status
The actions listed in the October 19 minutes are either completed or near completion.
1) AEIC contact made by M. Baber. Two fluid specifications and application guide for insulation temperatures of impreg nated-paper insulated cables forwarded to W. R. Richard and R. Munch. J. Roder and D. Roush have obtained Commonwealth Edison's specifications for cable insulating and taping oils--these are attached.
2) Samples of light and heavy polybutene are promised from Zanona at Commonwealth Edison in Chicago. J. Roder to pick up fluid when it arrives at Commonwealth.
A sample of Amoco polybutene was obtained by Roder from Union Carbide and forwarded to St. Louis.
A look at compatibility with alkylate benzenes and the dielectric properties has been initiated by R. Weiss.
3) J. Bryant has obtained the following MCS designations for candidate products for cable application:
MCS 1072 MCS 1072
alkylate H 230 L alkylate H 230 H
4) A 5 gallon sample of MCS 1072 will be adsorptive refined to improve the dielectric properties and will be sent to Zanona at Commonwealth Edison for aging tests. Aging tests are carried out at 95C. for 100 hours in air environment with and without copper metal. Measurements of power factor change and oxi dation of the fluid are tabulated.
5) J. Pullman in New York City has contacted the following cable manufacture rs:
General Cable Company - New York, New York Mr. Steve Turner
SW*01799
STLCOPCB4059866
Phelps-Dodge - Yonkers, New York Mr. Jim Moran Mr. Frank Teti
The Okonite Company Mr. Dick Waldron
Anaconda Wire & Cable - I^^tings on the Hudson, N. Y. Mr. Ed Eich
Pullman reports the following:
--The cable companies are interested. General Cable and Phelps Dodge are ready to test our fluid on receipt of samples and data. Tests will be similar to aging tests described in #4 plus compatibility with cable impregnants being used. Impregnants will not be changed to accommodate cable coolind fluidrathe r cooling fluid must be compatible with impregnant fluid and insulation system.
--Ihe heat transfer problem in fluid filled cables is of equal importance to the dielectric and service-life properties of the fluid. The cable manufacturers request help in the cooled cable installations. We have offered to consult on the heat transfer application of our fluids.
--Use of oil filled cables is just beginning in terms of the cooled cable applications which are required to accommodate higher electrical energy rates transferred. (See M. Baber report October 13, 1970, "Fluids for Power Cables") Oil filled cables have been in use for years ii Europe. The primary fluid used in alkyl benzene chemistry but energy rates are lower and do not require cooling.
--Installed filled cables can be converted to cooled filled systems. Phelps-Dodge is. working with General Electric on cryogenic cooling techniques.
--Present fluid filled cables are 90% static and 10% cooled. This ratio will reverse within 10 years according to cable manufacturers.
--General Cable is adding 10-15% dodecyl and tridecyl benzene to polybutene to improve heat transfer properties to get better cooling.
dS\N 201 &0
STLCOPCB4059867
--Price of cable oil (polybutene) confirmed at 50 1/2^/gallon for refined but untreated product. Treatment consists of degassing without removal of low boilers, demoisturizing, deaerate and blanket shipment with N^. Treatment adds 10^/gallon to the cost or 60. 5^/gallon for treated oil. Quality and clean-up of the oil are major problems, particularly at the job site. The installation and/or utility company has clean up equipment for maintaining fluid quality. Even N2 pressure is important on fluid,as too much pressure saturates oil with gas creating voids in the insula tion system and possible cable failure.
--MiscellaneousHSteve Turner of Anaconda lives one door from Pullman and Ed Eich of General Cable lives within a mile and is a ski buff. Jay is confident Turner and Eich will cooperate with our effort.
Miscellaneous Information
Cable System Many different arrangements of conductor and insulation exist in cable systems and not all cable systems are liquid filled.
Solid cross-linked polyethylene has been extruded to form an insulating core and outer shield on cable rated to 230 KV. Kaiser has extruded cable of this type. General Electric's clay-filled Vulkene has been extruded to 230 KV rating also but these systems are still being evaluated. The cross-linked PPE insulating systems are used more routinely to 135 KV.
The preference at this point is the cooled, liquid filled cables.
