Section 21S. 122 loading Operations
a) Ho person shall cause or allow the discharge
of more than 1.6 kg/hr (6 lbs/hr) of organic
MterlaV Into'the atmosphere during the
loading of any organic, Material from the
aggregate loading pipes of any loading
facility having'through-put of greater than
1$1 coble meters per day (40,000 gal/day)
Into any railroad tank car. tank truck or
.. trainer unless such loading facility Is
- equipped with submerged loading pipes or a
device-that Is equally effective in
. ...
controlling emissions ah^ Is approved by live.
.Agency according to the provisions of 35 111.
-Ado. Code 201:
'.
b) Ho person* shall-cause'oral low the loading of. -
.any organic material. Into any stationary tank having a storage,capacity of greater than 946 .1 (250 gal), unless such tank Is equipped . with a permanent submerged loading pipe or an
equivalent- device approved by the Agency according to the provisions of IS 111. Adi. i
Code 201. or unless such tank is a pressure tank as described In Section 2.15, 121(a) or Is fitted.with a recovery system as described In Section 215.121(b)(2).
c) Exception: If no odor nuisance exists the . limitations or this Sect1on:s|Ml1 only apply .. .
_ to the loading of volat11e;idrganic liquid wlth-a vapor'pressure,Of 17.21 kPa (2.5 psla) or greater at 294.3K (70*F).*
(Source: Amended at 1? 111. Reg. AIS, effective Oecenber >24, 1987)
Section 215.121 Petroleuv liquid Storage Tanks
0) The requirements of subsection (b) shall not . apply to any stationary storage tank:
1) Equipped before January 1, 1979 with one of the vapor' loss control devices specified In Section 215.121(b). except Section 21S.121(b)(1);
2) With a capacity of less than 151.42 cubic meters:
3) with a capacity of less than 1.600 cubic meters (422.400 gallons)'and used to store produced crude oil and condensate
. - prior to custody transfer; ,
4) With a capacity of 'less, than 1,430 cubic meters (376.000 gallons) and:vsed to store produced .oil or condensate.In crude oil gathering;
- S) Subject "to new source performance - standards for storage vessels or petroleum liquid. 35 111. Ada. Code 230;
6) In 4itch volatile petroleum liquid is not stored; or
7) Midi Is a pressure tank as described in Section 215.121(a).-
:b) Subject -to subsection (a) no owwr or
-Operator of a stationary storage tank shall cause or allow the storage of any volatile petroleum liquid In the tank.un1ess:
1) The. tank Is equipped with one of the
vapor loss control devices specified In Section 215.121(b);
2) Tberie are.no visible holes, tears or other defects lit the seal or any seal fabric or material of any floating-roofj~
.3) All openings of -any floating.roof deck, except .stub drains, are equipped, with
. covers. 1.1ds, of-seals , such that:.
.A)- The cover, lid or seal is In the closed position at all times except -Whesupctcolcum A1qa3dL.\s..transtccc.ed. to or from the tank;
B) .Automatic bleeder vents are closed at
-... ; .all times except Mtn the roof Is '
v, floated off dr landed on the roof leg
. . -supportsrand--
-
C) Rim vents. If provided; are set to .open-when the roof. Is belngfloated
off. the roof lfg supports of"at the manufacturer's recommended setting:
-'4).. Routine Inspections-Of floating roof seals are-conducted through roof hatches
once every six months;
's> A complete Inspect ton of the cover and seal of'any f.toiating roof tank Is made
... whenever, the. tank .Is.emptied, for reasons other than the transfer of petroleum liquid during the normal operation of the
tapk,. or whenever repairs' are made as a result" of" imy: semf-aMWar iwspectton or
Incidence of roof damage or defect; and
.'6) A record of the results of each Inspection conducted wider subsection
(b)(4) or (b)(5) Is maintained.
c) Owners and operators-of petroleum liquid storage tanks were required to have
- compliance schedules as summarized In
-. Appendix C.
(Source: Amended at 3 111. Reg. 124. effective July26. 1979)
Section 215.124 External Floating Roofs
a) In addition to meeting the requirements or Section 215.123(b). no owiier or operator of a stationary storage tank equipped with an
external floating roof shall cause or allow the'storage of any volatile petroleum liquid In-the tank unless:
1) The tank has been fitted with a continuous secondary seal extending from