American Society of Heating and Ventilating Engineers Guide, 1930 CHIMNEYS FOR GAS APPLIANCES The burning of gas differs from the burning of coal in that the force which supplies the air for combustion of the gas comes largely from the pressure of the gas in the supply,pipe, whereas air is supplied to a bed of burning coal by the force of the chimney draft. If, with a coal-burning boiler, the draft is poor, or if the chimney is stopped, the fire is smothered and the combustion rate reduced. Such a condition on a gas boiler or furnace would interfere with the combustion of the gas, but the gas would continue to pass to the burners and the resulting incomplete com bustion would produce a dangerous condition. In order to prevent incomplete combustion from insufficient draft, all gas-fired boilers and furnaces should have a back-draft diverter in the flue connection to the chimney. A study of the drawing of a typical back draft diverter will make it plain that a stoppage in the chimney will cause the combustion products to come out into the boiler room, but there will be no-interference with Table 6. Height of Stack in Feet for Horizontal Return Tubular Boilers (Sea Level and 60 Deg. Fahr. Outside Temperature)3 Nominal. Horsepower 15 20 25 30 35 40 50 60 .75 90 100 115 Drapt at Base or Stack, Inches 0.12 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 Ratino--Per Cent 100 150 200 21 22 25 26 28 30 35 37 41 43 46 51 52 56 61 60 65 71 69 74 81 78 84 91 86 93 101 95 102 111 104 112 122 112 121 132 ' Friction loss in stack assumed 0.1 in. per 100 ft. See also Note a, Table 5. the complete combustion of the gas. Another feature in the construction of the back-draft diverter is that a down draft from the chimney will have practically no effect upon the combustion of the gas, due to the baffle deflecting the draft into the boiler room. As is the case with the complete combustion of almost all fuels, the products of combustion for gas are carbon dioxide (CO,) and water vapor' with just a trace of sulphur trioxide (SO,). Sulphur usually burns to the trioxide in the presence of an iron oxide catalyst. The volume of water vapor in the flue products is about twice the volume of the carbon dioxide when coke oven or natural gas is burned. Because of the large quantity of water vapor which is formed by the burning of gas, it is quite important that all gas-fired central heating plants be connected to a chimney having a good draft. Lack of chimney draft causes stagnation of the products of combustion in the chimney and results in the con densation Of a large amount of the water vapor. A good chimney draft draws air into the chimney through the openings in the back-draft 258 Chapter 14--Chimneys Table 7. Available Draft for 100 Ft. Steel Stacks of Different Diameters3 (Based on a stack temperature of 500 deg. JahrP and 100 lb. of gas per horsepower. For other heights of stack, multiply draft by height + 100) HorsePOWER Diameter or Stack in Inches 36 42 48 54 60 66 72 78 84 96 108 114 120 132 144 200 0.55 0.62 400 0.21 0.46 0.56 0.61 600 0.19 0.42 0.53 0.59 800 0.23 0.43 0.52 0.58 0.61 0.63 1000 0.29 0.45 0.53 0.58 0.61 0.63 1200 0.35 0.47 0.54 0.58 0.61 0.64 1600 2000 2500 3000 35CX) 4000 4500 5000 0.31 0.43 0.52 0.56 0.62 0.64 0.65 0.65 0.43 0.50 0.59 0.62 0.63 0.64 0.41 0.54 0.60 0.61 0.63 0.48 0.56 0.59 0.61 0.63 0.64 0.40 0.52 0.56 0.58 0.62 0.64 0.48 0.52 0.56 0.60 0.62 0.43 0.49 0.53 0.58 0.61 0.44 0.49 0.56 0.60 Data from Marks' Mechanical Engineers Handbook. bFor other stack temperatures add or deduct before multiplying by height 100. as follows: For 750 deg. fahr. add 0.17 in. For 700 deg. fahr. add 0.14 in. For 650 deg. fahr. add 0.11 in. For 600 deg. fahr. add 0.08 in. For 550 deg. fahr. add 0.04 in. For 450 deg. fahr. deduct 0.04 in. For 400 deg. fahr. deduct 0.09 in. For 350 deg. fahr. deduct 0.14 in. Table 8. Stack Sizes by Kent's Formula (A ssumirig 5 lb. of coal per horsepower per hour) Dlim. Area In. Sq. Fr. SO 60 Height or Stack in Feet Side or. Equivalent 80 100 * 150 175 200 | 225 | 250 Square Stack, Diam. Inches Commercial Horsepower Inches 33 5.94 106 115 133 149 36 7.07 129 141 163 182 39 8.30 155 169 196 219 245 42 9.62 183 200 231 258 289 316 48 12.57 246 269 311 348 389 426 460 .54 15.90 318 348 402 449 503 551 595 60 19.64 400 437 505 565 632 692 748 66 23.76 490 537 620 694 776 849 918 72 28.27 591 646 747 835 934 1023 1105 78 33.18 700 766 885 990 1107 1212 1310 84 38.48 818 896 1035 1157 1294 1418 1531 90 44.18 96 50.27 102 56.75 1338 1496 1639 1770 1893 2008 2116 1532 1713 1876 2027 2167 2298 2423 1739 1944 2130 2300 2459 2609 2750 108 63.62 114 70:88 120 78.54 126 86.59 132 95.03 144 113.10 156 132.73 168 153.94 1959 2190 2392 2592 2770 2939 3098 2192 2451 2685 2900 3100 3288 3466 2438 2726 2986 3226 3448 3657 3855 2697 3016 3303 3568 3814 4046 4265 2970 3321 3637 3929 4200 4455 4696 3554 3973 4352 4701 5026 5331 5618 4190 4684 5131 5542 5925 6285 6624 4878 5454 5974 6454 6899 7318 7713 30 33 32 36 35 39 38 42 43 48 48 54 54 60 59 66 64 72 70 7ft 75 84 80 90 86" 96 91 102 98 108 101 114 107 -120 112 126 117 132 128 144 138 156 150 168