McDonnell & Miller, Inc.
Heating Systems
McDonnell Pump Control, Low Water Fuel Cut-off and Alarm Switch * . . for steam boilers of any size; maximum steam pressure, 150 lbs.
The McDonnell No. 150 Pump Control, Cut-off and Alarm switch (and f its equivalent, No. 157) is built down to the last detail to stand the gaff jm of high pres- jP sure and tern- 1 perature. It is equipped with
two switches. One closes on small float drop to control electric boiler feed pump, or electric valve in line to steam pump. Second op erates on greater drop to stop burner and complete low water alarm circuit. Underwriters' Laboratories approved. No. 150 has automatic reset; for manual reset order No. 150-M.
No. 157 is,
same as No. '
150, but has
in t e g ra1
water col
umn which
greatly sim
plifies in-
stallation,
assures ideal 1 reproduc
Nj.157
tion of boiler
water level in float chamber, and pro
vides effective direct blow-down. No. 157
has automatic reset; for manual reset
order No. 157-M.
Operation of No. 150 or 157
Typical hook-up of the McDonnell No 150 is shown below. When water level drops, No. 150 starts pump and then stoDs it when normal level is restored. If emer gency occurs, cut-off switch stops burnerterminals for low water alarm are also provided.
This method holds boiler water level
within the close limits necessary to attain not only safety, but also highest steaming efficiency. This has obvious advantages over the ordinary method of simply re turning condensate whenever a certain quantity has accumulated in receiver. Note McDonnell 21 Series make-up waterfeeders on receiver to maintain minimum water supply.
Drawings are available for all operating conditions--including two or more boilers supplied by one pump.
McDonnell No. 63 Low Water Cut-off for automatically fired hot water heating boilers.
In any hot water heating system there is a possibility of low water after a prolonged opening of an adequate relief valve as the result of some emergency condition. The protection against this, in automatically'fired boil ers, is a low water fuel cut-off, and for some time heating engineers have been using the McDonnell No. 150 to provide this protection because our low pressure low water cut-off was not rated for the higher pressures of hot water boilers. As a result the No. 63 Low Water Cut-off has been developed for pressures up to 50 lbs. It provides an equally dependable low water cut-off for hot water boilers at a more moderate price than that of the No. 150 which must be designed for higher pressures. The McDonnell No. 63 is also used on steam boilers where hook-up with 1 in. equalizing pipes is desired.
1364
No. 63
McDonnell & Miller, Inc.
Heating Systems E^cSois
No.33
McDonnell No. 33 Series Safety Relief Valves McDonnell Safety Relief Valves are built to comply with current A .S.M.E. BoilerCode, and have been tested and rated by the National Board of Boiler and Pressure Vessel Inspectors. The certified rating appears on the nameplate attached to each valve.
The No. 33 Series oners the ultimate in safety in guardingboilers and water systems against the dangers of over-pressure. They have low discharge rate which handles normal thermal expansion easily, and high rate for emergency conditions.
Normal Operation-- When pressure rises to 30 lbs., valve cone lifts just far enough to discharge water at low rate necessary to take care of thermal expansion.
mrrs, I12bS
v|gg| JjMsA -|g||rfj|
gjjjS[
Emergency Condition --If temperature rises into the emergency zone, increased ve locity acts on the "Hydra-Lift" ring, discharging full rated capacity.
For Hot Water Heating Boilers
No. 33 Safety Relief Valve, for boilers per hour. Opening pressure, 30 lbs Inlet, with gross heat output up to 242,900 Btu. $ in.; outlet, 1 in.
Valve No.
3345 3375 33100
33125 33150
'
For Domestic Hot Water Tanks and Heaters
Opening Pressure
45 lbs. 75 lbs. -100 lbs. 125 lbs. 150 lbs.
Btu Capacity
321,300 308,700 423,900 513,900 605,700
Inlet Pipe Size
3n
3*
V V V
Outlet Pipe Size
1" 1" 1' 1' 1'
McDonnell No. 33 Safety Relief Valve and No. 247 Feeder for hot water heating plants with boiler and radiation on same level.
The drawing illustrates how the Mc Donnell No. 33 and No. 247 team up to provide both efficient operation and pro tection for "same-level" systems. In this type of plant there is always a possibility of separation of the boiler from the con
nected load unless a means of maintaining a proper level is provided. The No. 247 water -feeder does this by
keeping the water level above the highest point in the main. Protection from excess pressure is provided by the No. 33 Safety Relief
for all boilers up to 242,900 Btu out put. When the boiler is automatically fired the No. 247 can be used with low water fuel cut-off switch (No. 247-2).
Valve
No. 247
McDonnell No. 65 Explosion Proof Float Switch
The McDonnell No. 65 is a dependable float switch that
can be used to control the operation of a pump, low water
alarm, low water fuel cut-off, and for many other liquid
level control applications. It has been Underwriters'
tested and approved for use under the following hazard
ous conditions:
Class J, Group C--Atmospheres containing ethyl-ether
vapors, ethylene, or cyclopropane.
Class I, Group D---Atmospheres containing gasoline,
petroleum, naphtha, benzine, butane, propane, alcohols,
No. 65
acetone, benzol, lacquer solvent vapors, or natural gas.
Class B, Group F--Atmospheres containing carbon black, coal or coke dust.
Class B, Group G--Atmospheres containing flour, starch or grain dusts.
Write for Catalogs covering McDonnell Products