Document LJMBYYN72pvEBGymBKE0gBXdb

564 CHAPTER 31 1965 Guide And'Datc Book and the pressure loss at BC are termed dynamic fosse*, and are characterized by being essentially independent of Reyn olds number. Dynamic losses occui\ because of changes in the direction or velocity of the air, and hence occur at duet transitions, bends (elbows), and obstructions such as damp ers. As will be shown later, dynamic losses can be specified in terms of a constant times the velocity pressure at a cross* section under consideration. '' Beginning at Section E the velocity pressure is constant, and the static and total' pressures again decrease, uniformly due to wall friction. The static' pressure at F is zero, as referred to the atmosphere. The total pressure is the velocity pressure and is a measure of the kinetic energy of the'stream as it discharges from the duct. The distinction between static and total pressure is im portant because the former is conventionally-used'as. the basis for system design, but the latter determines the actual mechanical energy that must be supplied to the system. Note in Fig. 1 that the static pressure.decreases and then increases ; in the direction of flow. Moreover, it even becomes negative; - (below atmospheric). Therefore, in dealing with static pres sures, distinction must always be made between static pres sure loss (Section AB) and static pressure change as a result of conversion of velocity pressure (Section BC). FRICTION LOSSES The air friction chart is based on standard air with a den Pressure drop in a straight duct is caused by surface sity of 0.075 lb per cu ft, flowing through average, chan, friction, and tins friction loss is most readily, calculated by . round, galvanized metal ducts having' approximately 40 means of the Air Friction Charts (Figs. 2 and 3) covering'. joints per 100 ft. Fig. 2 should not be used to obtain values volume ranges of. 10 to; 2000 cfm, and 1000 to 400,000 cfm,' ' below the charts by extrapolation,! because, critical flow respectively. These charts were developed by the ASHRAE - would occur in this region and values so obtained would be Research laboratory.1' % unreliable. The charts were constructed from the basic flow.equatiori 1 .. Variations in air temperature of .'the order' of 20 deg for the pressure Ices in circular ducts: . from 70 F affect duct friction very li^tie. Figs. 2 and 3 can tcAere ' "'-'(t;)"- therefore be used for all air systems with temperatures from /' <4>. 50 F to 90 F.1 For systems.carrying-air at much higher tem; peraturea, however, the values found.'in the charts must be . j corrected.* To determine the friction loss in.such systems, the B( head loss due to friction, inches of water. ' actual flow rate or velocity existing at the nonstandard con / -- a nondimenskmal friction coefficient,-which for-air- ditions must be used. . conditioning work depends upon Reynolds number and Changes in humidity, the usual changes in barometric the relative roughness of the conduit. Approximate' presure, or changes in the pressures required to circulate the values of / were taken from the work of Moody* where air through the systems have little influence on duct friction e " 0.0005 ft. (See Chapter 6, Fig. 5, Relation Between and can be disregarded in calculating,friction losses in ordi- Friction Factor and Reynolds number.) It is numeri ' nary air-flow systems.1 For'unusual conditions, the friction cally equal to the reciprocal of the number-of duct values obtained from Figs. 2 and 3 must be corrected.* diameters required to cause a pressure loss equivalent For ordinary applications, an excellent approximation for to one velocity pressure. nonstandard temperatures is: I -- length of conduit, feet. D ~ inside diameter of conduit, feet. . A. - Kh.. (5) H, = velocity pressure of mean velocity, inches of water. where A* TM friction loss under actual operating conditions, inches of water. h, ? friction loss obtained from Figs. -2 and 3 using the ac tual flow rate or velocity existing under the nonstand ard conditions, inches of water..\ K friction loss correction factor, obtained from Fig. 4, dimensionless. For ducts of other than standard sheet-metal construction, correction factors may be obtained from. Figs. 5 and 6. The correction factors shown in Fig. 5 were computed for the value of e, the roughness in feet, shown in Table 1.* Most . ductwork today is fabricated from galyanixed-steel or alumi num alloy,"or flexible tubing. Fibrous^ glass ducts have re cently been introduced for low velocity applications. Fig. 6 -presents in graphical form-the recommended correction fac- Air Duct Design 565 m r- A.. - 0.835 X 0.77 - 0.64Tn. per 100 ft. v.