Insulations & Coatings Coatings are required to protect buried pipe containing the cable. Epoxy and vinyl type coatings are used by Pipeline Service Company in Chicago for Commonwealth Edison.
Vinyl type - Endcor 382 Epoxy type - Endcor 745
available from Dearborn Chemical
Other insulation, conductor and sheathing materials are:
Mylar Copper Aluminum Insulating paper
Stainless steel Lead
DSty 201801
STLCOPCB4059868
Cable Oils - Competitive Specified are polybutene, light and heavy grades, Socony Mobilect A and Sun Oil Company's Sun #6. Alkyl benzenes have been used in Europe.
Witco Chemical Corporation, Golden Bear Division, recently advertised a new product compatible with any saturant and with moisture<15 ppm and flash point of 425F. Not identified chemically.
Further Action Required Through January 1971
Responsibility
1) Prepare tentative specification for cable oil based on low viscosity polybutene specifications and including data to date on our MCS 1072(mixed stream).
DER/JGB*
2) Obtain polybutene samples promised from Commonwealth Edison.
J. J. Roder*
3) Complete present evaluations of candidate fluids
R. W. Weiss *
--ethylbenzene bottoms (SD4) --aromatic oil #1 --MCS 1072
4) Complete compatibility study of polybutene and MCS 1072 R. W. Weiss *
5) Evaluate test data and select candidate fluid
6) Gain acceptance of tentative specifications by several OEMs and utilities and establish testing of candidate fluid. (Commonwealth Edison, General Cable and Phelps-Dodge have agreed to testing)
R. W. Weiss/ DER/JGB *DER/J.S. Pullman/ J. J. Roder
7) Prepare quantities of candidate fluid for testing
8) Investigate, in depth, electrical properties of candidate fluid.
R.W. Weiss* R.W. Weiss *
9) Determine production requirements of MCS 1072 (mixed stream) to meet tentative specification
10) Define further the heat transfer demands of pipe-type cable systems.
J. G.' Bryant *
J. S. Pullman* J. J. Roder D. E. Roush
*Prime Responsibility
DSW 201802
STLCOPCB4059869
11) Initiate market plan
* D. E. Roush J. G. Bryant
DSW 201803
STLCOPCB4059870
EM-27020 PAGE I OF 2
LOW VISCOSITY POLYBUTENE OIL FOR PIPE TYPE CABLE
.
1. SCOFE
1.1
The oil furnished In accordance with this specification will be used as the insulating, cooling and pressure medium in'69 and 138 kV high-pressure pipe type, forced-coded,
cable Installations.
2. GENERAL
'
g.l
This oil shall be a butylene polymer oil suitable for use in pipe type installations as an insulating and cooling medium. It shall be chemically compatible with the cable impregnant, and shall be free ~'rom matter which might be injurious to cable installation, or be affected by Endcor 382 v nyl pipe coating or Endcor 745 epoxy pipe coating and/or other parts of the pipe type c.ble system.
This oil shall meet the followirg requirements when tested in accordance with applicable ASTM standards of latest issue as listed for the most part in ASTM Specification D117.
. 3. PROPERTIES
3.1 FLASH POINT
---------------------130C or higher.
Test Method ASTM D92.
(J ' P'
.
3.2 POUR POINT Minus 45C or lower. Test Method ASTM D97-
4? f
3.3 VISCOSITY
At 37.8C: 115 to 140 Saybolt Universal Sec. At 100C: 38 to 44 Saybolt Universal sec. Test Method ASTM D88.
i<?'3 0 cs. ^
J,(, H ^ tS
3.4 NEUTRALIZATION NUMBER
The neutralization number or amount of potassium hydroxide in milligrams to neutralize 1 gram of the oil shall be lesB than 0.02. Test Method ASTM D974.
3.5 FREE AND CORROSIVE SULPHUR
The oil shall not contain free sulphur nor corrosive sulphur compounds. Test Method ASTM D989, except that the copper strip shall be maintained in the ol. at test temperature
for 16 hours.
3.6 DIELECTRIC STRENOTH
The dielectric strength of the oil slull be 35 kV or higher. Test Method ASTM D877.
3.7 POWER FACTOR
The power factor at 60 cycles shall be not more than 0.1 per cent at 100C. Test Method ASTM D9?4.
