Document KR1ZvaQmNQxZOR9OQR6ZLq856
American Society of Heating and Ventilating Engineers Guide, .1928.
greatest diameter at the top. It will be seen that 35 ft. elevation will give the necessary 15 lb. pressure at the highest fixture and that the pressure drop niay be made equal to the static head from the top fixtures down, or 40 lb. per 100.
FRICTION IN ELBOWS
Friction caused by elbows should be added to straight pipe friction. Each elbow in a line will add friction equal to a length of straight pipe
forty times the diameter of the pipe:
Pipe Size-.......................... % 1
Equivalent length of straight pipe in feet. 2.5 3.3
1)4 4.1
l'A 2 5 6.7
2A 8.3
3 3A 4 10 11.7 13.3
The water supply formula herewith makes it possible to accurately compute the flow of water in gallons through any pipe with any friction head and also gives formula for the additional head due to water entering the main, which, if extremely accurate calculations are necessary, should be added to the head required for friction; generally, however, this can
be neglected as it is comparatively small.
WATER SUPPLY FORMULA
CF = Cu. ft. per min. discharged G Gal. per min. discharged H = Friction head of water in feet = pressure X 2.31; if water is raised vertically,
deduct number of feet raised, from head due to pressure. L = Length of pipe in feet--including horizontal and vertical runs.
CF - 0.16
G -- 1.2 y<")'X3 H (1) (2)
(CF)' X L ~ .0768 (3d)5
,, (G)'XI (3) a 4.32 (3d)5
(4)
The above formula neglects the head due to entry, which need not be computed except when L is very short. Hi = head due to entry in feet.
\
Example.--Required the discharge of a 2 in. main with pressure 30 lb. 100 ft. hori
zontal run and 30 ft. vertical run.
,,
H = 30 X 2.31 -- 30 = 39.3. Formula (2) G = 1.2 `l
X 3 X 39.3 = 100.8
10(0 + 30
In ,the above case the head due to entry would be Hi
/0.83 X 100.8V = 2.56 ft. V 2 X 2 X 13 /
Usually this can be neglected, except for very close calculations. 152
Chapter VI--Piping for Water Supply Systems
HOT WATER SUPPLY
Tables 7, 8 and 9 give the hot water requirements for several kinds of buildings in terms of gallons per maximum hour and per day.
Pipe sizes for hot water systems may be calculated from the foregoing data on cold water systems; using the same quantities for the gallons of hot water required per min. as is given for the cold water. It may be borne in mind that a column of hot water is lighter than one of cold water amounting to about ft. per 100 ft. in the height of columns of equal weight. In case the cold water must first be fed down from roof tanks to heaters in the basement and then back up to the top floor fixtures, the extra length of run must be taken into consideration. As a check on the total quantity of hot and cold water required per day it is well to know that this generally runs from 2 to 3 times the amount of hot water re quired and from 80 to 100 gal. per occupant of the building.
Table 7. Hot Water Requirements for Apartment Buildings
Class
Lavatories
Hot-Wat kb Fixtures per Apartment
Bath Tubs
Showers Over Tubs
Kitchen Sinks
Laandry Trays
Separate Showers
Gallons Hot Watbb peb Apartment peb Maximum
Houb
Ai
i
i
i
2
0 25
A2
2
i
i
2
0 30
-A 2
2
2
i
2
0 35
A2
1
1
i
2
1 55
B1
1
0
i
2
0 20 .
C1
1
0
i
1
0 15
Note.--The quantity of hot water required per day is usually about 10 times the maximum hour requirement.
Table 8. Hot Water Requirements for Hotels
Class
Gallons
Add fob Kitchens peb Meal Capacitt
Add for Laundry
Hot Water Per H. W.
perH. W. Fixture
Fixture per Maximum
Per Day
per Day Hour
.Per Maximum
Hour
Per Washer Per Piece Per Washer per per Day per Day Maximum
Hour
High-Class Transient........
Medium-Class Transient. Apartment Hotels............
85 70 50
6.8 6.5 5.0
3.0 2.5
2.0
1.0
0.80 0.60
1.0 1.0 1.0
1200
1000
1000
250
200
200
Note.--Instantaneous demand rate for laundry washers from 25 to 50 gal. per minute. Table 9. Hot Water Requirements for Office Buildings
Class
Hot Water per Hot-Water Fixture
Per Day'
Per Maximum Hour
Having Hot Water in public toilets only
, 50
Water in Private Offices as well as in Public
Toilets
30
Por Self-Closing Hot Water Fixtures Deduct
40%
----- ----------
153
5.0
3.0 25%