CHAPTER 34
1959
to 12 in. water. A portion of the air or primary air required for combustion is-entrained from the atmosphere by the stream of gas issuing from an orifice, and the air-gas mixture is delivered through a venturi miring tube to the burner head and parts. About 40 to GO percent of the air required for combustion is in the form of primary air and the re mainder, known as secondary air, is supplied from the air surrounding the flame.
Each system embodies characteristics essential for certain applications. It is important that proper and qualified engi neering authorities be consulted prior to the purchase, in stallation, or operation of industrial gas equipment.
FUR BURNING RATES
The burning rate for automatic fuel-burning devices is de termined by the gross heat output required of the boiler, or furnace, to carry the net heating load; plus allowances for system losses and pickup. General values for these allowances have been given in preceding text. Detailed information for piping and pickup allowances for steam and hot water'sys tems, is given in Chapter 35, and for warm air systems, in Chapter IS.
When the gross output, operating efficiency, and heat value of the fuel are known, the required rate of burning can be determined by means of Figs. 17, 18, and 19 for the several fuels. As the rate of fuel-burning is directly propor tional to the load for a given efficiency, these charts can be extended by moving the decimal points the same number of digits in both vertical and horizontal scales.
The correct fuel-burning rate can be determined directly from the several charts for oil or gas burning installations, as these customarily operate on a strictly intermittent basis. These fuel burning devices usually introduce the fuel at a single fixed rate during the on periods, and this rate should be sufficient to carry the gross load. In the ease of coal stokers, which are usually capable of variable rates of firing, it is desirable to operate at as low a rate as weather condi tions will permit, but the maximum-firing rate of the stoker should be sufficient to carry the gross load. This rate may be determined by the same method as used for oil or gas.
CONTROLS FOR AUTOMATIC FUR-BURNING EQUIPMENT
Controls for the automatic fuel-burning equipment de scribed in this chapter are outlined here. The basic require ments for oil burners, gas burners and coal burners (stokers) are included and the term burner refers to all three types of fuel-burning equipment. Controls for these burners can be classified as operating controls, limit controls and primary controls. The schematic diagrams shown in Fig. 20 indicate the relationships of the basic components. The power supply may be line voltage for each type of bumeT. In control sys tems for domestic burners the line voltage may be reduced by means of a transformer for those portions of the circuits indicated by dotted lines. Such transformers' are usually built into the stoker and oil burner primary controls. Control systems for domestic gas burners frequently contain a sepiarate transformer as shown. There are domestic gas burner control systems which obtain their electrical power supply from the conversion of heat to low-voltage electrical energy, in which case no transformer would be required. As the burner sizes increase, the tendency to use ail line voltage controls increases in each of these general categories.
fig. 17 .... Coal Fuel-Burning Rate Chart
CROSS OUTPUT-THOUSAND-BTU VEft HOUR Thi* efairt abated upon No. JaO having* be*ieoste&ttf 143,400 Btu per (Al loa. II other trade* ol oil are need multiply the value obtained tram thk chart by following feetm: No. 1 ml (139.000 Btu per gallon) 1.033; No. 4 oil (144.500 Btu per gallon) 0.99S; No. tcil (140,000 Btu pergalkm) 0.983; and No. 0od (150,000 Btu per gallon) 0.950.
' fig. 18 .... Oil Fuel-Burning Rate Chart*
fig. 19 .... Gas Fuel-Burning Rate Chart
STOKER
OR. eURfCR
CAS BUHNER
(O =* Operating Control; P Primary Control; l = UmH Control) * fig. 20.... Schematic Diagrams of Some Typical Burner Control Systems
Automatic Fuel Burning Equipment
499
Operating Controls
Operating controls initiate the starting and stopping- of. the burner and on larger burners they usually vary the fuel and air input to the combustion chamber in response to varying load demands. For residential and small commercial heating plants with fuel inputs up to aproximately 500,000 Btuh, the operating controller is usually some form of room thermostat which automatically starts and stops the burner through the primary control as the limit controls piermit. As the sire of the heating system increases, the use of a. room thermostat as the operating controller for' the burner be comes less common. An insertion thermostat (for furnaces), immersion thermostat (for hot water boilers) or pressure controller (for steam boilers) may be appilied as an operat ing controller. Also, such devices as submaster and compen sated controllers (which are reset from outdoor temperature for governing the bonnet temperature in large furnaces or the water temperature in a boiler) come into more frequent use on the larger installations. The still larger burners are usually equipped to vary the rate of fuel and air input in response to varying load demands.