3.8 RESISTIVITY
The dc resistivity, in ohms per cubic centimeter, shall be 100 x 1012 or more at 100C. Test Method ASTM DII69.
3.9 GAS CONTENT
The Vendor in his proposal shall state a guaranteed maximum gas content under standard conditions of 760 mm of mercury and 0C, by ASTM D831, for the oil as shipped. The typical constituents of the gas on a volume percentage basis by gas chromatograph shall be included in the proposal.
DSW 201804
TRANSMISSION ENGINEERING DEPARTMENT
T-bfr
COMMONWEALTH EDISON COMPANY SYSTEM STANDARD
STLCOPCB4059871
I0-fe-fc9
EM-27020 Meet OF 2
3.10 COLOR NUMBER
The color number shall not exceed 1 as detern ined by use of the ASTM Union Colorimeter. Test Method ASTM DI55.
3.11 CHLORIDES
Organic chlorides as chlorine shall not exceed 30 ppm.
3.1? WATER
Water content shall not axceed 30 ppm. Test Method ASTM D1533-
4. METHODS OF SAMPLING AMD TESTING
'
>1,1 SAMPLING METHODS
.
The samples on which tests are made shall be obtained by Test Method ASTM D923> except that gas content samples shall be taken directly in the piston type sampling apparatus aE covered in ASTM D831.
5. DETERMINATION OF QUAN HTTSS
6.1
Li
7.2
8,1
Sixty degrees Fahrenheit (60**) is established n.-s the normal temperature for measurement of oil delivered under this specification. Tru tjap :rature of the oil shall be deter mined at the time of volume measurement. The apparent quantity of oil shall be corrected to a 60F basis in accordance with the Standard Abridged Volume Correction Table for Petroleum Oils; ASTM D1250 (Table 7).
6. SHIPMENT
The oil shall be shipped in clean tank cars or tank trucks with a positive regulated
nitrogen blanket at 2 pel maximum over the oil.
'
7. REPORT TO BE FURNISHED 3Y VENDOR
Proposals
include a statement indicating that the oil supplied will be in accordance
with this specification except for ppecifical ly stated exceptions. Any exceptions
shall be clearly listed in the proposal.
At the time of shipment, liquid samples shall be taken from each tank car or tank truck.
The reported inspection results shall include measured values of the properties listed
in the Specification.
.
In addition the amount of water in top and bottom tank oil samples shall be reported.
8. SUPPLEMENTARY SPECIFICATIONS
ASTM Specifications d88, D92. Dg7. BU7, t&55' B8`<1. 1)877, U923, D924, D974, D989,
DII69, D1250, D1533, all of latest revision.
DSW 201805
TRANSMISSION ENGINEERING DEPARTMENT
COMMONWEALTH EDISON COMPANY SYSTEM STANDARD
STLCOPCB4059872
SUPERSEDES EM-27015 3-7-56
5-7-64
EM-27015
Page 1 of 2
INSULATING OIL FOR PIPE TYPE CABLE
I.. SCO IT.
*
The oil furnished In accordance with this specification will be used as the Insulating, cool ing and pressure medium in 69 and 138 KV high-pressure pipe type cable installations.
2. GENERAL
2.1
'
This oil shall be a pure mineral oil specially prepared and refined for use in pipe type in stallations as an insulating and cooling medium. It shall be chemically compatible with the cable impregnant, and shall be free from matter which might be injurious to insulation. No-ox-id #260 pipe coating and/or other parts of the pipe type cable system. Sun Oil
Company Sun #6 Electrical Oil is an approved oil.
This oil shall meet the following requirements when tested in accordance with applicable ASTM standards of latest issue as listed in ASTM Specification 0117-5^.
3. PROPERTIES 3.1 FLASH POINT
190C or higher. Test Method ASTM D92-52, or latest revision. 3.2 POUR POINT
Minus 21C or lower. Test Method ASTM D97-47, or latest revision.
1,
3-3 VISCOSITY
At 37.8c between the limits of 750 to 850 Saybolt Universal sec.^
At 100.OC between the limits of 55 to 65 Saybolt Universal sec. Test Method ASTM D88-53, or latest revision.
