460 CHAPTER 20 1953 Guide cold air from infiltration thus effectively preventing drafts. This has been called perimeter heating. In any case, the warm air registers should be located so that the air stream never discharges directly against people at rest. Tests2 in Warm Air Research Residence No.'l at the University of Illinois, have indicated that continuous blower operation gave better re sults than intermittent operation. Register and Grille Openings Tests also conducted in Warm Air Research Residence No! 1'have in dicated that comparable results are obtainable with either high side wall or baseboard registers, if proper registers and air velocities are selected. Baseboard registers should be of a deflecting-diffuser type which throw the Forced Warm Air Systems 461 of'Manual 7, these-manuals;being publications of the National Warm Air Healing and.Air Conditioning Association. . ,, . : ^ v . . , Registers should be well-proportioned and decorated .to; harmonize with . the`trim..., Air .supply registers should be equippedwith dampers, and all registers should be sealed against leakage around,edges.,. The.register' types shown, in Figs. 1,; 2 and 3: have been recommended as. standard by the NcMorial Warm Air Heating and Air Conditioning-Association. Return air grilles may be located in hallways, near entrance doors, under! windows, in exposed comers, or inside walls, depending, on location of supply registers.' Baseboard returns are preferable to - floor grilles where warm .air. registers are located on inside walls. Where perimeter heating is used, returns placed high on inside walls are preferred. Fig. 1. Recommended Type of Baseboabd and Low Sidewall Installation on Warm Wall* . * Vertical bars with adjustable deflection, or fixed vertical bars with deflections to right and left not exceeding about 22 deg. For low sidewall location, the deflection for horizontal, multiple valve registers should not exceed 22 deg. For baseboard locations, the deflection for horizontal, multiple valve registers should not exceed about 10 deg. ..., air downward toward the floor and diffuse it at the dame time. For base board registers, air temperatures under 125. F,. and air velocities over 500 fpm, should be avoided as they may cause drafts. . ; High, side wall'registers must be of such type that the air is delivered ^horizontally oron a slightly downward direction, and must be'so located as, to avoid impingement of air on ceiling or wall. Directional-flow diffusing type registers should be used to insure best results. Register air velocities should be such that the air velocity will be about 50 fpm three quarters of the distance from the register to the opposite wall. }: Velocities through registers may be reduced by the use of registers larger than' the connecting ducts. Diffusers should be used to spread the air uniformly over the register face. Basic rules for the location and selection `of registers, together'with explanations of factors affecting operation, are given3`in Section III`of Manual .4, Section III of Manual 10, or Section B Fig. 2. Recommended Type of High Sidewall Installation on Warm Wall1* b Horizontal valves, in back or front, to give downward deflections not to exceed from 15 to 22 deg. Dampers Suitable dampers for air direction or volume control are essential to. any duct system. Special care must be used in the design, of any system, to minimize resistance. Sharp elbows, angles, and offsets should be avoided. Three types of dampers are commonly used. Volume dampers are used to completely cut off or reduce the flow through ducts. Splitter dampers are used where a branch is taken off from a main trunk. Squeeze dampers are used for adjusting the volume Of air flow and resistance through a given duct. It is essential that a damper with positive locking device be pro vided for each main or duct branch. Labels placed On ducts should indi cate the room being served. Damper positions should, be marked for summer and winter operation, and to avoid tampering. .. . . Ducts The ducts may be either round or rectangular in cross section. The centerline radii of elbows should preferably be not less than one and onehalf times the pipe diameter for round pipes, or the equivalent round pipe