G ROTON PLANT
{} }
CHAS. PFIZERS CO., INC.
ESTABLISHED 1049 GROTON. CONN.. 06340 AREA COOE ^03-4<4($611
April 1^ 1967
Mr. Stanley Shaw 800 Worth LLndberg Boulevard St. Louis, Missouri 63166
On the recommendation of Mr. Randall Graham and William Martin, of the Monsanto Co., a sample of three year old Therminol FR-1 is being sent to you for testing. We have been experiencing a loss of heat transfer oil and we have not determined if the loss is chemical or mechanical. However, we suspect a ruptured tube in the oil cooler.
* Past operation has been at ^00-425F, but we expect to raise the temperature to 500F in the near future. The oil is recirculated through the jacket of our reaction vessels at a flow rate of about 100 gpm. The system is operated vented to this atmosphere and is alternately heated and cooled over 18-20 hour cycles. Bayomet type electrical heaters and a shell and tube cooler are used.
Your comments on the composition of this oil sample will be greatly appreciated.
Sincerely yours
CHAS. PFIZER & CO., IWC
MGG: dap
M. G. Gollaher
DSW 435153
STLCOPCB4088214