,642 CHAPTER 23 1958 Guide y based on the change in volume from 0 F to 91 F. From Table 7, determine w = 62.5 lb per cu ft at 0 F, and w = 60.5 lb per cu ft at 91 F. From Table 1, Chapter 26, 10,000 ft of 1-in. IPS contains 44.9 gal. Allowing another 15 gal for heat exchanger' headers, etc., assume the system contains 60 gal. Then the expansion would be -- 2 65q! M-5*. 2.48 gal. A quick approximation of required head can be obtained from Fig. 20. At 91 F, the oil has a viscosity of 4.92 X 10"* ft sq per sec or 35 SSU. Enter Fig. 20 at 35 SSU and rise to the 12 gpm curve, read h = 12.5 ft per 100 ft, then ht -- 12.5 X -- = 37.5 ft, which agrees fairly well with the 37.9 ft obtained by the Equation 23. REFERENCES 1 Standard Specifications for Gypsum Plastering, including Requirements for Lathing and Plastering (American Standards Association, A 42.1, 1946). 1 Code and Manual for the Design and Installation of Warm Air Ceiling Panel Systems (Manual 7-A of the National Warm Air Heating and Air Conditioning Asso ciation). 3 Chapters 4 & 7 (pages 68,69,72-76,180) of Heat Transmission by.W. H. McAdams (McGraw-Hill Book Company, Inc., New York, Third Edition,-1954). 4 Natural Convection and Radiation in a Panel Heated Room, by T. C. Min, L. F. Schutrum, G. V. Parmelee, and J. D. Vouris (ASHAE Journal Section, Heating, Piping & Air Conditioning, May 1956, p. 153). 3 ASHVE Research Report No. .1444--The ASHVE Environment Laboratory, by Cyril Tasker, C. M. Humphreys,' G. V. Parmelee, and L. F. Schutrum (ASHVE Transactions, Vol. 58, 1952, p. 139). 6 ASHVE Research Report No. 1473--Heat Exchanges in a Ceiling Panel Heated Room, by L. F. Schutrum, G. V. Parmelee and C. M. Humphreys (ASHVE Transac tions, Vol. 59, 1953, p. 197). I ASHVE Research Report No. 1490--Heat Exchanges in a Floor Panel Heated Room, by L. F. Schutrum, G. V. Parmelee, and C. M. Humphreys (ASHVE Transac tions, Vol. 59, 1953, p. 495). 8 ASHVE Research Report No. 1499--Effects of Non-Uniformity and Furnish ings on Panel Heating Performance, by L. F. Schutrum and C. M. Humphreys (ASHVE Transactions, Vol. 60, 1954, p. 121). ASHVE Research Report No. 1516--Effects of Room Size and Non-Uniformity of Panel Temperature on Panel Performance, by L. F. Schutrum and J. D. Vouris (ASHVE Transactions, Vol. 60, 1954, p. 455). 10 Heat Loss Through a Solid Floor, by H. H. Macey (Journal Institute of Fuel, 1949, 22-128, p. 369). II Performance of Covered Hot Water Floor Panels, Part I--Thermal Character istics, by E. L. Sartain and W. S. Harris (ASHAE Journal Section, Heating, Piping and Air Conditioning, October, 1955, p. 117). 13 Thermal Design of Warm Water Concrete Floor Panels, by a Subcommittee of the TAC on Panel Heating and Cooling, R. L. Maher, Chairman; W. P. Chapman: H. T. Gilkey: P. B. Gordon; E. F. Snyder; and J. M. Van Nieukerken; and by ASHAE Laboratory Staff Members, L. F. Schutrum, and C. M. Humphreys (ASHAE Jour nal Section, Heating, Piping and Air Conditioning, October 1956, p. 125). 13 Thermal Design of Warm Water Ceiling Panels, by a Subcommittee of the TAC on Panel Heating and Cooling, R. L. Maher, Chairman; W. P. Chapman; `H. T. Gilkey; P. B. Gordon; E. F. Snyder; and J. M. Van Nieukerken* and by ASHAE Laboratory Staff Members; L. F. Schutrum, G. V. Parmelee, and C. M. Humphreys (ASHAE Journal Section, Heating, Piping and Air Conditioning, December 1955> p. 123). 14 Design Conditions for SnowMelting, by W. P. Chapman (Heating and Ventilating, November, 1952, p. 88). 18 Design of Snow Melting Systems, by W. P. Chapman (Heating and Ventilating, April, 1952, p. 95). , 18 Snow Melting System Hydraulics, by W. P. Chapman (Air Conditioning, Heating and Ventilating, November, 1955). 