3.4 NEUTRALIZATION NUMBER
The neutralization number or amount of potassium hydroxide in milligrams to neutralize 1 gram of the oil shall be less than 0.02. Test Method ASTM D974-54T, or latest revision.
3.5 FREE AND CORROSIVE SULPHUR
The oil shall not contain free sulphur nor corrosive sulphur compounds. Test Method ASTM D989-51, or latest revision. The copper strip shall be maintained in the oil at test temperature for 16 hours.
3.6 DIELECTRIC STRENGTH
The dielectric strength of the oil shall be 25 KV or higher. Test Method ASTM D877-49, or
latest revision.
.
3.7 POWER FACTOR
The power factor at 60 cycles shall be not more than 1.0 per cent at 100C. Test Method ASTM D924-49, or latest revision.
3.8 RESISTIVITY
The d-c resistivity in ohms per cubic centimeter shall be 2.0 x 10^ or more at 100C. Method ASTM D1169-54T, or latest revision.
Test
3.9 GAS CONTENT
The oil need not be degassed by the vendor.
NOTE: After degassing, the gas content shall be less than 1.0 percent under standard condi tions of 760 m.m. of mercury and OC. Test Method ASTM D831-48, or latent revision.
TRANSMISSION ENGINEERING DEPARTMENT
T-L--fr
DSW 201806
COMMONWEALTH EDISON COMPANY SYSTEM STANDARD
STLCOPCB4059873
5-7-64
EM-27015
Page 2 of 2
10 COLOR NUMBER
The color -number shall not exceed 2 as determined by Use of ASTM Union Colorimeter. Method ASTM D155-45T, or latest revision.
Test
4. METHODS OF SAMPLING AND TESTING
4.1 SAMPLING METHODS
The samples on which tests are made shall be obtained by Test Method ASTM D923-49# or latest revision, except that gas content samples Bhall be taken directly In the piston type sampling apparatus as covered In ASTM D831-48.
5. DETERMINATION OP QUANTITIES
Sixty degrees Fahrenheit (60F) Is established as the normal temperature for measurement of oil delivered under this specification. The temperature of the oil shall be determined at the time of volume measurement. The apparent quantity of oil shall be corrected to a 60F basis In accordance with the Standard Abridged Volume Correction Table for Petroleum Oils; ASTM D1250-53 (Table 7).
6. SHIPMENT
6.1
Insulating oil supplied under this specification shall be shipped In clean tank cars with nitrogen gas In the space over the oil.
7. SUPPLEMENTARY SPECIFICATIONS
7.1
ASTM Specifications D88-53, D92-52, D97-47, D117-54T, D155-45T, D831-48, D877-49, D923-49, D-924-49, D974-54T, D989-51/ D1169-54T, D1250-53, all of latest revision.
TRANSMISSION INOINiEIINC MPARTMNT
DSW 201807
COMMdNWiXiJH KDfcdN teMPANY SYSTEM STANOAftD STLCOPCB4059874
SUPERSEDES EM-27005
11-9-55
Stock No. 351.022, 5 gal can 351.007, 55 gal drum
CABLE INSULATING OIL
2-28-56
EM-27005
Page 1 of 2
1. SCOPE
1.1
The oil furnished in accordance with this specification will be used as an insulating medium in cables and accessories for 34.5, 69 and 138 kv solid type and low-pressure oil-filled cables. It shall be a pure mineral oil approved by the purchaser, and conforming to the following requirements, as determined by the stated method of testing.
2. GENERAL
2.1
A one gallon sample of the kind of oil that is proposed to be furnished shall be submitted in a clear glass container for the purchaser's approval. If the sample meets the specifi cations, and is approved by the purchaser, oil of equivalent quality can be shipped as instructed. This does not require that the oil supplied be of the same lot as the original sample, but it does require that it be in accordance with the same specifications and have characteristics eqqal to those of the original.sample when subjected to the same tests and inspection. Socony Mobil Mobiiect A is an approved oil.
2.2
Each shipment of .oil will also be sampled and tested by the purchaser end shipments not meet ing these specifications will be rejected.
3. PROPERTIES
3.1 FLASH POINT
150C or higher. Test Method ASTM D92-52, or latest revision.