=:.i The friction loss for 75 ft is then 0.75 X 0.64 -- 0.48 in. CIRCULAR EQUIVALENTS OF RECTANGULAR DUCTS An air-handling system is usually sized first for round ; ductsi -Then, if rectangular ducts are desired, duct sixes are selected to provide flow rates equivalent to those of the round ducts originally selected.' A comprehensive study at the ASHRAE Research Labora- Fig. 6...: Correction Factors for Aluminum Duct - toiy proved that, for most practical purposes, rectangular ducts of aspect ratios not exceeding 8:1 will have the.same - friction pressure loss for equal lengths and mean velocities of flow as a circular duct of the same hydraulic diameter. When tore 'for aluminum ductwork.4 The correct1 friction loss for ducts of other than standard sheet-metal construction may be determined by multiplying the losses obtained from Figs. 2 duct sizes are expressed in terms of hydraulic diameter, and . when equations for friction loss in round and rectangular -ducts are equated for equal-flow rate and equal length,- Equation 6, giving the circular equivalent, of a rectangular and 3 by the factors found in Figs. 5 and 6. Accurate experimental data on the absolute roughness for : duct, is obtained.* flexible tubing are not yet available. There is also .little in- , ' formation on the friction loss in fibrous glass ducts or ducts (ob)#,M* . j , (ab)* (6) linpH with acoustical material. Until definite information is available, it'is recommended that the correction factor for very rough pipes be used for uncovered material, and the fac tor for medium roughness be used for material behind per forated metal. ` where a -- length of one side of rectangular duct, inches. ; b -- length of adjacent side of rectangular'duct, inches. de -- circular equivalent of a rectangular duct for equal friction and capacity, inches. Example 1 illustrates the use of Fig. 3 to determine friction - ; Table 2 gives the circular equivalents of rectangular ducts loss in a galvanized sheet-metal duct. Examples t, S, and 41 : for equal-friction and flow rate for aspect ratios not greater illustrate the use of Figs. 4, 5, and 6 in applying.correction; than 11.7:1, based on Equation 6.* Note that the mean factors for ducts of other than sheet-metal construction and' velocity in a'rectangular duct will be less than in its circular for air at high temperature. Example I: Determine the friction loss when circulating 10,000 cfm of air at standard density through 75 ft of 24-in.;- diameter gahranized steel duct. /, . :- Solution; Find 10,000 cfm on the' left scale of Fig. ;3 and.' move horizontally to the right to the diagonal line marked 24 in. The'other intersecting diagonal shows that the velocity m the:' pipe is 3200 fpm. Directly below the intersection, the friction per: 100 ft is 0.50 in'.; then for 75 ft the friction.wOl be 0.75 X 0.50! *= 0-38 in. In a like manner, any two variables may be determined by-the--intersection of the' unea'representing the other, two'.. variables. equivalent. Multiplying or dividing the length of each side of a duct by a constant is the same as multiplying or dividing the equivalent round size by the same, constant. Thus, if the cir cular equivalent of an 80 X 24 in. duct i3 required, it will be twice that of a 40 X 12 in. duct, or'2 X 23.0 -- 46.0 in. DYNAMIC LOSSES ' - Wherever eddying flow is present, brought about by sudden changes in the direction or magnitude of the-velocity of. the Example t: If,the duct in Example 1 is very rough, not galvan .air flowing, a greater, loss in pressure takes place than would ized steel, with 40 jdinta per 100 ffci And the total friction. ! f . - - occur in a steady'flow through a similar length of straight Solution;..On Fig. 5 And (by interpolation between 12-in. and .' 40-in. pipe) the intersection of the 24-in. very rough pipe line and the 3200 fpm velocity ordinate, and at the left margin read" a correction factor of 2. The friction Ices in the rough duct is - therefore 2.X 0.38 =* 0.76 in.. . duct having a uniform cross-section. The amount of this loss in excess of straight-duct friction is termed' dynamic loss. Although dynamic losses may be assumed to be caused by changes in area actually occupied by the air flow, they are Example '3: IS the duct in Example / is made of aluminum, instead of galvanized steel, find the total friction..' - divided into two general classes for convenience: (1) those caused by changes in direction of the duct and (2) those caused Soluluni; On Fig. 6 find (by interpolation between 12-in! and by changes in cross-sectional area of the duct. 36-in. pipe) the intersection of the 24-in. line and the 3200-fpm velocity ordinate, and at the left margin read a correction factor ' of 0.91. The friction loss in the "aluminum duct-is therefore'. 0.91 X 0.38 *= 0.35 in. Example 4' Determine the friction loss `in the duct -of Ex ample 1, if the temperature of the air transmitted through the duct is 200 F.- Solution: For ( * 200 F, the density of the air is pc " 0.060 >o per cti ft. Hence, the actual air-flow rate in the duct is: 5 Table 1 : 1. Value* of Roughness e for Different Pipes* Dvgro* - Pip* of Roughness Rovsfanen in feet: 10,000 X 0.075 , Q' 0.060 ,. 12,500 cfm and the actual velocity: 12,500 4,000 fpm 3.14 With Qc = 12,500 and D = 24 in., find A, = 0.77 in. of water per 100 ft in Fig. 3 and K " 0.8?* A under actual operating conditions ii Drawn Tubing................................ New Steel or Wrought Iron Pipe.. Galvanized Steel....................... r- - Average Concrete.......................... Average Riveted Sted................... Very smooth Medium smooth Average' Medium rough Very rough. 0.0000015 0.00015 0.0005 0.003 0.01 -