CHAPTER 42
1965 Guide And Data^Book)
PSutsC and D of.Fig: 6 show values of pressure.' as afuno-;
tion of length of travel, water quantity, and loading..PartiC:
b based on a loading of 8 sq ft per ton,.while Part'D provides
corrections-for other loadings. The values, of-pressure drop
used on Figi 6 are based on a nominal tube length of: 14- ft;.
Pressure loss in the water beads b based on Fig. C-5 of Refer
ence 5. - > .. '
............ .. j..,. i
Example 8: Select s'water-cooled condenser for 76`tons"of;
refrigeration with an entering' water temperature of 80 F-, reaeoD-
able water cost and average power cost.
....
Solution: At a Sow rate of 5 gpm per ton, the leaving terminal
difference (Part A of.Fig. 6) is reasonable at a length of travel of
56 ft'(4 pass,' 14 ft condenser). The terminal difference would be
6.4 F at a loading of 8 sq ft per ton and 5.4 F- for a loading of lO
sq ft per ton (Part B of Fig. 6). .
For a 56 ft travel and 5 gpm per ton, the' resulting pressure drop
would be 4.9'psi at a loading of 8 sq ft per ton (Pvt C, Fig. 6) and>3.3 pei at 10 sq ft per ton (Part D, Fig. 6). If the lower,pres
sure drop,were selected, the condenser would require about 750 sq ft of external tube surface and would have.a leaving teramial difference of approximately 5.4 F deg plus 1.5 F deg for nobebn^
densable gases, or 6.9 F deg. The condensing temperature would be the sain of (1) the entering water temperature, (2) the tempera
ture rise of 30 gal deg per (min) (ton) + gpm per ton, and (3) the leaving terminal difference, or 80 4- 6.0 + 6.9 ~ 92.9 F.' This
corresponds to a condensing pressure of 174.6 psig. `
: Although ;the optimum condenser selection depends .upon the conditionsiof each installation,-the prevailing power.and water rates, .and the.quantity of water, available, the above
selection-.would be satisfactory for average water and. operate
lug conditions. For use. with water which-will cause .heavy scaling, the-condenser.should be selected, for low-values of terminal difference and on the flatter portion of-the perform ance curves,-where-a change in heat transfer.will,resultrin-a` smaller change in condensing pressure. , : -Fig. 6 shows that,-at low water quantities, short lengths of
travel, and low .values of square feet per ton, the leaving termi nal difference becomes excessive. At such cnnHitimm, a;smail change in heat transfer would mean a large change in con densing pressure. Conversely, the curves show that, at high, water quantities for-long lengths :of travel and-relativelysmall values of square feet per ton, the pressure drop becomes., excessive. The curves therefore provide a direct comparison %
and a balanceof conditions to give-a practical and complete analysb .of oondenser performance.-'
In Fig; 7 the test results of other investigations on ammonia
condensershave been condensed to express the heat transfer as
a functionof the water velocity. Curve A b for clean tubes. Curve B refers to data taken in the same manner as for Curve
A, after the tubes had been in service 16 hr. Curve C refers to dirty tubes,' Although the length of time the condenser;had
been in service! was not stated.
`; '
The variation'in heat transfer as a function of the length of time the condenser has been in service U dearly indicated by
the progressively lower, values as indicated'by Curves A, B
andjC Of F1g.-7..Ferrous tubes.seem to have an increasing
scale' resistance,* even with normal water, due to the continu
ous oxidation, ofjnside tobe.surfaces., High rates of heat
transfer would usually, indicate that condensers having new clean tubes were tested. ' '
Curve D of Fig. 7 shows the coefficient of heat transfer that
may- be expected in practice after the condenser has been in
service s reasonable.length of time. The curves of Fig/7 are'
based on external tube surface actual temperature differences'
measured at various points and averaged. The product of the!
logarithmic mean temperature difference and.the coefficient of>
heat transfer from Curve D will yield the heat transfer with'
sufficient precision for application purpose. Values so obtained
w^ be'in agreemeht with data from Reference 6.'
