instead, places the emphasis on ascertaining the level at the point where the sound enters the room.
The noise introduced into a. room or building by ventilating or air conditioning equipment may be divided into two_general kinds depending on how it reaches the room with various sub-divisions:
1. Noise transmitted through the ducts.
a. From equipment such as sprays, fans, etc.
bg From outside, and transmitted through duct walls into air stream.
c. From air current, including eddying noises.
-'
d. Cross talk and cross noises between rooms connected by the same duct system.
e. Noise produced by the grilles.
2. Noise transmitted through the building construction. a. From machine mountings as vibration. b. From equipment through room wall surfaces..
The next step in the solution of this problem is to present data and
discuss methods whereby solutions to the noise problem- can be obtained
when the allowable room noise level and the path through, which the noise reaches the room are known.
NOISE TRANSMITTED THROUGH DUCTS
Operation of an air distribution system results in the generation of noise which may be transmitted through the ducts to the ventilated or conditioned room. The transmission of this noise may be controlled by the proper application of sound absorptive material within the ducts. The application of the absorptive material is a problem,in balancing the room noise level requirements against the intensity of the noise generated.
The four steps in the problem are:
1. Determination of acceptable room noise level resulting from the operation of the equipment.
2. Determination of noise level generated by the equipment.
The difference between items 1 and 2 in decibels is the over-all noise reduction required between the equipment and the room. In the discussion which follows reduction of
noise will be referred to as attenuation of noise.
3. Determination of the natural attenuation of the duct system. .
4. Selection of the proper sound treatment for the duct system.
%
The difference in decibels between the over-all attenuation required and the natural attenuation (3) is the additional sound attenuation to be provided .by absorptive ma- -
terials installed in the duct system.
DESIGN ROOM NOISE LEVEL
Measurements of noise levels have been observed by several, investi gators in various rooms and locations and are listed, in Table 1. The values given were determined with the air conditioning or ventilation equipment not in operation, and with all windows and doors closed simulating the conditions of an actual installation.
This is an important consideration, for in offices or stores adjacent to busy thoroughfares the difference between the typical noise level in the space with the windows and doors open and closed may be as high, as 10 db. Minimum, representative, and maximum levels are given for each type of space! The values are intended to give the variation with respect - to location and not to time, and may be roughly classified by the following:
Minimum loudness refers to: Spaces of expensive construction, typified
' Sound Control
587
by double windows, carpeted floors, heavy upholstered furniture, or acoustically treated walls and ceilings.
Representative loudness refers to: Spaces of average construction and
furnishings which are exposed to external noises typical of the: locality
in which the space is usually found.
.. .
Maximum loudness refers to: (1) Any space of inexpensive construction, and bare furnishings where noise is not an important factor. (2) Spaces
in close proximity to very intense street traffic or to, intense factory noise.
Table 1. Typical Noise Levels
Rooms .
Sound Film Studios.... Radio Broadcasting Studios....1 Planetariu m.... Residence, Apartments, etc__ _________________ - Theaters, Legitimate__::
Theaters, Motion Picture ________ 1. Auditoriums, Concert Halls, etc! Churches_____ ___________ ___________________!
Executive Offices, Acoustically Treated Private Offices Private Offices, Acoustically Untreated General Offices.'____________ Hospitals.....______________________ ______________
Class Rooms____________________________ ._______ Libraries, Museums, Art Galleries
Public Buildings, Post Offices, etc_______________j_ Court Rooms.:i! Small Stores.'.__'
Upper Floors Department Stores.:
Stores, General, Including Main Floor Dept. Stores.__ Hotel Dining Rooms_______ ___ __ ____
Restaurants and Cafeterias_______________________ Banking Rooms:__________________ _______________ . Factories_______ __________________ ;________ ____
Office Machine Rooms:
Railroad Coach_ Pullman Car..___
Automobile_____ Vehicular Tunnel. Airplane________
Vehicles
Noise Lhvel m Decibels to be Anticipated
Min.
Representative - Mux.
10 14 .20
10 14 20 15 20 . 25 33 40 48 25 30 35 30 35 40 25 30 40 25 30 35 30 38 45 35 43 50 1 50 60 70 25 40 55 30 35 . 45, 30 40 45 45 55 - 60 30 35 45 40 50 60 40 50 55 . 50 60 7040 50 60 50 60 70 50 55 60 65 77 90 60 70 80
60b 70 55b 65 50 65 75 85 75 80
80 .75 80 95 90
"These values are only'tentative and approximate and. in general, are for acousUcally treated spaces. Recent measurements by D. F. Seacord. Bell Telephone Laboratories {Journal Acoustical Society ofA mcrico, VOL 12. pp. 183-187. 1940) give average values and standard.deviations of room noise in residences, offices, stores, factories, etc., in large American cities.,
bFor train standing in station a level of about 45 db is the maximum which can ordinarily be tolerated.
_ In general, if the noise level in the space resulting only from the opera tion of the air conditioning equipment is equivalent to or less than the typical level given in Table 1, the installation will prove satisfactory. If the typical level and the equipment level are equal and heard together the resultant level will be 3 db higher than either of them alone.
In some cases it is desirable to keep the equipment noise level in the ventilated or conditioned room at such a value that it actually will not increase the noise level in the room to any measureable degree. This can be accomplished if the equipment noise at the room can be kept 10 db below the noise levels shown in Table 1.