616 CHAPTER 41 1960 Guide up to a distributing system from which it runs down through the pads and back into the sump. A fan (usually included within the unit) pulls the air through the evaporative pad and delivers it to the space to be cooled. The spray-type cooler (see Fig. 7) contains an evaporative pad usually made of glass fiber, a water slinger, a centrifugal vaporizer, or spray nozzles to throw a fine spray into the air stream and the evaporator pads. Eliminators are usually re quired on the downstream side of the evaporator pads. These devices are supplied with or without the air-handling fan. The rotary-type cooler (see Fig. 8) is a device which con tinually wets and washes the evaporator pad by rotating it through a water bath and into the air stream. The evapora tor pads are usually of copper wire construction to provide the necessary structural and corrosion resistance. The air washers previously discussed in this chapter axe also used for direct evaporative cooling. Control of sump water within these evaporative coolers consists of a float valve for level control and a bleed-off de vice. Overflow stand pipes, automatic valves or recirculating pump bypass connections are used for bleed-off. An evapora tive air cooler operating with an efficiency of 80 percent is generally considered optimum. In this case, efficiency is the same as humidifying or saturating effectiveness found from Equation 1. Design Considerations Various methods for designing evaporative coding systems are in common use. Simplified rule of thumb methods use an assumed air change rate as a basis. Good engineering practice requires an evaluation of the building heat gun, internal loads, and the cooling season wet-bulb temperature pattern. The suitability of evaporative air conditioning for a par ticular application is, in the first instance, determined by the climatic conditions. The lowest temperature theoretically attainable with the most common systems of the direct or single-stage type is that of the wet-bulb temperature of the entering air. The process is one of adiabatic saturation and in practice is almost always operated with 100 percent outdoor air. Since the lowering of the dry-bulb temperature of the air during the evaporative process is always accompanied by a corresponding increase in moisture content, it follows that the greatest application of evaporative cooling for con ditions for human occupancy is in areas in winch periods of high temperature are always accompanied by low outdoor relative humidities. The areas in which the climate is suit able for the reliable production of optimum comfort condi tions by evaporative cooling are limited. Despite this, evap orative air conditioning is extensively used over areas with less favorable climates as a means of improving conditions for human occupancy. It finds wide application also in in dustrial applications, particularly in those in which an im provement of dry-bulb temperatures can be used to advan tage, and in which high humidities are desirable or at least not objectionable. Proper analysis of the cooling season climatic data is most important. The most acceptable approach appears to be based on an analysis of the average high wet-bulb tempera tures of tiie area for the periods when cooling is needed. Cri teria established on baas must, of necessity, take into account the extent to which departures from optimum condi tions both in degree and duration can be tolerated. There is no latent heat load on evaporative cooling equip ment as with refrigeration cooling', since it operates on a 100 percent outdoor air basis. The air quantity handled by a typical evaporative cooling system is higher than with re frigerated cooling or heating systems. These relationships ean be seen by comparison of Example 1 with the sample airconditioning cooling load calculation, Example 11 of Chapter 13. Example 1: An evaporative cooling system is to be installed in the one-story office building shown in Fig. 6 of Chapter 13. Outdoor design conditions are assumed to be 05 F dry-bulb and 65 F wet-bulb. The heat gains, calculated in Example 11 of Chapter 13, which are used in the design of this type of system are: All walls, roof and doors Glass areas Occupants lighting 78,500 Btu/hr 5,970 17,000 62,700 Total sensible heatload = 164,170 Btu/hr Find the required air quantity, the temperature and humidity ratio of the air leaving the cooler (entering the office), and the temperature and humidity ratio of the airleaving the office. Solution: A temperature rise of 10 F deg in the cooling air is assumed. Equation 20 from Chapter 13 may then be used to cal culate the air volume required to be supplied by the evaporative cooler: Qr <! 1.08(1.- - 1.) 164^30 = 15,200 cfm 1.08 X 10 where Q,, -- required air quantity through equipment, cubic feet per minute. q, = instantaneous sensible beat load, Btu per hour. tj -- indoor oit dry-bulb temperature, Fahrenheit. 