CHAPTER 14
1946 Guide
above grade should be based on outside temperatures and the proper airto-air coefficients. Heat loss through basement walls below grade should
be based on the floor and wall coefficients for surfaces in contact with the soil and on the proper ground temperature.
TRANSMISSION HEAT LOSS
The basic formula for the loss of heat by transmission through any -surface is given in Equation 3.
where
Ht - A U (t - <o)
J
(3)
Ht :: heat loss transmitted through the wail, roof, ceiling, floor or glass, Btu' per
hour.
,
A = area of wall, glass, roof, ceiling, floor or other.exposed surfaces, square feet.
U = coefficient of transmission, air to air, Btu per (hour) (square foot) (Fahrenheit
degree temperature difference) (Chapter 6).
t = inside temperature near surface involved* which may not .necessarily be the
so-called breathing line temperature,. Fahrenheit degrees,
to =r outside temperature, or temperature of adjacent unheated space or of the ground,- Fahrenheit degrees. *
Example 8. Calculate the transmission loss through an 8 in., brick wall having an . area of 150 sq ft if the inside teinperature (/) fa 70 F and the outside temperature (to) fa --10 F.
Solution. The coefficient of transmission ( U) of a plain 8 in. brick wall fa 0.50 (Chapter 6, Table 7). The area (A) is 150 sq ft. Substituting in Equation 3:
Ht = 150 X 0.50 X 170 -- ( -- 10)1 = 6000 Btu per hour.
Transmission Loss, Through Ceilings and Roofs
The transmission heat loss through top floor ceilings, attics and roofs may be estimated by either of two methods:
1. By substituting in Equation 3 the ceiling area (4), the inside-outside temperature difference, (/ -- to) and the proper value of (U):
a. Flat roofs. Select the coefficient of transmission of the ceiling and roof from' 1 Tables 14 or'15, Chapter 6, or use appropriate coefficients in Equation 1 if side
walls extend appreciably above the ceiling of the floor below.
b. Pitched roofs. Select the combined roof and ceiling coefficient from Table 17, Chapter 6 or calculate the combined roof and ceiling coefficient by means of Equation 5, Chapter 6, where this formula fa applicable as explained in Chapter 6.
2. By estimating the attic temperature (based on the inside and outside design tem perature) by means of Equation 1, and substituting for to in Equation 3, the value of to thus obtained, together with the ceiling area (A) and the ceiling coefficient (U). This applies to pitched roofs. In the case of flat roofs it fa not necessary to calculate the attic temperatures as the ceiling-roof heat loss can be determined as per paragraph la.
INFILTRATION HEAT LOSS
The infiltration heat loss includes-(1). the sensible heat loss or the heat required to warm the outside air entering by infiltration and (2) the latent heat loss or the heat equivalent of any moisture which must be added.
Sensible Heat Loss
-
The formula, for the heat- required to warm the outside air which '
enters- a room by infiltration to the temperature of. the room,, is given in Equation 4.
Heating Load
267
where
;
Ht = 0.24 Qd (t - to)
-..
, (4) ..
Ha = heat required to raise temperature of air leaking into building from to to t, Btu per hour,
0.24 = specific heat of air.
Q = volume of outside air entering building, cubic feet per hour (see Chapter 8). d = density of air at temperature to, pounds per cubic foot.
It is sufficiently accurate to use d = 0.075 in which case Equation 4
reduces to
H, - 0.018 Q (t - to)
(4a)
The volume of outside air entering per hour ( depends on the wind velocity and direction, the width of crack or size of openings, the type of openings and other factors, as explained in Chapter 8. Where the crack method is used for estimating leakage, it is more convenient to express the air leakage heat loss in terms of the crack length:
Ha = 0.018 QL(t -- to) = B L (t -- to)
(4b)
where
B = air leakage per (hour) (foot of crack) (Chapter 8) for the wind velocity and type of windows or door crack involved multiplied by 0.018.
L = length of window or door crack to be taken into consideration, feet.
Example 4. What fa the infiltration heat loss per hour through the crack of a 3 x 5 ft
average, double-hung, non-weatherstripped, wobd window, based on a wind velocity of 15 mph? Assume inside and outside temperatures to be 70 F and zero respectively.
. Solution. According to Table 2, Chapter 8, the air leakage through a window of
this type (based on VjJ in. crack and %-t in. clearance) fa 39 cu ft per foot of crack per hour. Therefore, B = 39 X 0.018 = 0.70. The length of crack (L) is (2X5) +
(3 X 3), or 19 ft; t = 70 and to -- 0. Substituting in Equation 4b,
Hs = 0.70 X 19 X (70 - 0) = 931 Btu per hour.
Crack Length to be Used for Computations .
The amount of crack' used for computing the infiltration heat loss should not be less than half of the total crack in the outside walls of the room. For a building having ho partitions, whatever wind enters through the cracks on the windward side must leave- through the cracks on the leeward side. Therefore, take one-half the total crack for1 computing
each side and end of the building. In a room with one exposed wall, take all the crack; with two exposed walls, take the wall having the most crack; and with three or four exposed walls, take the wall having the most crack; but in nb case take less than half the total crack.-
The total infiltration loss of a building having partitions will not be
equal to the sum of the infiltration losses of the various rooms, since at-
any given time infiltration will take place, only, on the windward side or
sides and not on the leeward side. Therefore, if a building has more than
one room which is divided by interior walls or partitions, it is sufficiently
accurate to use half of the total infiltration losses for determining the
total heat requirements.
. .'
Latent Heat Loss
When it is intended to add moisture to air leaking into a room for .the maintenance, of proper winter comfort conditions, it is .necessary to