Document LKYZ2vejRxNjneNjmEwopYdL3
jaw o u ]y/o
Recommended Procedures for the Disposal of PCB-Containil 11j
3RAI- liTM, ~ n
Wastes (Industrial Facilities)
On December 22, 1975, the Administrator of the Environmental
Protection Agency announced an action plan of regulatory and
administrative actions to help ensure that polychlorinated
biphenyls currently in service do not enter the environment.
One portion of that program includes investigation and
recommendation of appropriate disposal procedures for industrial
users of this family of chemicals. The Agency is also evaluating
the consumer waste disposal problem an3 may issue further
guidance on that subject at a later time.
General Background
*
Polychlorinated biphenyls (PCBs) are chlorinated aromatic
organic compounds which give rise to concern because of
their toxicity coupled with their pervasiveness and persistence
in the environment and their tendency to accumulate in food
chains. It is this bioaccumulative characteristic which
manifests itself by possible adverse effects on animals,
including ma.i, that causes the present and continuing concern
over the disposition of PCBs to the environment. PCBs have
been used both in closed systems, defined as applications
where the PCBs are recoverable, and consumptive applications,
where the PCBs are used in and consumed with the product.
Uses of PCBs include formulation into ballasts for
fluorescent fixtures; impregnation of cotton and asbestos for
HONS CW5603
2 braided insulation of electrical wiring; a plasticizer in wire and cable coatings; capacitors and askarol-type transformers; and plasticizers of vinyl chloride polymer films. PCBs used as dielectric fluids in transformers and capacitors are referred to genetically as askarels. Because of their thermal stability and fire resistance, pcbs also find application in high-pressure hydraulic fluids, specialized lubricants and gasket sealers, heat transfer agents, and machine tool cutting oils. Miscellaneous uses include: formulation into some epoxy paints; protective coatings for wood, metal, and concrete; adhesives;'and in carbonless reproducing paper.
The sole producer of PCBs in the United States is the Monsanto Company, under the trade name of Aroclor. PCBs have also been marketed and used by manufacturers in their products under various trade names. Appendix A provides a listing of the trade names used by domestic and foreign manufacturers. Cumulative sales in the U.S. since the intro duction of PCBS are estimated to be 1.5 billion pounds. In 1970 Monsanto voluntarily restricted domestic sales to transformers and capacitors. As a result, current production is down about 50t from the peak years before 1970, but still amounts to about 40 million pounds per year. Monsanto has introduced Aroclor 1016 which is reported to have lower toxicity and higher biodegration rates. Most capacitors
HONS 045604
3
(using'PCBs) produced in the past two years use Aroclor 101G.
Almost all of the PCBs ever produced still present a
serious threat to the environment because of their toxicity,
biohccumulative characteristic in the food chain and slow
degradation. An estimated 150 million pounds of PCBs produced are still in use; 300 million pounds are estimated
to be present in landfills. It is estimated that less than half the PCBs ever produced have entered the environment; of
this amount, only about lot (50 million pounds) are estimated
to have degraded or been incinerated.~The recommendations of
this document are directed only at the PCBs presently in service (or which will enter servico as a result of future production).
Purpose
Pursuant to Section 204 (b)(1) of the Solid Waste Disposal
Act, as amended, the Administrator may issue advisory
guidance and recommendations related to the disposal
of waste materials. These recommended procedures do not have
Btandard-setting or regulatory status, but represent the
best information available on preferable disposal options
for PCB-contaminated waste materials. In addition,, the
Agency plans to conduct studies to determine other options
for treatment and disposal of PCB-containing wastes (including incineration of capacitors containing PCB liquids) during
calendar 1976. The Agency is also aware that the American
National Standards Institute is in the process of revising its
guideline foi^ disposal of askarels containing PCDs
MQNS 045605
4 (ANSI Cl07.1-1974). As significant new information becomes available from these and other sources, this Federal Register issuance will be revised.
`'.The purpose of this issuance is to provide guidance for the disposal of PCB-containing wastes. Thic guidance is addressed primarily to industrial users of PCBs, particularly those manufacturing and/or using capacitors and transformers containing PCBs, although the recommended procedures are appropriate to all PCB-containing wastes. Technical Background
Polychlorinated biphenyls are a class of synthetic compounds which have no known counterpart in the natural environment. PCBs are manufactured by the chlorination of biphenyl with anhydrous chlorine using iron filings or ferric chloride as a catalyst. The three most important physical properties of PCBs are low vapor pressures, low. water solubility, and high dielectric constants. They are miscible with most organic solvents. The chemical properties that make PCBs desirable industrial materials are their excellent thermal stability, their strong resistance to both acidic and basic hydrolysis, and their . general inertness. They are quite resistant to oxidation.