3.2 POUR POINT
Minus 40C or lower. Test Method ASTM D97-47, or latest revision.
3.3 VISCOSITY
At 37.8c between the limits of 92 to 125 Saybolt Universal sec. At 54.4c between the limits of 60 to 72 Saybolt Universal sec. At 100.OC between the limits of 38 to 40 Saybolt Universal sec Test Method ASTM D88-53, or latest revision.
j'iiJ*
V
3.4 NEUTRALIZATION NUMBER
The neutralization number or amount of potassium hydroxide in milligrams to neutralize 1 gram of the oil shall be less than 0.02. Test Method ASTM D974-54T, or latest revision.
3-5 FREE AND CORROSIVE SULPHUR
The oil shall not contain free sulphur nor corrosive sulphur compounds. Test Method ASTM D989-51 or latest revision. The copper strip shall be maintained in the oil at test temperature for 16 hours.
3.6 DIELECTRIC STRENGTH
The dielectric strength of the oil shall be 25 KV or higher, Test Method ASTM D877-49, or latest revision.
3.7 POWER FACTOR
The power factor at 60 cycles shall be not more than 0.50 per cent at 100C. Test Method
ASTM D924-49, or latest revision.
'
3.8 RESISTIVITY
The d-c resistivity in ohms per cubic centimeter shall be 15 x 10^2 or more at 100C. Test Method ASTM D116S-54T, or latest revision.
TRANSMISSION EN6INKRING DEMITMfNT DISTRIBUTION ENGWEERING DEPARTMENT
T L-S-
DSW 201808
COMMONWEALTH EDISON COMPANY SYSTEM STANDARD
STLCOPCB4059875
2-28-56
EM-27005
Page 2 of 2
3.9 QAS CONTENT The oil need not be degassed by the vendor.
3.10 COLOR NUMBER The color number shall be less than 1 as determined by use of ASTM Union Colorimeter. Test Method ASTM D155-45T, or latest revision.
4. METHODS OF SAMPLING AND TESTING 4,1 SAMPLING METHODS
The samples on which tests are made shall be obtained by Test Method ASTM D923-49, or latest revision.
5. DETERMINATION OF QUANTITIES
5.1 Sixty degrees (60F) is established as the normal temperature for measurement of oil de livered under this specification. The temperature of the oil shall be determined at the time of volume measurement. The apparent quantity of oil shall be corrected to a 60 de gree basis in accordance with the Standard Abridged Volume Correction Table for Petroleum Oils; ASTM D1250-53 (Table 7).
6. SHIPMENT 6.1
Cable oil shall be shipped in 55-gallon steel drums. Each container shall be oil-tight ftnd sealed to prevent the entrance of moisture and shall be stencilled "Socony. Mobil Mobilect A" The figures shall be at least one-half inch high and preferably one inch or mure high.
7. SUPPLEMENTARY SPECIFICATIONS
7.1 ASTM Specifications D88-53, D92-52, D97-47, D115-45T, D877-49, D923-49, D924-49, D974-54T, D989-51, D1169-54T, D1250-53, all of latest revision.
TRANSMISSION ENGINEERING DEPARTMENT DISTRIBUTION ENGNEERtNG DEPARTMENT
DSW 201809
COMMONWEALTH EDISON COMPANY SYSTEM STANDARD
STLCOPCB4059876
SUPERSEDES E-32105 EM-27010
9-E8-42.
QUARTS - STOCK NO. 351.004 GALLONS - STOCK NO. 351.010
TAPING OIL
8-5-fc<
EM-27010
Page 1 of 2
1. SCOPE
1.1
This specification covers oil used to fill Joints of paper Insulated solid type cable rated 34.5 kv and below. The oil may also be used In conjunction with varnished cloth tape application in cable Joints and terminals, to test paper cable Insulation for moisture at temperatures not exceeding l60C, and to wash filingB from connectors.
2. GENERAL
Vendors Initially quoting on this oil Bhall submit two one quart samples representative of the oil to be furnished under this specification. All subsequent shipments will be rejected If found inferior In any respect to the sample submitted, or not meeting the requirements of this specification.
3. PROPERTIES
3-1 FLASH POINT The flash point shall not be less than 225C. Test method ASTM D-92.