'
The water; friction pressure, loss, important oh horizontal!
hers, consists of the loss through the tubes plus the loss
resulting from entry conditions, returabenda *nd chang**? in cross-section area.' Fig. 8 shows expected'pressure loss' through
tube circuits and in heads forming the multipass arrangement!
Condensers -
;'
689
Tube pressure loss b given per foot of tube;' Pressure drop
^ypugjj tire
includes toss in change of direction and all_
other loses for one pass. . . ] \ 1 . { , 8 . 1 g^^rch on performance of ammonia condensers of various
typC8 hy. Iinge1 has brought out some important conclusions^
which follow.
Oindenffltkm takes place in the superheated part of the con denser as long a* the walls are cooled below the condensing,tem-._
7
J
V
f
perjteIwoduct of the coefficient of heat transfer' and the mean- -
tomneratuie difference between the vapor add the wall is practiZuJtiie same for superheated vapor and saturatedyapor.^vhen the superheat increases, the transmission coefficient de creases to about.the same extent as the temperature difference *' f-ejeases* thus the quantity of heat transmitted remains about__ the ~rTM,> Therefore,-an average overall heat transfer coefficient and the mean.temperature difference calculated by using the. con1^ning temperature corresponding to the saturated condense in* pressure and the entering and leaving water temperatures,, nay be used to give reasonably accurate condenser ratings.
Vertical Open _ SHelNand-Tub Ammonia: Con?,
f r~/
pr
WATER FLOW PER TUBE-GPM
Fig. 10.-... Heat.Transfer Coefficients for Vertical Shell-and-tube Ammonia Condensers
denser
-. . '
' . .. with 14 ft a common height. As a rule, the seamless steel tubes
The characteristics of this type of condenser are: (a) large ; are 2-in. OD of 0.120 in. average wall thickness.
condenser capacity may be installed in small floor space, (b).
The top of each tube is fitted with a water distributor made
complete installation cost b low/ (c) water !distribution is ---' of cast iron, brass, plastic,
or porcelain, to give the
rimpKfipd, (d) large space.b available in the condenser for ' water a swirling motion as it enters the tube.
earing liquid ammonia,- (e) it is adaptable to easy, purging of
Fig. 10 shows overall heat transfer coefficients for 2 in. and
contaminant gases, (0 tubes'may be easily cleaned without -- ' 2H in. OD tubes at various rates of water flow per tube,
shutting'down, (g) the condenser can be made;to canylarge_ i. Fig.. 11 :shows typical values of leaving terminal difference
overloads by increasing the quantity of -water 'circulated - (temperature corresponding to ammonia pressure minus leav-
through the tubes while, at the same time, avoiding a heavy * ing water temperature) as a function of water flow in gallons
increase in friction head, and (h)_it can be-used.effectively.____l^per minute,per tube for loadings from,5 to 18 sq ft of external
with mndgnsmg water from a cooling tower'or spray pond.*' tube surface per ton and for condensing water quantities from
The construction'of a typical vertical' ammonia shell-and- 1 to 5 gpm per ton. The values are for commercially clean 2-
tube condenser b shown in Fig. 9. It b common in sizes vary in OD steel tubes with a-nominal length.of 14 ft; and are
ing.from 16 to 60 in. in diameter, with a range, ofs 20 to 400 t^, based, on a condenser free of noncondensable gases. The rise
tidies, respectively, and a range in heights from 10 to*16 ft, in the condensing water temperature b normally based on a
(actor of 30 gal deg pei- (min) (ton), and the heat rejection
from the amirmnia vapor b 15,000'Btuh per ton.-Note that
evaporative cooling effect of air within the tubes reduces the
Fig. 7 .... Heat Transfer Coefficients in Horizontal Shell-and-tube Ammonia Condensers
.Fig. ,8
300 .WATER VELOCITY"FPU
jWater.Friction Pressure Loss in Horizontal ,. ., Multipass Condensers
'fig.' 9V. //'Construction of Typical Shell-and-tube;
' Condenser
'Fig. 11 .... Performance ' of Vertical Open : Sbell-andtube Ammonia Condensers*