Limit Controls
limit controls guard against unsafe temperature, pressure or water level to assure that safe conditions prevail for the operation of the burner. Regardless 'of the type of fuel burned, draft controls increase combustion efficiencies and reduce flue gas loss by maintaining proper draft conditions at all times. For fuel input requirements above approxi mately 1,000,000 Btuh, some additional factors become common to all types of burners. For example, the draft in the firebox is controlled at a suitable constant for all firing rates, including the off period, by measuring the draft con ditions in the firebox and actuating a damper operator to position the damper at the boiler outlet. Where necessary, provision may be made to open the boiler outlet damper wide before permitting the burner to start and then "to-re turn this damper to automatic control after the burner has been started. Also, the firing rate of these larger burners is frequently automatically adjustable. Provisions are made for always starting the burner on its low firing rate, with facilities for increasing the firing rate slowly after the burner has been started. It is not recommended and codes seldom permit the use of one and the same -instrument as both an operating controller and a high limit control. In such cases an operating controller will be adjusted to control at the de sired set point while the high limit control will be adjusted to stop the burner at some higher point in the event that the operating controller fails to stopthe burner before the higher shut-ofl point is reached. For example, to maintain a constant water temperature in a hot water boiler, the operating con troller may be set to stop the burner when the boiler water temperature reaches 180 F. The high limit control should then be set to stop the burner at about 200 F.
Various interlocks or limit controls are usually included to assure safe operation of these larger burners. A latchswitch interlock prevents burner operation if the burner is not in its proper firing position. Another interlock must prove that the burner is in its low-fire position before the burner can be started. Safe draft conditions should be proved before the burner can be started or allowed to run, especially where induced draft fans are involved. A smoke detecting device may sound an alarm and stop the burner if excessive smoke is produced. Also, protection against electrical over loads must be provided.
Primary Controls
Primary controls provide for the safe start and operating procedure of the burner. They are somewhat different for each of the three types of fuel burners. - 1. Stokers. Stokers are equipped with refueling, or holdfire, controls. These primary controls cause the stoker to in termittently feed a predetermined amount of coal during the long off periods of the operating controller to maintain igni tion and' to reduce the possibility of having idle fuel beds damage stoker castings. In some cases the primary control system includes an out-fire feature which stops the feeding of coal into the firebox if the fire goes out.
2. Oil Burners. Primary controls required for oil burners depend on the size and type of burner. Some of the more common primary controls are discussed in following para graphs a to d.
a. Domestic oil burners of the vaporizing type usually re quire a primary control that* will (1) meter the correct amount of oil into the burner to maintain the pilot flame; (2) regulate the required amount of oil into the burner for its high flame operation; and (3) completely shut off.the flow' of oil in the event of a flame failure.
b. Domestic oil burners of the pressure-atomizing type require a primary control that will (1) energize the burner motor and electric ignition; (2) test for the establishment of main burner flame and stop the burner and ignition if flame has not been established; (3)- cut off the ignition after a safe burner flame has been established (does not apply to constant ignition type burners); (4) monitor the flame con tinuously during burner operation and stop the burner in the event of flame failure (manual reset is necessary follow ing a flame failure lock-out); and (5) stop the burner when either the.operaring controller or limit control requires it.
c. Commercial and industrial oil burners of the pressure atomizing type have primary controls that are essentially the same as those outlined for domestic oil burners of the pressure atomizing type. In addition, some models are equipped with'a solenoid oil-shut-off valve to provide a pre purge period, if desired, and a quick shut-off of the oil flow when the burner is stopped. . .
d. Commercial and industrial oil burners of the horizontal rotary-cup type are usually equipped with a more elaborate primary control system. The primary control is often de scribed as a programming combustion safety control. Its most important operations include (1) starting the burner upon a call for heat; (2) providing a pre-purge period before activating the gas-electric ignition; (3) proving the presence of proper ignition before permitting the flow of oil to the main burner; (4) proving the presence of a stable main' burner flame within a predetermined period of time; (5) shutting off the gas-electric ignition after a predetermined length of time has elapsed; (6) monitoring the main burner flame during its entire on period and stopping the burner quickly in the event of a flame failure (it is usually required that the flow of oil through the burner be stopped within four seconds following a flame failure); (7) stopping the flow of oil through the burner when either the operating controller or a limit control requires it; (8) operating the burner for a predetermined length of time after the main fuel valve has been closed; and (9) locking out on a flame failure shutdown (the programming control then must be manually reset prioT to a restart).
When steam-, air-, or mechanical-atomizing burners are