Document K6eXj3mZ71rg6ZaZaBD0Xy98K

CHLORINATED BIPHENYL DIELECTRICS THEIR UTILITY AND POTENTIAL SUBSTITUTES Introduction In 1971, Monsanto voluntarily withdrew chlorinated biphenyl from a number of major applicational areas. By 1973, pro duct was sold only to manufacturers of sealed electrical equipment such as transformers and capacitors. Major applications affected by our withdrawal were carbonlesej paper, fire resistant hydraulic fluids, heat transfer fluids, and plasticizers. Sales for other miscellaneous minor applications were dis continued at the same time. This action resulted in a reduction, in the use of chlori nated biphenyl in areas where entry to the environment was lessj controllable, of 32.5 million lbs. per year. We decided at that time to continue supply to closed electrical applications because we believed thati a) Entry of chlorinated biphenyl to the environment was limited and controllable; b) The capacitor industry could use more biodegradable lower chlorinated homologs; and c) Withdrawal would have brought to a halt production of equipment essential to the safe and efficient distribution ind use of electrical energy. Today we continue to sell chlorinated biphenyl observing the following policy. 1. We supply only to manufacturers of sealed electrical equipment such as capacitors and transformers. 2. We supply lower chlorinated homologs, Aroclor 1016, to :he capacitor industry. 3. We offer an incineration service for liquid PCB wastes. MONS 047924 4. We continue to work with ANSI Committee C107 and other bodies to establish appropriate handling and control procedures for equipment containing chlori nated biphenyl. 5. We do not reclaim used dielectric fluid and, in those cases where our advice is sought, we seek to ensure that reclaimers are knowledgeable about PCB and exercise proper control. 6. We allocated increased research resources in 1969 to seek and develop effective replacements. This program continues. 7. In seeking possible replacements, we will ensure that differences between Aroclor and candidate fluids, from our program, are widely reviewed in order that the potential impact of any compromises is fully evaluated. The implementation of these and other programs both by our selves and electrical equipment manufacturers was prompted by the utility of this dielectric family and the difficulties inherent in developing substitutes to effectively and fully replace it. MOWS 097925 2. Utility of Chlorinated Biphenyl in Capacitors re Resistance The adoption of chlorinated biphenyls in 1929 as capa citor dielectrics stemmed from their superior dielectric properties compared to mineral oil. However, recognition of the fire resistant character of the fluids influenced system and equipment design and standards over the sub sequent 45 years. It is probably true that today many people find it difficult to assess potential capacitor fire hazard purely because Aroclor has been used for 45 years. P^rticular examples where fire resistance in a capacitor if) of benefit include: a) fluorescent lighting ballasts; b) air-conditioner motor capacitors; c} television capacitors; d) large power capacitors where high fault currents can cause case rupture and ejection of fluid from pole mounted unite close to people and buildings: e) industrial furnace capacitors. Stability , The persistence of chlorinated biphenyl in the environment is associated with the high degree of thermal, chemical, oxidative, and hydrolytic stability which permits capacitor manufacturers to supply to the exacting reliability require ment;- which exist today. electric ConBtant/Dielectric Strengths Th.ese properties are important in determining the size of a capacitor. In a mixed dielectric system, e.g., l> per/Aroclor or Paper/Polypropylene/Aroclor, the dielec- }t; ic properties of Aroclor permit optimization of stress d Stribution between the components making up the dielectric l*:yer. HONS 041926 This has enabled capacitor manufacturers to reduce pap?r and film volumes for a given capacitance. I sha 1 discuss under the heading of "potential substitutes the impact that this could have on: a) paper/film availability; b) design of equipment containing capacitors. HONS 047927 3. Utlility in Transformers Chlorinated biphenyl transformers represent less than 15% of transformers in service. Their use is associated with the need to limit fire hazard in installations. 