A review of the technical and economic advantages and disadvantages with particular reference to safety
by j. M. Thomson*
I
' Perhaps because few electrical engineers are also- chemists, ;/ many engineers are not familiar with the use of askarel
fluid in distribution transformers. Even the difference ; between transformer oil and askarel is often not underj stood by transformer users. The two insulants are of j course not alike but this goes beyond the obvious difference | that oil burns and askarel is fire resistant. Differences i extend to insulation values, operating characteristics, main tenance and reliability. I The ASTM definition of askarcls indicates their impor tant features as being " synthetic fire-resistant type insulati ing liquids which when decomposed by electric arc evolve ; only non-explosive gaseous mixtures."1 Although there ; are many liquids which satisfy this definition, for a fluid j to be successfully used as a transformer dielectric coolant, | it is necessary to meet many more requirements such as 1 stability, freedom from corrosion, dielectric strength and I low cost. For these reasons the askarels currently pro ' duced are blended from a class of chemical compounds
known as chlorinated aromatic hydrocarbons.
Table I.--Composition of gases evolved by an arc under askarel
Gas
Hydrogen
... ...
Saturated hydrocarbons
Unsaturated hydrocarbons
Carbon monoxide
...
Carbon dioxide ...
...
Oxygen ... ... ...
Nitrogen
. . ...
Hydrogen chloride ...
... ...
. ...
...
... ...
... ...
...................
... ...
... ...
... ...
... ... ...
... ... ...
... ... ...
... ... ...
... ... ...
... ... ...
... ... ...
.... ...
...
Percentage
0 0 OS 025 0 0-25 20 97-0
chloride gas in the transformer as a result of either small internal corona discharge or major fault arcing, askarel fluid is formulated with a highly efficient chemical scavenger which neutralises any small amounts of HC1 gas formed, thus preventing any pressure build up even in sealed unit?.
Hydrogen chloride gas forms hydrochloric acid only in association with water and although there are always
Chemical hazard examined
One of the factors involved in the acceptance of askarels
as transformer fluids is that a new or unknown chemical
hazard might be introduced, either during normal opera
; tion, or under fault conditions. Experience has shown that
no serious hazard is met.
If a transformer is of the sealed type (and this is the
type that is most widely used), there is no escape of vapour
as the askarel is fully contained. There is then no possi-
j bilily of contact between liquid and personnel during
f normal operation.
.
i Under fault conditions in which the arc is struck below
i the surface of the askarel the fluid is decomposed with the
) liberation of hydrogen chloride and carbon. Clark2 has
reported the composition of the gases evolved by an arc
j under askarel, see Table 1.
Hydrogen chloride is a colourless gas with a pungent
' smell and its maximum allowable concentration in a
; human environment is 5 ppm (by volume) or 7 mg/m3. On
J account of its high solubility in humid air it is quickly
! dispersed. For this reason and because it is most un
pleasant to breathe, making its presence easily detectable,
. it is very unlikely that any injury would result from this
source in spite of its relatively low maximum allowable
concentration. In any case transformers are normally
. located in well ventilated areas to assist heat dispersion.
Hydrogen chloride gas is generated in an askarel trans
former only'when an arc has been struck and immediately
this arc is broken gas formation ceases'. Thus only a
limited amount of gas is formed which is proportionate to the intensity of the arc. To prevent build up of hydrogen
This 1.000 kVA askarel transformer teas installed in the basement of the llirmingham Civic Centre itt 19.16 and is still operating
`Marketing Department, Monsanto Chemicals Ltd.
satisfactorily with the original thud charge
Pon M-.rf-h 1070 .................. ...........
427
DSW 323550
STLCOPCB4075197
minute quantities of water present in even a sealed trans on the lats or me skjii ju a muiuoj nuumvi ^.........
former, generally the absorption of both the gas and the and _dry cleaning solvents. Therefore when an askarel
acid by the askarel is so efficient that falls in acidity after . comes into contact with the skin it should be washed oil
extended periods of operation have been observed. The with plenty of soap and water at the earliest opportunity.
results in Table 2 were obtained from a sample taken from Saturated clothing should be removed and dry cleaned.
a sealed transformer after 34 years of operation.
Infrequent exposure to askarel vapours will not cause any
It is sometimes thought that the decomposition of askarel ill-dfcct but prolonged exposure to a high vapour content
by an arc results in the formation of chlorine or phosgene should be avoided.
but investigations have shown that this is not so. The matter has been extensively investigated in Germany by the Chemische-Technische Reichsanstalt3 and in France by P. Jay.* The Chemische-Technische Reichsanstalt carried out a series of tests in which askarel was: (i) heated with metals up to 96-98C; (ii) dropped on to heated metals up. to 800C; (iii) vaporised and passed over metals heated to 500-740C in the presence of air; and fiv) decomposed by an electric arc (high and low voltage) both with and with out the presence of air. In none of these tests was the presence of chlorine or phosgene detected. . While transformer askarels have been used in the elec trical industry for over 35 years, they are chlorinated hydrocarbons and it is wise to take suitable precautions when handling them. The liquid has a solvent-like action
The main advantages of askarel-insulated transformers
are as-follows:--
-
Fire Resistance. Transformer askarel was designed to have similar physical characteristics to mineral oils since it was intended that the use of askarel should require minimal redesign of the transformer. The most important advantage askarel has over oil is fire resistance, that is, it will not support combustion. However, the possibility of a general fire started elsewhere and involving a transformer should also be considered.