13 Anti-Freeze Protection for Snow Melting Systems, by P. B. Gordon (Official Panel Heating 643 Bulletin, Heating, Piping and Air Conditioning Contractors National Association, February, 1950, p. 21). 18 Properties of Ethylene Glycol and Its Aqueous Selution, by C. S. Cragoe (National Bureau of Standards CRC Report No. 9, Society of Automotive Engineers). 18 Are Thermal Stresses a Problem in Snow Melting Systems? by W. P. Chapman (Heating, Piping and Air Conditioning, June and August, 1955). BIBLIOGRAPHY Trend Curves for Estimating Performance of Panel Heating Systems, by B. F. Raber and F. W. Hutchinson (ASHVE Transactions, Vol. 48, 1942, p. 425). ASHVE Research Report No 1192--Panel Heating and Cooling Performance Studies, by B. F. Raber and F. W. Hutchinson (ASHVE Transactions, Vol. 48, 1942, p. 35). ASHVE Research Report No. 1193--Radiation as a Factor in the Feeling of Warmth in Convection Radiator and Panel Heated Rooms, by F. C. Houghten, Carl Gutberlet and E. C. Hach (ASHVE Transactions, Vol. 48,1942, p. 55). Panel Heating and Cooling, Analysis, by B. F. Raber and F. W. Hutchinson (ASHVE Transactions, Vol. 47, 1941, p. 285). Operating Results of a Residence Radiant Wall Heating System, by E. J. Rodee (ASHVE Transactions, Vol. 47, 1941, p. 123). Performance of a Residential Panel Heating System, by H. F. Randolph and J. B. Wallace (ASHVE Transactions, Vol. 49,1943, p. 235). Radiant Heating (Healing and Ventilating, March, 1941, p. 35). Radiant Heating and Cooling, by F. E. Giesecke (Heating, Piping and Air Condi tioning, June, July, August, September and October, 1940). Calculations for Radiant Heating, by T. Napier Adlam (Heating and Ventilating, October, 1931). Radiant Heating and Cooling, Part I, by C. O. Mackay, L. T. Wright, Jr., R. E. Clark, and N. R. Gay (Cornell University Engineering Experiment Station, Bulletin No. 32, 1943). Design Method for Panel Heating Systems Using Copper Tubing, by R. G. Van- derweil (ASHVE Journal Section, Heating, Piping and Air Conditioning, Nov. 1947, p.123). ' . Air Temperature Gradients in a Panel Heated Room, by J. M. Ayres and B. W. Levy (ASHVE Transactions, Vol. 54, 1948, p. 131). Graphical Solution of Radiant Panel Areas, by W. P. Chapman and R. E. Fischer (Healing and Ventilating, Jan. 1948, p. 88). Embedding Coils in Radiant Heating Panels, by D. L. Mills and L. J. LaTart (Heating and Ventilating, Dec. 1947, p. 75). Radiant Heat with Copper Tubing, by D. L. Mills and L. J. LaTart (Heating and Ventilating, Nov. 1947, p. 95). Panel Heat with Copper Tubing--Experiment in Practice, by D. L. Mills and L. J. LaTart (Heating and Ventilating, Oct. 1947, p. 65). Experimental Studies on Panel Heating Tube Spacing, by B. F. Raber and F. W. Hutchinson (ASHVE Transactions, Vol. 53, 1947, p. 369). Panel Heating--A Basic Discussion, by S. Konzo (American Artisan, Oct. 1946, p. 68). Solar House Heated by a Warm Air Floor Panel, by John E. Peterson (American Artisan, Dec. 1946, p. 83). Design Data for a Warm Air Floor Panel, by Axel B. Algren (American Artisan Jan. 1947, p. HI). The Mechanism of Heat Transfer, Panel Cooling, Heat Storage, by Charles S. s^drLeopold (Refrigerating Engineering, July 1947, p. 33). A eat'n6--Simplified Design and Installation (Copper and Brass Research Research Report No. 1387--Laboratory Studies on Heat Flow Within a ConI i? ?a,ne'> by C. M. Humphreys, H. B. Nottage, C. V. Franks, R. G. Huebscher, * Schutrum and D. W. Locklin (ASHVE Transactions, Vol. 56, p. 175). Research Report No. 1388--Heat Flow Analysis in Panel Heating or Cooling oect'ons, by L. E. Hulbert, H. B. Nottage and C. V. Franks (ASHVE Transactions, Vo1* 56, 1950, p. 189).