Document KJYE8ZOv0zKmnNgkZL37dEaBQ
(conoco)
Interoffice Communication
To R. D. Gamblin
From
J. A. DeBernardi
Date October 28, 1975
subject
Elevated Working and Walking Surfaces - VCM Plant
Attached you will find the subject report. This transmittal also includes
the status of working and walking surface deficiencies discovered as a result of our pre-turnaround inspection. With the exception of the items noted in this report, all items included in the July 17, 1974 inspection report as Priority I, II, and III have been completed.
is Enc CC + enc: REL
CCR 000016561
/'
Interoffice Communication
To J. A. DeBernardi From C. E. Gremillion Date October 27, 1975 subject Inspection of Elevated Walking & Working Surfaces
VCM Plant Attached is the 1975 third quarterly status report of the repairs to the priority II & III items. Completed priority items have been dropped from the list. This report includes repairs made through October 21, 1975.
C. E. Gremillion
CCR 000016562
ATTACHMENT A PRIORITY II & III ITEMS VCM PLANT - LAKE CHARLES
TITLE
C-102 II - Remove foot obstruction behind the ladder at 6th level platform
H-485 Fin Fan III - Replace expanded metal grating or add supports
T-511 Anhydrous Ammonia II - Install handrails on steps to dike
-
T-101 III - Ladder rung not in alighment with platform <-
H-104 III - South of H-104 railing is substandard (28")
H-106 Ill - On both ladders top rung is not in alignment with platform
.
Light Ends Column III - Add intermediate platform on ladder - exceeds 20 feet
Platform Over S-207A and 207B, S-108 & S-109 II - Remove top ladder rungs
Structure at T-103A, T-110 & T-102 Tl ^ Add safety screen at west ladder to platform over T-103A (43" opening)
Vertical Tanks West of HC1 Tank Yl - Install toe boards on west side of platform
C-500 Scrubber Yl - Provide intermediate platform or safety climbing device-ladder is
about 35' high.
Tank Farm T-401A,~B & C III - Install toe boards III - Cover floor holes
T-402, 405, 422, 452 & 460 III - Ladder is substandard - side rails are 14" apart
L--'"
Dikes IT - Install handrails on all cross over steps
CCR 000016563
farehouse II - Add toe board to midrail on handrail overhead storage area
H-202A II - Install portable handrail on platforms at north & south heads
ESTIMATED COMPLETION
DATE Completed Completed Completed Being reviewed Completed Being reviewed Being reviewed Being reviewed Completed Completed
Being reviewed
Completed Completed 11-01-76 Completed Completed Being reviewed
PRE-TURNAROUND INSPECTION OF WALKING & WORKING SURFACES - VCM PLANT
TITLE
C-101 Steam Stripper Install vertical bars in opening between ladder cage and railing
C-202, HC1 Column Screens should be installed on already existing metal platforms from ladder cages to handrails.
C-103 Heavy Ends Column
'z
Install safety screens in opening between ladder cage and railing
ESTIMATED COMPLETION
DATE
Comp!eted
Compl eted
Compl eted
000016564
CCR