A tank containing many hundreds of gallons of flam mable fluid will add substantially to the extent of fire damage. The number of fires started by transformers is very low but a far greater number of transformers are involved in and contribute to fire damage. In addition, it
Table 2.--Analysis of a sample taken from a sealed askarel-filled should be remembered that oil decomposes under arc,
transformer after 34 years in service
evolving a mixture of hydrogen and hydrocarbons which
Test
Method
Acidity mg
KOH/g
............. Monsanto
Trans former
Fluid Tested
0 006
IEEE Survey* Average Range
New Askarel Speci fication
0 12 0-05-0-5 0-01 mix
unlike gases evolved from askarel--is both flammable and explosive over a wide range of gas/air mixtures.
Freedom of Siting. Because of the safety features of askarel transformers they can be placed anywhere. No fire
* Mineral oil-fiflcd transformer*.
precautions have to be taken nor is there any necessity
STLCOPCB4075198
tUi C/laJt rrciiij VI j/vvt/i*' w ------------j ----------- . x
at the load centre if desired. Because there is no risk from
'atmospheric contamination they can also be installed before
construction is complete.
In comparison, dry type transformers are limited in this
flexibility of location because of their susceptibility to
atmospheric contamination. Additionally, installation costs
usually run much higher with dry' type transformers than
with askarel units especially if sound proofiing or protec
tion from atmospheric contamination is required. Due to
their nature, open dry type units may require a great deal
of maintenance, have a high noise level, be expensive to
operate and'have a .low impulse strength and overload
capacity. In practice, dry type transformers have been
found to be less dependable because of these operational
disadvantages combined with their susceptibility to atmo
spheric contamination: :i
.
Maintenance. If moisture is kept out of the askarel the
liquid insulation should undergo no change and the trans
former unit should give trouble-free operation for 30 years
or more.
The main disadvantages of askarel-insulated transformers are as follows: --
oil
Cost. An askarel transformer costs approximately 40 per cent more than an equivalent mineral oil transformer but about a similar amount less than a dry type transformer of the equivalent rating. But when installation costs are , included the askarel transformer can well prove to be the least expensive choice of the three types.
Weight. Askarel is about twice the weight of oil. Typical relative weight difference of the three different types of transformer as manufactured in Britain are . given in Table 3. In practice the extra weight rarely presents a constructional problem.
Switchgear and Tap Changers. Askarel transformers are not normally constructed with on load tap changers nor are askarels suitable for use in sw'itchgear because askarel does not possess the same arc quenching properties as oil.
Contamination by Oil. Mineral oil is soluble in askarel and any contamination of the askarel by oil will degrade its fire resistance. A maximum mineral oil content of 2 per cent by volume can be tolerated without seriously affecting the fire resistance. Askarel transformers should never be topped up with oil.
Effects on design and costs
Askarel transformers have been made to operate at voltages as high as 120 kV but since they are normally employed indoors as distribution transformers their voltage rarely exceeds 11 kV. One of the largest askarel trans formers to be designed and built in Britain has recently been completed. It operates at 33 kV and has a rating of 14 MVA. An important factor in the design of askarel units is the relatively high cost of the fluid compared with oil. Efficient design is, therefore, necessary to keep the volume to a minimum.
As water is askarel's greatest enemy completely sealed transformers are generally used. The introduction of allwelded, as opposed to gasketed, transformer tanks has resulted in the frequent specification of this type of con struction for askarel transformers. Where gasket seals are needed, for example, for hand hole openings, they should be designed with a recessed fitting to prevent the gasket softening and extruding out of its seat.
Table 3.--Comparative weights of oil, dry type and askarel-filled transformers manufactured in Britain
.
Ratine (kVA)
750 ........................ 1,000 ........................ 1,500 ........................
.
Oil-filled (lb)
6.600 8,100 H.000
'
Atkarel-fiiled
<lb)
8,500 11,000 17,000
i 1 i
;
i
Dry type Clan C
(lb)
s.ooo
7.300 9.800
Fine grain cork impregnated with nitrile rubber instead
of plain or coarse grain cork makes the best material for
gasketing. Nitrile rubber alone has been used but the cork
impregnated material has been shown to perform better.
Additionally, there are a number of other materials which
are completely resistant to askarel; these include Teflon
and Viton and most silicone rubbers. These materials are
often used for smaller gasket applications particularly in
the dynamic state.