In the process of replacing hydrogen atoms with chlorine atoms, a large number of substitution combinations arise.
MQNS 045606
5 Theoretically 210 PCB compounds can be prepared, but the number of isomers observed in commercial formulations is significantly smaller. In commercial preparation, PCB compounds contain from 12 to 68 percent chlorine; the typical product is a mixture of several PCBs.
Monsanto, the sole U.S. producer of PCBs, has adopted a four-digit designation for its Aroclors; the last two digits represent the approximate chlorine content by percentage weight. The first two digits indicatS^the type of material; biphenyl, triphenyl, or mixture of the two. The higher chlorinated biphenyls are non-flammgble and have extremely low volatilities. Unfortunately, some of the characteristics (stability, non-degradability) which make PCBs so valuable in industrial applications also make them highly persistent in the environment.
The chemical stability, low volatility, high dielectric constant, and compatibility with other chlorinated hydrocarbons have resulted in many and varied industrial applications for the PCBs. The solubility of PCBs in nonpolar solvents explains why they are readily absorbed into fatty tissue and into the liver. Their resistance to oxidation or other types of chemical degradation explains their persistence and accumulation in animal tissue. The latter effect is enhanced both by their insolubility in water and solubility in organic solvents. Their chemical inertness and resistance to metabolism account for their low acute toxicity* But as they
HONS 045607
G slowly build up in a living system, their concentration approaches
toxicity levels, at which point chronic effects make themselves
evident.
.
The low solubility of FCDs in water probably limits
the rate at which they are dispersed by water systems, but
does not seem to limit their range of dispersion. PCBs
discharged into a river or lake will accumulate in the sediment
in relatively high concentration. Plants and animals can
concentrate PCBs above their level in-water alone. Shrimp and
oysters exposed to 10 ppb of Aroclor 1254 have been known to
bioaccumulato from 130- to .3300-ifold: PCBs are not intended to get into the environment, but
they do because their unique chemical properties prevent thorn
from being destroyed by usual waste disposal methods. Thus, they inadvertently escape and become widely dispersed.
Environmental transport models for PCBs have not been developed. Conclusions regarding their behavior, particularly their
distribution and transport in the environment, are based
largely upon the results of DDT research. Recent data indicates
that aerial transport is the most efficient route, although
dumping and river runoff will contribute more effectively to
local contamination.
Disposition of PCBs The persistence of PCBs necessitates extremely careful
attention to final disposition of PCBs and PCB-contaminated
HONS 045608
7
materials. Initial attention within the manufacturing or
l'CD-user facility should be given to reducing the use of
PCBs. Manufacturers or users may either use substitute
(less- contaminating) materials or more efficient methods which produce less waste. However, no matter how many
substitutes are developed and no matter how efficient the
operation may become, there may still remain some applications for which PCBs are the current optimum material and there
still will be waste materials. Spills, damaged goods, and
housekeeping materials will require disposal. Recommended options for the disposal of PCB-contoining wastes (in
priority order) are:
*
Reclamation or recycling
.
Incineration
.
Controlled land disposal
Recycling - Reclamation or recycling of PCBs is usually
feasible only with relatively uncontaminated liquids. Monsanto
maintains a toll-free telephone number (800/325-3850) for
the public for advice on scrap PCBs. If liquids cannot be reused, Monsanto will incinerate returned liquids in their
high temperature incinerator. A technical description of the
Monsanto incinerator is provided in Appendix B.
Recycling of transformers is accomplished by General
Electric Co. and several independent companies. The tank and
inside copper of the'transformer is reclaimed; the PCB liquids,
HONS 045609
8
1 they can't be reused, can be drained and incinerated at
facilities such as General Electric's Pittsfield, Massachusetts^
plant.
............... ......................................................................................................
^lt is quite possible to leach out the PCBs from solid
wastes with a suitable solvent, e.g., acetone, and then dispose
of the decontaminated waste. The solution containing PCBs may
be separated by distillation into PCB, which may be reclaimed,
and the solvent which may be used again. This technique
(of leaching and reclamation) is especially useful after
accidental spills of liquid PCBs. The spills should be absorbed
on dry sand, ash, sawdust, or commercial absorbents and then
processed as above.
