Document KRmyqbp6yYryLaxQbBVxQrX12
u/
American Society of Heating and Ventilating Engineers Guide, 1937
Table 6. Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets and Urinals
(Riser No. 2. Fig. 4)
Floor of
Bldg.
1st
2nd
Fixtures on
Fux>r
1 w. c.
2 W. C. 3 U. 1 Lav.
Gpm PER Fixture
45
45 30
3
Maximum Gpm on
Floor
45
90 30
3
Maximum Gpm
ON Riser
Probable Use
(per cent;
45 100
Probable Demand
Riser Gpm
45
Allowable Drop
Lb per 100 Ft
30
Pipe Size In.
123
168
58
98
3rd
4 W. C. 2 U. 3 Lav.
45 30
3
180 60 9
30 1 %
4th
4 W. C. 2 U. 3 Lav.
45 30
3
249
180 60 9
417
31 130
30 2 --------------
5th
6 W. C. 4 Lav.
45 3
249
270 12
666
24 160
30 2 --
6th
6 W. C. 4 Lav.
45 3
282
270 12
948
19 180
30 2 -------------- -
7th
6 W. C. 4 Lav.
45 3
282
270 12
1230
16 396
30 2H
8th
6 W. C. 4 Lav.
45 3
282
1512
270 12
282 . 1794
14 211 12 215
30 2X 24
Then the allowable drop per 100 ft will be 25.6 1b X 3o0u0u
100
= 8.5 lb and the s!izes shown
in.Fig. 5 are based on this amount of drop. Of course the other risers will have the same
maximum flows at the bottom as they formerly had at the top, namely 215 and 122 gal,
respectively, for Risers Nos. 2 and 3. Combining these maximum flows in the same man
ner as pursued in the down-feed system it is seen that the maximum flow between Riser
No. 2 and Riser No. 3 is 255 gpm, and between Riser No. 3 and the street main, 282 gpm
which at a drop of 8.5 lb gives the main sizes indicated. It will be noted that in determin
ing the maximum flow in an up-feed riser it is necessary to begin at the top floor and
work down instead of beginning at the bottom floor and working up as was done in the down-feed sizing.
Chapter 35--Water Supply Piping and Water Heating
Table 7. Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets and Urinals
(Riser No. S. Fig. 4)
__ --
Floor
of
BLDG.
Fixtures
on Floor
1st 1 S. S.
2nd
3 W. C. 1 Lav.
3rd 2 Lav.
4th
3 W. C. 1 Lav.
1 S. S.
5th 1 s. s. 6tb 1 s. s. 7th 1 s. s. 8th ' 1 s. s.
Gpm per Fixture
4 45 3
3 45 3 4
4 4 4 %4
Maximum Gpm on
Floor
4
Maximum Gpm
on Riser
Probable Use
(per cent)
Probable Demand Riser Gpm
4 100
4
Allowable Drop
Lb per
100 Ft
30
135 3
138 142
63
6 148 . 61 .
89 90
30 30
135 3
4
142 290 4 294 4 298 4 . 302 4 306
41 41 ; 40 40 40
119'
120 120 121 122
30 30 30 30
2
Pipe Size In.
H
1M 1M
i
2 2 2 2
3
required that a gravity circulation be kept up in such hot water lines and
this often has a considerable influence on the size. There are three
methods of arranging circulation lines, as follows:
.
1. By using the plain up-feed with a return carried back from the top of the riser and
paralleling it.
2. By carrying a supply riser up in one location thus supplying fixtures on up-feed,
then crossing over at the top and coming down past another collection of fixtures and supplying these by a down-feed.
3. By carrying all of the water to the top of the building and dropping risers wherever
needed, feeding all hot water on a down-feed system.
>
Table 8: Size of Distribution Main for Down-Feed Systems (See Fig. 4)
Riser No.
1 2 3
Maximum Gpm Riser
1038 1794
306
Maximum Gpm Main
1038 2832 3138
Probable Use
(per cent)
18 9 9
: Probable Gpm
Allowable Drop
Lb per 100 Ft
187 255 282
2 2 2
Sub of Main In.
* '
4 4 5
j *s
I,
j | f
| j I f | j
j f J i *
SIZING UP-FEED AND DOWN-FEED HOT WATER SYSTEMS
Hot water supply systems, when of the circulating type, have a few differences to be-considered although the same general principles of sizing apply to these lines as to the cold water lines. Owing to the fact that .there are no flush valves'on the hot water piping and also because many plumbing fixtures have no hot water connections, the sizes of the hot water piping in general will be considerably less than the cold water piping in the same building. On the other hand it is almost invariably
656
In the first instance the up-feed riser may be sized for the same pressure drop as used for the cold water riser and, from the top of the riser just below the top fixture connection, a return circulation line may be carried'" back to the main return line ip the basement .and connected through a check valve, set on a 45-deg angle, and a gate valve; these return circu lation lines should nevec.be less than % in., and on the farther half of the risers, not less than 1 in. to favor circulation in the far end. ' Typical top and bottom connections for such risers are shown in Tig. 6.
657
J\