With the increase in price of copper,'the possibility of
substituting aluminium for this material becomes more
attractive. Aluminium is perfectly compatible with askarel,
having been used for many years with similar fluids in
capacitor construction.
In general, askarel-resistant materials are no more expen
sive and no less readily available than oil-resistant
materials. In fact askarel/oil transformer production canes
be standardised to use products including gaskets and tanksio
that are common to both fluids, thus making for greatefes
versatility and flexibility in the transformer manufacturer's"
plant.
w
Experience has shown that silica gel breathers on openQ
transformers are often not maintained and sealed units are
therefore preferred to avoid the ingress of water. To relieve
tank pressure in the event of a sustained fault condition,
graphite bursting discs can be used. Alternative protection
can be effected by use of a pressure actuated relief valve
that provides both a visual and aural warning. The use of
Buchholz relays is not recommended as askarel, unlike
mineral oil, is not degassed before filling the transformer.
This has been known to lead to false actuation of the relay
caused by the escape of air as the fluid heats to operating
temperature when the unit is on load.
Because of the hygroscopic nature of the fluid the trans-
Eleclrical Review 7.0. March 197ft
429
I
i i
I !I II
i
I
STLCOPCB4075199
*- iOJinCI aiiUUlU lie-VC/1 UO (iUVJVYl/ll LV/ OIUIIU V|/VII UUHI.^
manufacture for any length of time, particularly when the humidity is high. The graph indicates the absorption of water from humid air by transformer askarel and mineral oil.3 Another important factor that affects design is the solubility of gases in askarel. The calculation of airspace between the surface of the fluid and the top of the tank is basically a function of fluid volume and tank pressure rating. Table 4 gives the relative solubility of various gases in askarel fluids.
. There will always be locations in non-hazardous areas where an askarel transformer cannot be judged an economic proposition. These locations will nearly always be either isolated substations or outdoor industrial sites
Gas
Carbon dioxide
.................
Air ..............................................
Nitrogen
... .................
Hydrogen chloride* .................
* In the absence of scavenger.
Percentage of Gas by Volume Corrected to:
25C 760 mm
O^'C 760 mm
3SC 710
5-7 60 37-8
I00C 470
4-9 48 50 9
j
I
j '
25C -- 5-8
5-S --
i i
I00:C -- 50
4-4 --
where a permanent location can be guaranteed and load centring is not possible.
In certain circumstances it is necessary to locate oilfilled switchgear in the substation and in such situations there would be no point in installing a fire resistant trans former as the presence of oil would already require fire protection apparatus. Oil switchgear can of course be located outdoors or alternatively air-break or SF6 insulated switchgear can be used indoors. There are many locations where there is a fire risk and space for substation construc tion is limited. Dry type transformers may be used under such restrictions but only if there is no fear of atmospheric contamination and a thorough maintenance programme is strictly adhered to. In addition, the higher noise levels and lower impulse/overload capabilities of dry type trans formers would have to be considered.
Load centres
A fire risk location is not the only place where askarel transformers can be used to advantage. In recent years package substations or load centres incorporating the trans former and associated switchgear have become popular.
Initially dry type transformers were used but the lower cost and operational advantages of askarel transformers have resulted in their acceptance in place of the dry type in this
application. Askarel transformers are widely used in multi-storey
buildings. Much the same approach as that used in indus trial load centring can be taken, locating askarel trans formers at the load centres of various floors. Potentially hazardous substations in the basement of the building are
avoided and savings are made by eliminating the use of
long runs of expensive m.v. cable. The low noise level of askarel transformers makes them
attractive for installation in residential buildings, hospitals, universities and schools. As a rule of thumb askarel trans formers produce 75 per cent less noise than the equivalent
dry type. Askarel transformers offer a margin of safety against
surge and overload levels and they fully satisfy the British Standard requirements for impulse testing and losses. The same overload protection is obtained as with an oil-filled
transformer without the attendant fire hazard. For over 35 years askarel transformers have served to
distribute the power for many industrial and residential areas in Britain and during this time they have established an excellent record of safety, economy and reliability. Over the last five years the sales of askarel transformers have
quadrupled in Britain.
DSW 323553
One oj four 750 kVA askarel-filled transformers installed in a flameproof area at the Convey Island methane terminal .
References
1 ASTM D 901-62 " Standard Methods of Testing Askarcls"
..
2 F M Clark " Non-flammable Dielectric Organic Compounds.
Ind. Fing. (hem. 29, 698 (June. 1937). 3 Report front Chemiscbe-J eehnisebe Reichsanslall, Berlin, dated -I*1
May. 1940.
.. .
4 P. Jay, " Study of the Formation of Phosgene by Decomposition ot
Chlorinated Hydrocarbons in the Electric Arc." Chcmic et Industrie.
92, No. 5 (November. 1964).
_ . ,.
a F. M. Clark. " Water Solution in High-Voltage Dielectric Liipiids.
AJEF Transactions Electrical Engineering, Vol. 55, pp. 441-443 (Aligns!.
1940).
Electrical Review 20-March 1970