3.2 POUR POINT The pour point shall not be above 5C nor below -15c. Test method ASTM D-97-
3.3 VISCOSITY
The viscosity shall be within the following limits;
Tempera ture Degrees Centigrade
Viscosity Saybolt (Universal) Sec.
100.0
1300-5000 400-1500
60-175
The viscosity shall be determined by a Saybolt Universal Viscosimeter having a standard orifice 0,1765 inch In diameter. Test method ASTM D-88.
3.4 NEUTRALIZATION NUMBER
The neutralization number or amount of potassium hydroxide In milligrams to neutralize one gram of the oil shall be less than 0.03. Test method ASTM D-974.
3.5 FREE AND CORROSIVE SULPHUR
The oil shall not contain free sulphur or corrosive sulphur compounds. Test method ASTM D-989. The copper strip shall be maintained In the oil at test temperature for 16 hours.
3-6 DIELECTRIC STRENGTH
The dielectric strength shalL be 25 kv or higher when tested in accordance with ASTM D-877.
3.7 PCWER FACTOR
The power factor at 60 cycles shall not be more than 1.00 percent at 100C. Test method ASTM D-924.
DSW 201810
TRANSMISSION ENGINEERING DEPARTMENT DISTRIBUTION ENGINEERING DEPARTMENT
TLS
COMMONWEALTH EDISON COMPANY SYSTEM STANDARD
STLCOPCB4059877
8-5-64.
EM" 27010
Page 2 of 2
INSPECTION
4.1 TESTING Each shipment received shall be tested for viscosity at 54.4 and 100C as per Par. 3-3* and for dielectric strength per Par. 3.6. At the option of the Inspector a complete t st of all properties shown In Section 3 may be made on any shipment.
4.,- SAMPLING If the shipment consists of 50 cans or less, 3 cans shall be selected at random for testing. If the shipment exceeds 50 cans, 4 Bamples shall be selected. If any one sample Is found defective, the shipment shall be rejected.
5. PACKING AND MARKING
5.1 Taping oil shall be shipped in quart or gallon cans as specified In the purchase order. The cans shall be of the sealed type and shall be packed In cartons containing approximately 10 quart cans, or 4 one gallon cans.
5-2
Each can and carton shall be marked with the name of the supplier, and "Taping Oil EM-27010". In addition each carton shall be marked with the purchase order number.
6. SUPPELBflSNTAHY SPECIFICATIONS ASTM Specifications D-88, D-92, D-97, D-877, D-924 and D-989 all of latest revision.
TRANSMISSION ENCINEERINC D0>ARTMENT DISTRIBUTION ENGINEERING DEPARTMENT
DSW 201811
COMMONWEALTH EDISON COMPANY SYSTEM STANDARD STLCOPCB4059878
*ft**rg*gyg?a:
:l
/
/
/
/
/
/I. THE PROJECT
PROJECT PROFILE
TITLE: Formulated Fluids for Transformers, Switchgear and Power Cables Replacement in Mineral Oil Applications.
TYPE: A - Extension of Product Line
j -- n,4:c. *
is
5% /
Product Objective (Who are the customers and what are they trying to accomplish?):
Power and distribution transformers consume the bulk of the electrical mineral oil used in the electrical industy. Present consumption in transformers is estimated to be about 45 M gallons_or $11 M. Consumption in switchgear and cables may be on the order of 4 M gallons.
Present mineral oil is felt to be satisfa tory in all these applications, and there is no great desire to change fluids. However, there are certain
properties in which present mineral oils are somewhat deficient.
Fire resistance in transformers is one, thus the market for 1.4 M gallons of Askarel. A small market may exist for a blending agent which would make transformer oil more fire resistant and more resistant to the formation of , arc-formed gases. Askarel might be used in switchgear except that non explosive, but corrosive HC1 is formed under the repeated arcing conditions.
Viscosity is important in transformers, the lower the better for fluid flow and good heat transfer. Historically, viscosity was unimportant in under ground cables and viscous fluids are still normally used. More recently, designs for EHV underground cables required that the fluid be pumped and forced cooled. Lower viscosity fluids were needed and the slightly more expensive polybutenes were substituted for some straight mineral oils.
