Document LK9dXk8Nq47m6nw4QOqmrgLnq
414
CHAPTER 17
1954 Guide
Tc = temperature of flue gas, Fahrenheit, absolute. W = flue gas flow rate, pounds per second. / = coefficient of friction. L = length of friction duct (approximately equal to H), feet. tD = minimum diameter of round chimney, feet. x and y = length and width of cross-section, of rectangular chimney, feet.
The following notes facilitate the use of Equations 3 and 4.
1. The barometric pressure, represented by Bo, is the actual pressure at the site of
the chimney and, not the pressure reduced to sea level datum. In general, the barometric pressure decreases approximately O.i in. Hg per 100 ft'
increase in elevationT
2. The unit weight of a cubic fool of chimney gases at 0 F and sea level barometric
pressure is given by the equation:
'
Wc = 0.131(70* -f 0.0950* + 0.0S3jVs
(5)
In this equation 00*, 0* and Nt represent the percentages of the parts by volume of the carbon dioxide, oxygen and nitrogen content, respectively, of the gas analysis.
For ordinary operating conditions, the value of We.may be assumed at 0.09.
The density effect on the chimney gases, $ue to superheated water vapor resulting from moisture and hydrogen in the fuel, or due to any air infiltration in the chimney1 proper, is disregarded. Though water vapor content is not disclosed by Orsat analy-' sis, its presence tends to reduce the actual weight per cubic foot of chimney gases..,
3. The atmospheric temperature is the actual observed temperature of the outside air at the time tne analysis of the operating chimney is made. The mean atmospheric
temperature in the temperate zone is approximately 62 F. 4. The chimney gas temperature decreases from the breeching connection to the top1
of the stack. This drop in temperature depends upon the material and construction1 of the stack, its tightness or freedom from leaks, its area, its height, and the velocity:
of the gases through it. The same chimney will suffer different temperature losses, depending upon the capacity under which it is working, and the variable atmospheric* conditions. No general equation covering all these variables has been suggested, but from observations on chimneys varying in diameter from 3 to 16 ft, and in height
from 100 to 250 ft, Equation 6 was deduced:*
Rfr-]3.13T
(6);'
where
.
Ti = temperature at the center of the connection from the breeching, Fahrenheit.
degrees, absolute.
.
Hb =* the height of the stack above center line connection to breeching, feet.. .
5.The coefficient of friction between the chimney gases and a sooted surface has. been taken by many workers in this field as a constant value of 0.016 for the condi tions involved. This value, of course, would be less for a new unlined steel stack than, for a brick or brick-lined chimney, but in time the inside surface of all chimneys, re-; gardless of the materials of construction, becomes covered with a layer of soot, a-,
thus the coefficient of friction has been taken the same for all types of chimneys a,.* generally constant for all conditions of operation. For reasons of simplicity a?? convenience to the reader, this constant value of 0.016 has been employed in the de .-
velopment of the various special equations and charts shown in this chapter.
In important large chimney design, especially when the construction or the xnat*7
rials are unusual, it is recommended that use be made of the Reynolds number.!?-
determining the friction factor, /.
-ri
The following problem illustrates the use of Equation 3:
-a
Example 1: Determine the available draft of a natural draft chimney 200 ft *?;-
Chimneys and Draft Calculations
415
height and 10 ft in diameter, operating under the following conditions: atmospheric temperature, 62 F; chimney gas temperature, 500 F; sea level atmospheric pressure, Bo = 29.92in. Hg; atmospheric and chimney gas density, 0.0863 and 0.09, respectively; coefficient of friction, 0.016; length of friction duct, 200 ft. The chimney discharges 100 lb of gases per second.
Solution: Substituting these values in Equation 3 and reducing,
D. = 2.96 X ^200 X 29.92 X /(0.--086-3-------0-.-0--9\1 ---0--.-0-0--1-2--6---X---1--0-0--2--X----9-6-0---X----0-.-0--1-6---X----2-0--0-
\ 522 960)
105 X 29.92 X 0.09
- 1.27 - 0.14 = 1.13 in.
Fig. 2 shows the variation in the available draft of a typical 200 ft by 10 ft chimney operating under the general conditions noted in Example 1. When the chimney is under static conditions and no gases are flowing, the available draft is equal to 1.27 in. of water, the theoretical intensity. As
Fig. 3 is a typical chimney performance chart giving the available draft for various gas flow rates and sizes of chimney. This chart is based on an
atmospheric temperature of 62 F, a chimney gas temperature of 500 F, a unit chimney gas weight of 0.09 lb per cu ft, sea level atmospheric pressure, a coefficient of friction of 0.016, and a friction duct length equal to the height of the chimney above the grate level. These curves may be used for
general operating conditions. For specific conditions, a new chart may be Prepared from Equations 2 or 4.