Document K6vwQ82YM11vOELLO5N5JeJJK

778 CHAPTER 39 1949 Guide sion. ..Table 6 shows the maximum tonnage of refrigeration normally allowed for ammonia lines, assuming a maximum of 100 feet of equipment length of pipe. Table 6 shows the tonnage capacity normally allowed for Freon-12 liquid lines per foot equivalent length of pipe and Table 7 the maximum.tonnage for suction and discharge Freon-12 lines. EQUIPMENT CHARACTERISTICS AND SELECTION The various types of compression systems have quite different charac teristics of capacity and power with varying evaporator and condenser temperatures, as may be noted from curves in Figs. 14 and 15. 85 90 95 100 105 110 CONDENSER TEMPERATURE. DEG FAHR Fio. 15. Performance Characteristics op Compression Refrigeration Machines at Constant Speed From Fig. 14 it may be observed that power requirements for the centrif ugal compressor-increase much more rapidly'than for the reciprocating compressor with increase in evaporator temperature. Similarly, the capacities of the steam ejector and centrifugal compressors increase more rapidly than those of the reciprocating compressor with increase in evapo rator temperature. Thus, both the steam jet and centrifugal machines tend to be more self-regulating than the reciprocating. It is also evident from Fig. 14 that the steam jet equipment is best suited for operation at high evaporator temperatures. 'Hie effect of condenser temperature upon the power and capacity of the different types of compressors is shown in Fig. 15. It may be noted that the power required by the reciprocating compressor increases rapidly with. increase in condenser temperature, while the power curve for the centrifugal compressor is relatively flat. It is also evident that the ca- Refrigeration 779 Capacity Tons . 0 to-5 5 to 25. 25 to 50 50 to 400 400 and Over Table 8. Basis op Equipment Selection Majority Used Some Used Few Used Unit systems in con Unit central systems Built up: central sys ditioned space. using duct distri tems. bution. Built up central sys tems using recipro cating compres sors. Unit central systems using duct distri bution. Unit systems.in con ditioned space. Built up systems us ing absorption and adsorption sys tems. Built up central sys tems using recipro cating compresr sors. k Built up central sys tems using centrif ugal compressors. Central systems us ing adsorption sysT terns. Built up central sys tems using recipro cating compres sors. Built up central sys tems using steam jet and centrifugal compressors. Built up central sys Built up central sys tems using centrif tems using steam ugal compressors, jet. parity of the stem jet compressor is independent of condenser temperature until a certain point is reached where it drops to zero. As previously stated, steam jet equipment requires more condensing water than other types of compression systems. Consequently, steam jet systems Eire well suited to those applications where condensing water is cheap, or where condensing water is rather high in temperature. The selection of proper refrigeration equipment for any air. conditioning job is of utmost importance for satisfactory results. The most-important factors in the selection of the equipment Eire: 1. Loads (as determined by the conditions of the space to be cooled). 2. Economics (both initial and operating oosts). 3. Codes (local safety codes must be adhered to and influence the type of system to be used). ; A broad division of equipment to be used for a particUltir installation or application may be made on the basis of the magnitude of the load. Cur rent general practice is outlined in Table 8. Unit or packaged systems, consisting of a reciprocating compressor, condenser, evaporator, and fans, are generally used in the smaller sized jobs where electric power is available, as they are manufactured complete, ready to install and are the most economical (see Chapter 36). The reciprocating compressor in the built-up central system (see Chapter 43) covers the widest range of application since it is applicable to either the direct expansion or indirect systems and can be driven by steam or gas engines, or by electric motors. The quEintity of condensing cooling medium required is also less than for any other system with the exception of the centrifugEil compressor, which uses the same amount. Centrifugal compressors Eire used for large installations, and usually