HEATING VENTILATING AIR CONDITIONING CUIDE 1942
conditions. In addition to this vacuum control, a float control is included which will automatically start the pump whenever sufficient condensation accumulates in the receiver, regardless of the vacuum on the system. A selector switch is usually provided to allow operation at night as a con densation pump only, also to give manual or continuous operation when desired.
There are several variations in the control of the vacuum maintained on the system by the pump. In some sub-atmospheric systems where orifices are used, the vacuum pump control maintains a pressure difference between the supply and the return piping, which is held within relatively close limits. There are other sub-atmospheric systems which utilize special temperature-pressure actuated controls for maintaining the desired conditions in the return lines. Where various zones are connected to the
Fig. 17. Method of Discharging High-Pressure Apparatus into Low-Pressure Heating Mains and Vacuum Return Mains through a Low-Pressure Trap
same return main, the return vacuum must be controlled to meet the. requirements of the zone operating at the lowest steam supply pressure.
Piston Displacement Vacuum Pumps Piston displacement return vacuum heating pumps may be either elec
tric or steam driven. They should be provided with mechanical lubricators and their piston speed in feet per minute should not exceed-20 times the square root of the number of inches in their stroke. They are usually supplied with an air separating tank, open to atmosphere, placed on the discharge side of the pump and at an elevation sufficiently high to allow gravity flow of the condensate to the boiler. If the boiler pressure is too high for such gravity feed then an additional steam pump for feeding the boiler is desirable. The extra pump is sometimes avoided by using a closed separating tank with a float controlled vent. In both arrangements, the air taken from the system must be discharged against the full dis charge pressure of the vacuum pump. In the case of high or medium pressure boilers, it is better to use the atmospheric separator and the second pump.
282
CHAPTER 14. STEAM HEATING SYSTEMS
In figuring the required displacement for such pumps, a value of from 6 to 10 times the volumetric flow of condensation is used for average
vacuums and systems.
TRAPS
Traps are generally classified as to function as (a) separating traps, (b) return, lifting or vacuum traps, and (e) air traps. Separating traps may be either float operated, thermostatically operated, or float and thermostatically operated. Return traps for low pressure service are referred to later as alternating receivers in this chapter. Return traps may also operate to receive condensate under a vacuum and return it to atmosphere or a higher pressure. Air traps are generally float operated.
Separating traps are used to release water of condensation but to retain steam. The thermostatic, and float and thermostatic types release both condensate and air but retain steam. Separating traps are used for draining condensate from radiators, indirect air heaters, steam piping systems, - kitchen equipment, laundry equipment, hospital equipment, drying equipment and many other kinds of apparatus. Air traps release air but retain water. Devices known as air vents are, in principle, traps which allow the passage of air but prevent the passage of either water or
steam. Return traps are used for returning condensate either by gravity, by
steam pressure, or by both, to a boiler or other point of disposal, and for lifting condensate from a lower to a higher elevation, or for handling condensate from a lower to a higher pressure.
The fundamental principle upon which the operation of practically all traps depends is that the pressure within the trap at the time of discharge shall be equal to, or slightly in excess of, the pressure against which the trap must discharge, including the friction head, velocity head and static head on the discharge side of the trap. If the static head is in favor of the trap discharge it is a minus quantity and may be deducted from the other factors of the discharge head.
Traps may also be classified according to the principle of operating device which supplies the power to cause them to function as (1) float, (2) . bucket, (3) thermostatic, (4) float and thermostatic, (5) impulse, or
(6) tilting traps.
Float Traps. A discharge valve is operated by the rise and fall of a Boat due to the change of water level in the trap. When the trap is empty the float is in its lowest position, and the discharge valve is closed. A gage glass indicates the height of water
in the chamber. Unless float traps are well made and proportioned there is danger of considerable
steam leakage through the discharge valve due to unequal expansion of the valve and seat and the sticking of moving parts. The discharge from a float trap is usually con tinuous since the height of the float, and consequently the area of the outlet, is propor
tional to the amount of water present.
Bucket Traps. Bucket traps are of two types, the upright and inverted, and although they are both of the open float construction, their operating principle is entirely different In the upright bucket trap, the water of condensation enters the trap and fills the space between the bucket and the walls of the trap. This causes the bucket to float and forces the valve against its seat, the valve and its stem usually being fastened to the bucket. When the water rises above the edges of the bucket it flows into it and causes it to sink.
283