HEATING VENTILATING AIR CONDITIONING GUIDE 1944
toward the duct openings to the room. To find the total static pressure against which the fan must operate, the static pressure loss of each section must be calculated separately and the total loss found by adding the indi vidual losses of the various sections of the run having the highest resis tance. Usually this is the longest run but in some cases a shorter run may have more elbows, transformations, booster heaters, etc., which will cause it to have a higher resistance pressure. This method requires judgment and experience in choosing the proper velocities to approach equal friction for all lengths of run but many engineers believe that the velocity method is handier to use than other methods and will give satisfactory results for most practical applications. The air velocities given earlier in this chapter are helpful in choosing proper velocities. Adjustable dampers or splitters are used to regulate air quantities delivered.
Equal Friction Method
The equal friction method of design is sometimes preferred because it does not require nearly so much judgment and experience in selecting the proper velocities in the various sections of a system. The usual procedure in this method of design is to select the main duct velocity to be con sistent with good practice from a standpoint of noise for a particular type of building. This velocity should be less than the fan outlet velocity; All main ducts and branch ducts are sized for equal friction by the use of Fig. 2 and Table 1 or Fig. 4.
In cases where the fan or factory assembled air conditioning unit has a limited external resistance, it is necessary to divide the available resistance by the total equivalent length of the longest or most complicated run of duct to determine the resistance per 100 ft and then to size all ducts at this resistance value, which will automatically determine 4he duct veloci ties and give the desired total duct resistance. A further refinement which is sometimes used in large systems is to size each branch duct so that it has a resistance equal to the resistance of the main system at the point of juncture.. Even when this refinement isadded, regulating dampers are recommended in each branch.
After the duct system is designed the frictional resistance is calculated and tabulated together with the resistance of all component parts. The fan is then selected for the required volume of air, static pressure and outlet velocity.
Example 2. Fig. 6 shows a typical layout of an air distribution system which is applicable for ventilation of hotel dining rooms and offices. The volume of air in cubic feet per minute for the room is determined on the basis of the number of air changes per hour required. In the example shown, the room ventilated is a hotel dining room 135 ft x 85 ft x 15 ft. A 7^-min air change (8 air changes per hour) is assumed for proper ventilation, giving 22,935 cfm as the air required.
The free area of the outdoor air inlet is based on a velocity of 1000 fpm or 22,935 s1000 = 22.94 sq ft. The main duct velocity selected from Table 3 is 1250 fpm which gives a main duct area of 22,935 -h 1250 -- 18.354 sq ft (60 X 44 in.). From Table 1 a 60 X 44 in. duct is approximately equivalent to 56 in. diameter.
Referring to Fig. 2, a volume of 22,935 cfm through a 56 in. diameter duct gives a resistance of 0.028 in. per 100 ft. The amount of air to be handled by each section of pipe is shown in Fig. 6, and by locating each of these values on the 0.028 in. friction line, the round pipe sizes are obtained and then, referring to Table 1, the equivalent rectan gular sizes are selected as shown in Table 4.
608
CHAPTER 32. AIR DUCT DESIGN
Table 4. Pipe Sizes for Example 2a
Volume of Air (cfm)
22,935 12,510 10,425 8,340
6,255 4,170 2,085
Diameter of Pipe (Inches)
56 45 42 39 35 29.5 23
Equivalent Size of Rec tangular Duct (Inches)
60x44 58 x 30 50 x 30 42x30 42 x 24 30x24 30 x 15
aVelocity through grilles (not shown) to be approximately 300 fpm.
The pressure at the outlets nearest the fan will be greater than at the pipes farther along the run so that the former will tend to deliver more than the calculated amount of air. To remedy this condition, volume regulating dampers should be located at the base of each riser, or in each branch duct, and adjusted for proper distribution. At points where branches leave the main it may be advisable, depending upon the nature of the installation, to install adjustable splitters similar to that shown in Fig. 6 where the main
duct divides into the 58 x 30 in. and 50 x 30 in. brandies.
Resistance Losses for the System
w Outdoor air intake, 1000 fpm velocity (1.5 heads X 0.0625) (2) Filters (from manufacturer's tables)............................ .--........ (3) Tempering coil loss (from manufacturer's tables)__________ (4) Air washer loss (from manufacturer's tables)__________ ____ (5) Reheating coil loss (from manufacturer's tables)--...............
0.094 in. 0.250 in. . 0.074 in. . 0.250 in, . 0.083 in.
(6) Duct resistance:
The longest run is___ .-._______ ____________________ ________ = 150 It
Two, 58 x 30 in. elbows (150% ratio) ^
---............ = 126 ft
Two, 30 x 15 in. elbows (150% ratio) ^ * 12 ^................ = ft
Three, 15 x 30 in. elbows (75% ratio) ^ ^ ^ ^ --.......... = ^
Total equivalent run.--_________________ _____ -..........
472 ft at 0.028 in. per 100 ft----- --------------------------------- ---(7) Allowance for damper adjustment, 25% of 0.132------------
(8) Supply grille resistance (from manufacturer's tables).)-------
Total static pressure loss of system---------------------------
0.132 in. 0.033 in. 0.036 in. 0.952 in.
The fan is selected from the manufacturer's ratings to deliver 22,935 cfm at a static pressure of 0.952 in. as outlined in Chapter 30.
Example S. If the rooms and offices of the hotel building of Example 2 are to be served from a manufactured unit with a capadty of 22,935 cfm against an external resistance of 0.35 in., the known resistances are calculated as:
CD Outdoor air inlet__ ____________ ,---------------------------(2) Allowance for damper adjustment___..----- ,. (3) Supply grille resistance (from manufacturer's tables).
.. 0.094 in. . 0.033 in. , 0.036 in.
Total known resistance._______________________
. 0.163 in.
609