1. -- room supply air dry-bulb temperature, Fahrenheit. This air volume rate represents a 2.6 minute air change for a building of this size. The evaporative air cooler is assumed to have a saturating effectiveness of 80 percent. This is the ratio of reduction of the dry-bulb temperature to the wet-bulb. The dry-bulb tem perature of the air leaving the evaporative cooler is found from Equation 3: t* - ti - e(t, - l') (3) For the conditions of this problem Equation 3 becomes: t, - 95 - 0B(95 - 65) f* - 71 F The humidity ratio of the cooler discharge W, is found from the peychrometric chart Wt = 0.01185 lb per lb dry air. Equation 8, Chapter 13, may be adapted to solve for the remaining unknown, the humidity ratio of the air leaving the space being cooled W,, from Equation 4: q. - Qr, X 4S40(IF, - HO) (4) where q, = latent load, Btu per hour. Qr, = rate of entry of air to the space from the cooler, cubic feet per minute. Evaporative Air Cooling and Humidificarion 617 The humidity ratio of the air leaving the space, Wt, from Equation 4, is therefore: ,W q + Wt <?,, X 4840 The only latent load of the space for .this design is the occupancy load, 21,250 Btu/hr as calculated in Example 11 of Chapter 13. Substituting this and the other known quanti ties in Equation 4: ^ " s.Jf'tsTo + 001185 " 001214 ,b/Ii> dr" The remaining values of wet-bulb and relative humidity for tbe problem may be found from the psychrometric chart. Fig. 9 illustrates the various relationships of the outdoor air, supply air to the space, and the discharge air. AIR TEMP. THRU COOLER MDB^ AIR TEMRERATU itS THRU COOLEO SR CC 7lD___------- 7808 aaawe 0 cu 5 $ hi s I is * i). i 8a $ s *$ u t s 1 3 \ Rg. 9 .... Conditions Within Evaporative Cooler and Cooled Space for Example 1 The design of evaporative air-cooling systems is similar to other heating or cooling systems. It should be kept in mind that considerably more air will be handled as no recircula tion is used and, therefore, duct, fan, and grille sizes will be larger. This problem has been solved in a number of ways. Large, open buildings such as supermarkets have been suc cessfully cooled and heated by the use of four evaporative air coolers for cooling, two of which are fitted with duct heaters for space heating. In this way a balance between tbe summer cooling and winter heating air quantity is obtained. In di mates which are not particularly suited to direct evaporative air cooling, a combination of refrigeration and evaporative cooling may be economical. There are many industrial demands for cooling where direct evaporative cooling is economical. Successful applica tion of this type has been made for electric-motor cooling, turbine cooling, and spot cooling in the factories such as tex tile mills, steel mills, and foundries. Laundries, with their large exhaust air loads, may also take advantage of evapora tive cooling. In cattle and poultry barns evaporative cooling has been used with excellent results even in dimatom which give poor results with human occupancy. This is possible be cause the blood temperature of these animals is higher than human.* Greenhouses use evaporative cooling to reduce tem perature and raise humidity. Two Stage Evaporation Air Cooling On industrial or commercial installations two stage evap orative cooling will sometimes be found to be effective and economical. Such a system uses a cooling tower and a blast coil ahead of the evaporative air cooler. Using a 6 or 8 row coil and a well designed cooling tower, the air discharged from the blast coil can be within 15 F of outdoor wet bulb. This part of the cooling takes place at constant humidity ratioPassing the cooled air through an evaporative air cooler fur ther reduces the dry-bulb temperature, the process following the thermodynamic wet-bulb temperature line on the psy chrometric chart. Use of this two stage system will result in smaller required air quantities and consequent low duct costs. Careful design can frequently allow the mwc duct and grille system to be used for heating and maintain proper duct and register velocities. Control of Evaporative Air Coolers Control of evaporative air-cooling systems may be accom plished by ordinary dry-bulb thermostats or a combination of a. dry-bulb thermostat and a humidistat. These controls are set to turn on at a dry-bulb temperature and off at a pre-set high humidity. When two-speed fans are used, auto matic control of fan speed may be employed to provide bet ter control results. Evaporative air-cooling systems can also be used for ven tilation on mild days and at night when air temperatures are relatively low and straight ventilation produces comfortable results. A valve on the water supply to the evaporative air cooler may be operated by a thermostat in the outdoor air to accomplish this automatically. See Chapter 43 for general information on controls. Maintenance Much of the discussion of maintenance and operation prob lems at the end of Chapter 40, Evaporative Apparatus for Heat Rejection, is pertinent to evaporative air cooling and humidification equipment as all these devices use the evapora tion of Water as the COOling Tnftp-hftTnsm Some air washers and all evaporative air coolers contain ex tended surface, evaporator pads of one sort or another. Be cause of these pads, control of the scale-forming mineral con tent of the water ia required or the extended surface pads will soon plug up with scale and the air flow will be reduced. Another effect of scale deposit is to cause channeling of the water and air and so give local high velocities and consequent entrainment. Some scale will be deposited on these pads dur ing drying after shut-down. If replacement or cleaning is re quired more frequently than once a year the scale control method is usually at fault. Chemical water treatment with polyphosphates is helpful to prevent hard scale. Regular blowdown or bleed-off of sump water is usually the best con trol to prevent corrosion and hard scale deposit. REFERENCES 1W. D. Collins: Temperature of water available for industrial use in the United States (U. S. Geological Survey Water Supply Paper No. 520 F). *Air conditioning in Iran (Heating and VentUatma. June 1947, p. 93). *D. L. Fiske: Refrigeration is not new (Refrigerating Engineenng, October 1932, p. 201). 4 George Cecil: Keeping cool in India (The Heating and Ven tilating Magazine, June 1927, p. 61).