1. Railroad Transformers Multiple unit cars as used in rapid transit systems have transformers mounted beneath each car. By nature of the type of service, involving high pas senger density, safety is essential. 2. Urban Power Substations (e.g., Underground Vaults) These designs need to take account of city center space limitations and, also, the safety of the public and maintenance crews. Fire resistant liquid trans formers are helpful to all these objectives. 3. Industrial Load Centers Efficient system designs for large, power intensive, manufacturing plants (e.g., automotive assembly, steel production) often incorporate transformers close to the electrical load centers. The use of Aroclor transformers at these centers, in the heart of the plants or overhead in roof structures, protects both employees and plant. 4. Transformer/Rectifiers Programs to reduce the emission of particulate matter from stack gases, for example in fossil fuel generating plants, include installation of electrostatic precipi tators. The transformer/rectifiers energizing the precipitator field must be located close to the elec trodes. In many designs, the multiple transformers are located in a penthouse above the precipitator. A fire in the penthouse could lead to close down of the precipator and thus, the generating plant, if pollution control is to be maintained. A fire resistant fluid is of obvious benefit in this application. MGNS 047928 In each of these applications, Aroclor protects the system from! a) An electrical fault within the transformer initiating a transformer fluid fire; b) Electrical breakdown of the fluid causing emission of flammable gases; c) Propagation of fire if the transformer liquid content is involved in an external fire. MONS 047929 A. Potential Substitutes in Capacitors Research Objectives In seeking potential substitutes, our research objectives, of necessity, related to those properties which gave Arjoclor its value. Equally, we recognized the need that an Arroocclor replacement should eliminate environmental concerns. Desirably, a replacement should operate across the full range of current Aroclor capacitor applications while requiring minimum changes in design of capacitors and equipment utilizing capacitors. The use of chlorinated biphenyl is worldwide. Monsanto manufactures chlorinated biphenyls both in America and Great Britain. We supply to the capacitor industry of many countries. We sought potential replacement product that could be made available with the consistent quality control applied to Aroclor on a worldwide basis. Wei referred earlier to availability of co-dielectric comPi'cjnents in capacitors. A solution which required substantial cli anges in availability of polypropylene film (quantity or a ality) or a major increase in short-term availability capacitor paper, we considered unsatisfactory. If in i 974, such increased quantities had been required, they w<'culd not have been available. Capacitor production would 3ve fallen short of demand, further jeopardizing efficient wer supply. 04r research objectives can be broadly summarized in the fAllowing Table 1. . MONS 047930 POTENTIAL SUBSTITUTES CAPACITORS RESEARCH OBJECTIVES 1. MATCH OR EXCEED AROCIOR 10l6 CAPABILITY. A) DIELECTRIC CONSTANT DIELECTRIC STRENGTH - AVAILABILITY CONVERTABILITY B) STABILITY POWER FACTOR . - RELIABILITY C) SAFETY - FIRE RESISTANCE 2. GOOD ENVIRONMENTAL COMPATIBILITY. 3. A) SPAN EXISTING APPLICATIONS - COMPLETE SOLUTION. ' B) INTERNATIONALLY AVAILABLE - NOT SOLELY USA SITUATION MGNS 047931 Before! X refer to non-PCB fluids, X would like to raise the matter of potential use of dichlorobiphenyl as a capacitor dielectric. MCS 1043 is predominantly dichlorobiphenyl and contains no pentachlorobiphenyl homologs. Its dielectric properties and stability make it an attractive candidate to many capacitor manufacturers. While it is somewhat less fire resistant than Aroclor 1016, it is considerably more fire resistant than some of the other alternates which we will discuss. Its commercialization would require further detailed environmental study and significant plant modifi cation One ofj the key issues for discussion in earlier sessions and in the session tomorrow, devoted to possible controls, is the difference in environmental impact of higher and lower chlori- nated biphenyls. This same issue was faced squarely in France thie-s lmmsr jiihsn regulation of chlorinated biphenyls wea peb- 1 ishad in the "Journal Offieielllr~ffaly 26-;--18 75-.