Fluids which will operate at higher temperatures in combination with paper
are desired for some transformer applications, but mainly in cables. Above
75C or so degradation products from the paper attack mineral oil. Both
Askarels and mineral oils are more sensitive to contaminants, oxygen and '
water that is desirable.
.
-
Heat transfer is generally a prime function of an electrical fluid. A fluid or system which allowed faster heat transfer would be of interest to the industry.
Finally, if some way could be found to improve the dielectric strength of the fluid or the fluid and paper in combination, this would be considered a major advance by the industry and would be most desirable. It has been suggested that the formation of a jell in the paper might cause a significant increase in dielectric strength of the system.
DS\N 2a8A2
STLCOPCB4059879
i. '
-'
.
i/ ' '
-.
/.
I
.
(What are the specifications of the products we propose to develop
jose customers?):
/'
.
'
'.
hsformer and switchgear applications, the product would.have to impart '/ increase in desired properties (dielectric strength, low temperature tfiance, oxidative stability, viscosity, non-flammability, etc.) to ty a higher price, even as a blending agent. Otherwise it must be iitive in price and superior to mineral oil in some respect. Therminol ja alkyl benzene high boiler available from the Inorganic Division msy jbly be superior to mineral oil in some respects.
/same is true in cables, but with some exceptions. Above 345 KV the
jof present fluids and materials causes the need for pumping stations
.
/ forced cooling, which is expensive. Forced cooling would not be
quired if fluid/solid dielectric (paper or film) systems could be designed
I operate at higher temperatures, say 125C. Higher temperature fluid/paper
^sterns should find limited applicability in transformers as well.
;ome cables are designed to operate above 550 KV. It is possible that for
these neither cellulosic paper nor non-synthetic mineral oils will be
useable, and synthetic fluids will be required. Low dissipation factors
and low dielectric constants are important in higher voltage cable appli
cations .
1
CONTRIBUTION TO SALES AND PROFITS
/
i/
f
i Market Potential
Year
Total Market
1972 1974 '
$13 M $15 M
ii
1977
$18 M
J
Basis of estimates:
Expected Market Share
$0 M $1 M
$2 M
10-127. of total use in transformers and switch gear. Chances of success are below 50% at these sales levels.
Estimated Profit Contribution (How much profit, when?):
20% on sales or $0.4 M in 1977
"
Estimated Capital Investment Required: Minor plus working capital in early years, as this is a byproduct stream.
III. PROJECT APPROACH, RESPONSIBILITY AND CONTROL________________________
'`
R and D Program (brief statement of general approach)
.
As materials and approaches come to mind, these should be evaluated for possible R&D effort. The development of anti-oxidants could be considered. The following steps will be taken on the alkyl benzene high boiler:
. DSW 201813
STLCOPCB4059880
V
i
i.
i
i) Determine how much by-product material we have available.
What its physical, chemical and electrical properties are.
Whether it would be of uniform quality or subject to variations at the whim of those operating the detergent alkyl benzene process.
4) Have it evaluated by the complete set of industry tests for
transformer use by someone like Doble Engineering. -
! 5) See how properties match industry needs.
6) Decide what treatment is needed.
/
/
i
/
/
/ /
7) Determine whether or not any additives are required or could be
used if needed to improve cost/performance.
8) Evaluate to see if cost/performance is better.than other
materials.
R and D Expense:
$10,000 on alkyl benzene high boiler.
Project Leaders - Marketing or Development J, Bryant on alkyl benzene, M. Baber on others
Research
R. H. Munch
Action Plan: .
Electrical/Electronic Industry Diversification Plan, Initial Draft, M. F. Baber, 8/28/70
IV. PROJECT STATUS REVIEW
Status:
Achievement Targets (minimum)
Samples of alkyl benzene streams obtained
Properties of streams measured
_-
. Additives research completed
Samples of product to G.E. and Westinghouse
Dates
2/1/71
3/15/71
.
6/1/71
7/1/71
Possible Road Blocks and Alternatives:
Utilities prefer only one general purpose fluid for transformers. The new
fluid may not be enough superior to mineral oil to justify use of a second
fluid.
;
We could consider reselling mineral oil for Lion Oil or another oil company,
perhaps one presently in the business and doing poorly. DSW 201814
STLCOPCB4059881