Incineration - Present knowledge indicates that the proper
incineration of waste PCBs must involve a suitable balance
among temperature in the incinerator, dwell time in the firing
chamber, plus oxygen availability. Also, a suitable scrubber
must be provided on the exhaust stack to remove the
hydrochloric acid mist that is formed. Preferred requirements are: (1) 2-secoiy) dwell time at
IIOCCC(2000*F) and 3% excess oxygen in the stack; or (2) 1 1/2
second dwell time at 1500"C(2700*F) and 2 excess oxygen in
the stack gas.* These alternates are recommended. Open
hearth incinerators are not considered suitable; the relatively
* These values are from ANSI C107.1-1974. Guidelines for Handling and Disposal at Capacitor and Transformer-Grade Askarelc Containing Polychlorinated Biphenyls, American National Standard
Institute.
HONS 045610
9
low operating temperature of this equipment would only \
volatilize the PCB and pollute the atmosphere.
The above recommendations are suitable for liquids.
Incineration of solid wastes containing PCBs has not been
demonstrated. However, such destruction does appear feasible.
For example, a rotary kiln furnace, with an afterburner and
scrubbing system could probably safely incinerate Golid wastes
containing PCBs. Likewise, other smaller, high temperature
incinerators with sufficient residence times may be satisfactory.
Land Disposal - Wastes containing PCBs should not be disposed
of with other mixed wastes in a sanitary landfill.
Characteristics of transport of PCBs through the soil are
not definitively established. The interaction with other
'
decomposing wastes is not well understood. The ubiquity and
persistence of PCBs indicate that their disposal should be
carefully controlled until additional data are developed.
While these data are being gathered, PCBs (when disposed to
the land) should only be placed in a secure chemical waste
landfill. In general terms, a chemical waste landfill provides
complete long-term_protection for the quality of surface and
subsurface waters from hazardous waste deposited therein, and
against hazards to public health and the environment. Such
sites should be located or engineered to avoid direct hydraulic
continuity with surface and subsurface waters. Generated
leachates should be contained, and subsurface flow into the
disposal area eliminated. Monitoring wells should be
HONS 045611
10 established and a sampling and analysis program conducted. Additional characteristics of a chemical waste landfill are
described in EPA publication. Landfill Disposal of Hazardous y
Wastes: A Review of Literature and Known Approaches (EPA/530/ SW-165)**. Encapsulation of wastes in cement prior to burial in a sanitary landfill has been used for small quantities of solids or sludges contaminated with PCBs. Only those specific sites which have been state-approved for PCB wastes should be used. The EPA publication, Hazardous Waste Management Facilities, (EPA/S30/SW-146) provides some information to potential disposers; this data when used in consultation with State solid yaste management officials can assist in planning' a disposal action.
** Documents referenced here may be obtained from Solid Waste
Information, U.S. Environmental Protection Agency, Cincinnati,
Ohio 45268 v
'
HONS 045612
Appendix A*
v Listing of Names Used for PCBs by Manufacturers
Name
Aroclor Asbestol Askarel Chlorextol Diaclor Dyknnol Elemex Hyvol Inerteen No-Plamol Pyronol Saf-T-Kuhl
Manufacturer
Monsanto American Corporation *
Allis Chalmers
Sangamo Electric
Cornell Dubilier
McGraw Edison
Aerovox
Westinghouse Electric
Wagner Electric
`
General Electric
Kuhlman Electric
Clophen Fenclor Kennechlor
Phenoclor
PK Pyrolene Santotherm
Bayer (Germany) Caffaro (Haly) Kenneclor (Japan) Prodelic (France) Caffaro (Italy) Prodelec (France) Mitsubishi (Japan)
* generic name used for insulating liquids in capacitors and transfomers; may contain PCBs.
MONS 045613
Appendix B
Description of Monsanto Incineration Facility
. . Sauget, Illinois
..
Background
The Krumrarich Plant is one of Monsanto's large
chemical manufacturing plants. The product line
includes sulfuric acid, benzene, chlorine,
polychlorinated biphenyls, several rubber compounds,
and various chemical intermediates. The plant is
located immediately south of East St. Louis, lll._ near the Mississippi River. Since June 1971, Monsanto
has operated a liquid injection incinerator to dispose
of in-house liquid wastes and contaminated PCBs from
customers.
