American Society of Heating and Ventilating Engineers Guide, 1932
have a temperature drop of only 10 deg as follows: Sections AB and KA supply 275 sq ft of equivalent heating surface and hence carry 66,000 Btu with a temperature drop of 10 deg; if the temperature drop were 20 deg these sections would (with the same velocity and the same friction head) carry 132,000 Btu. Hence, refer to Fig. 4 for 132,000 Btu and a unit friction head of 100 milinches, and note that the correct size would be about half way between a lj^-in. and a 2-in. pipe. Therefore, select a lj^-in. pipe for Section AB and a 2-iri. pipe for Section KA. The pipe sizes for the remaining eight sections and for the radiator connections can be selected in the same manner and recorded on the pipe diagram as shown.
The circulating pump for the system should be one which has its highest efficiency when it is delivering 13.2 gpm against a head of 2 ft.
Table 2. Capacities of Pipes in Equivalent Square Feet of Heating Surface,a and in 1000 Btu, and Velocities of Water in Pipes in Inches Per Second For Forced Circulation Systems with a Total Friction Head of
2 Ft and for a Maximum Temperature Drop of 10 DEGb
1
Pipe Size (Inches)
2
Equivalent Length of Pipe (Feetc)
6 23 4 5
89
Equivalent Total Length op Pipe in Feet in Longest Circuit
100
150
200
250
300
Unit Friction Head, in Milinches
350
400
240
160
120
96
80
69
60
ki
26 6.2
15
20
4.8 12
17
4.1 10
14
3.4 9
12
2.9 8
11
2.6 7.5
10
2.4 7
K -2
55 13.2 18
43 10.3 14
36 8.6
12
31 7.3
11
26 6.2
10
25 6.0 9
23 5.5 8.5
i 2.3 104 80 68 60 52 50 46 25.0 19.2 16.3 . 14-4 12.5 12.0 11.1 22 17 15 13 12 11 10.5
IK
3.0
220
170
145
130
116
110
100
52.8 40.8 34.8 31.2 27.8 26.4 24.0
27 21 18 16 15 14 13
IK 3.5 330 253 213 190 170 167 150 79.2 60.7 51.2 45.6 40.8 40.0 36.0 30 23 20 18 16 15 14
2 4.0 640 500 425 390 360 340 308 . 153.8 120.0 104.0 93.5 86.4 81.5 73.8 36 28 24 22 20 18 17 .
2K 6.0 1040 800 685 620 580 565 510 N 250.0 192.0 164-5 149.0 139.2 135.8 122.5 41 32 28 25 22 21 19
3
6.5
1850
1450
1225 1124
1060
1000
930.
444-0 348.0 294.0 270.0 254.0 240.0 223.0
48 37 32 29 26 24 22
a Based on 240 Btu per square foot.
bFor other temperature drops the capacities of pipes are to be changed correspondingly. For example,
for a temperature drop of 30 deg, the capacities shown in this table are to be multiplied by 3. The velocities
remain unchanged.
^
cApproximate length of pipe in feet equivalent to one elbow in friction head. This value varies with the
velocity.
116
Chapter 8--Hot Water Heating Systems and Pipe Sizes
Pipe Size Tables
If a number of heating systems are to be designed for similar conditions, i.e., for a total friction head of 2 ft and a temperature drop through the radiators of 10 deg when the maximum quantity of heat is being delivered to the building, a table such as Table 2 may be prepared from the data of Fig. 4. Having this table, the pipe sizes for the system of Example 1 can be easily selected. For example, for Sections BC and JK, each supplying 225 sq ft (54,000 Btu), the equivalent pipe length of the system is 227 ft.
Table 3. Capacities of Pipes in Equivalent Square Feet of Heating Surface3 and in 1000 Btu, and Velocities of Water in Pipes in Inches Per Second for Forced Circulation Systems with a Total Friction Head of 6 Ft and for a Maximum Temperature Drop of 10 DEGb
1
Pipe Size (Inches)
2
Equivalent Length of Pipe (Fbbtc)
3 4 ` 5 6 7 .8
Equivalent Total Length of Pipe in Feet in Longest Circuit
200 '
300
400
600
800
1000
Unit Friction Head, in Milinches
360
240
180
120
90 72
K1
31
7.4 18
25 6.0
15
21 5.0 13
16 3.S 10
14
3.4 9
13 3.1 7.5
K2
66 15.8 22
53 12.7 18
45 10.8 16
35
8.4 12
32 7.7
11
28 6.7 9
1
2.5
125 . 100
85
66
58 52
30.0
24-0
20.4
15.8
13.9 12.5
27 22 19 15 13 11
IK 3.3 270 218 185 140 125 112
64.8
52.5
44-4
33.6
30.0 26.8
33 26 23 .18 16 14
iK 4.0 400 320 270 210 187 170
96.0
76.8
64-8
50.1
44.7 40.8
37 31 26 20 18 15
2 5.0 800 640 540 420 375 330
192.0 153.0 130.0 100.1
90.0 78.0
44 36 30 24 21 18
2K
6.0
1250
1020
860
670
600 540
300.0 244.O 206.0 161.0 144-0 130.0
50 41 35 26 24 21
3
7.5
2300
1820
1540
1200
1040
950
550.0 436.0 368.0 287.0 249.0 228.0
58 48 42 32 27 24
"Based on 240 Btu per square foot. >For other temperature drops the capacities of pipes are to be changed correspondingly. For example, for a temperature drop of;30.deg, the capacities shown in this table are to be multiplied by 3. The velocities remain unchanged. approximate length of pipe in feet equivalent to one elbow in friction head. This value varies with the velocity.
117