Waste Characteristics
The large majority of the wastes burned are PCB
derivatives. The sources of these wastes are process
still bottoms, spoiled batches, and contaminated
transformer'bils. The heating value of the materials
is about 9000 BTU/lb. Other in-house high BTU liquid
wastes' are also incinerated. Phosphorous compounds
cannot be burned due to the formation of particulates
(Pz,05,,) which foul the injection system. The system is not equipped to handle suspended solids. Four
HONS 045614
20,000 gallon tanks are available ior storage. The wastes are typically stored for several days before incineration to allow undissolved solids to settle. After the settling period, the wastes are pumped directly from the tanks to the liquid combustor. Incinerator Description
The incinerator is a liquid injection type housed in a horizontal cylinder 20 ft. long and 9.5 ft. in diameter. High pressur? steam is used to atomize the waste liquid and inject it into the liquid combustor. The feed rate-measures 2 gal/min. An additional gun which burns natural gas is also positioned inside the plenum. The natural gas serves as an auxiliary fuel to increase the heating value of the waste if necessary. The operating temperature . varies from 2000 to 2200P. If the temperature is too high,' water can be sprayed into the chamber to act as a heat sink. The cylinder is protected from the heat by a lining of refractory brick. High aluminum brick is used in the plenum chamber. A blower supplies 25t excess air forcing the fumes from the plenum and through an oxidizer. The residence time inside the oxidizer is 2-3 seconds.
The unit is operated 24 hours/day requiring 2 men/ shift. Initial capitol costs were $740,000. The disposal cost has averaged lOC/lb.
HONS 045615
Air Pollution Control The fumes exit the oxidizor and enter a water
quench column. The main purpose of the quench is to reduce the temperature of the hot fumes. Particulates are removed next in a high energy venturi. Finally, the emissions are cleaned in a packed bed (polypropylene packing) at the base of the stack- The 40 ft. stack is equipped with a demister. Scrubber liquors are drained to the sewer without treatment.
HONS 045616
REFERENCES
1. Polychlorinated biphenyls and the environment, Inter
departmental Task Force on PCB's. Depts. of Agriculture, Interior, HEW, Commerce and EPA, May 1972.
2. 'Carnes, R., Doerger, J., Spearks, H.L. Polychlorinated biphenyls in solid waste and solid-waste-related materials. Cincinnati. 1973.
3. American National Standards Institute (ANSI). Guidelines for handling and disposal of capacitor-and transformer-grade asknrels containing polychlorinated biphenyls. New York,
January 1974.
4. Peaksall, D.B. PCB's and their environmental effects. Critical Reviews in Environmental Control. CRC. 1975.
5. Brondhurst, M. Use and replaceabilfty of polychlorinated biphenyls. Environmental Health Perspectives. Oct. 1972.
6. Versar, Inc. Assessment of wastewater management, treatment
technology, and associated costs-for abatement of PCBs
concentrations in industrial effluents. Jan. 1976. (Draft
report).
.
7. Bremer, C. State of concerns of the Lake Michigan Toxic Substances Committee related to PCB. Chicago. Internal EPA Report.
8. Aroclor.Polychlorinated polyphenyls (biphenyls). Technical
Bulletin O-FF/IR. St. Louis: Monsanto Industrial Chemicals
Company, Nov. 1971.
'
9. PCB's-environmental impact. Environmental Research. 1972.
10. PCB's their use and control. Organization for Economic Cooperation and Development. Paris. 19747
11. Sewage sludge incineration. Section IV. Effect of incineration on metals, pesticides, and polychlorinated biphenyls. EPA Task Force. March 1972.
12. PCB Conference. National Swedish Environment Protection Board. 1970. pg. 83-86.
13. Hazardous waste management facilities in the United States. Leshendok, T. Environmental Protection Agency SW-146, revised, 1976.
MQNS 045617
2
14. Scut lock, '.A. et al.; .Incineration in hazardous waste management. Environmental Protection Publication SW-141, 1974.
15. Lindsey, F. and Fields, T. Landfill disposal of hazardous '( Wastes: review of literature and known approaches. Environmental Protection Publication SW-165, 1975.
16. Farb, D. information about hazardous waste management
facilities. Environmental Protection Publication SW-145, 1975.
17. Tucker, E., et al. Migration of PCB's in soil induced by percolating water. Monsanto Co. Bulletin of Environmental Contamination and Toxicology, Vol. 13. 1975
18. ASTM. Standard method of test for rapid gas chromatographic estimation of higher boiling homologues of chlorinated biphenyls for capacitor askarels. specification D 1810-63 (1973).
19. HEW. Registry of toxic effects bf chemical substances. 1975 Edition NIOSH dune 1975.
.
20. Mitre Corp. Environmental cycling of PCB's. 1975 (unpublished report).
MOMS 045613