--A--beanslation of thir mmjnir i-nrr *T Tt-t-rhnfli (irFnndiv 8) . ^he French Ministry of Industry and Research formally recognize a differ ence between, in U. S. terms, Aroclor 1254 and Aroclor 1016. / If a farther modification in isomer content is useful and desiraale, it will be difficult to proceed further before agenciBS, on the basis of their studies of the past 3 years, make Bame more positive and overt conclusions regarding the difference between existing higher and lower chlorinated homologs. Hon-PCP Candidates The cai|pacitor industry is.currently examining two Monsanto non-P<CB (candidate) dielectrics. These contain no chemical biphenlyl and are not chlorinated products. The two fluids are designated: MCS 1238 MCS 1588. MOMS 047932 ( i Both are baaed on a single concept. Me have used a base liquid with good dielectric strength, but with dielectric constants lower than Aroclor 1016. To these, we have added a limited quant Lty of a liquid of very high dielectric constant to yield a mix :ure of equivalent dielectric constant to Aroclor 1016. Both of these products are blends of synthetic hydrocarbons with i high dielectric constant additive. Table 2, on the following page, lists some of the properties of MC:EE 1238 and MCS 1588 compared to Aroclor 1016. You will observe that we have labelled the line. Corona Inception Voltage/Extinction Voltage, "Industry". These values are more a function of capacitor design than of the liquid, itself. While preliminary industry results demonstrate acceptable results in capacitors, more full scale work is required before definite conclusions can be drawn. Diele btric constants relate closely to those of Aroclor 1016 over the temperature range of capacitor operation. RydroLysis stability is mentioned because of work carried out on earlier candidates based on esters which gave concern because of hydrolysis instability. Dissipation factors for the fluid and a model capacitor are given to indicate that while the fluid has, inherently, a highe^: "loss" than Aroclor 1016, this is not pronounced in the final capacitor. M0NS 047933 PROPERTY DK 25*C 100 C ' CORONA IV/EV ' . HYDROLYSIS STABILITY* (NEUTRALIZATION NUMBER) DISSIPATION FACTOR FLUID TANg 60 HZ. 100C DISSIPATION FACTOR MODEL CAPACITOR AT 90C AROCLOR 1016 5.9 4.85 INDUSTRY , 0.00 0.0025 0.0032 MCS 1238 6.0 5.1 INDUSTRY 0.00 0.05 0.0039 MCS 1588 6.1 5.1 INDUSTRY 0.00 0.05 0.0035 SNOW SEE TEXT Fire Resistance Neithe MCS 1238 or 1588 is fire resistant. This deficiency versus Aroclor 1016 must be closely considered. Environmental Considerations The enyironmental/health evaluation of capacitor replacement fluids must be related to: a) Exposure - Extent of Human Exposure* How will material enter the environment? In what quantities? b) Degradation - If some quantity enters the environment, at what rate and through which mechanism will it degrade? c) Accumulation d) Tosficity - Occupational Safety Environmental Compatability Exposure - We expect to see similar routes and quantities as experienced with Aroclor 1016. Degradation - Biodegradation has been studied using a semicontimiouB activated sludge technique. Forty-eight hour exposure of Aroqlor 1254, Aroclor 1016, and MCS 1238 dielectric fluids to activated sludge using a semi-continuous procedure resulted in the following percent biodegradation rateB and 95% confidence limits: Mater lal Table 3 % Biodegradation Feed Concentration, ppa Aroclorr 12254 Aroclorj 1016 MCS 1238 33 - 14 70 - 10 1 1 M0NS 047935 I'or thfe polychlorinated biphenyl (PCB) materials, the level of chlorination appears to be the most significant factor in their relative biodegradability. The rate of biodegradation decreases as the number of chlorine atoms per biphenyl molecule increases. Chromatograms representing samples after exposure to activated sludge show significant alteration iii the Aroclor 1016 isomer distribution, but little for Aroclor 1254 . Degra dation of the non-halogenated fluid, MCS 1238, proceeds much more rapidly than for the halogenated PCB fluids with no evidence of resistant components. Methodology for this technique is described in Appendix B. Accumuilation Table (Graph) depicts the results of Rat Tissue Residue Level Studied vs. Time and compares Aroclor 1242, Aroclor 1016, and MCS 123 8. ( See following page.) Results of Feeding Study A fraction of the ingested Aroclor 1242 and Aroclor 1016 was Btored in rats' lipid reservoirs. However, most of this residue was depleted after the rats had been on the basal laboratory diet for several weeks. During the course of the feeding study, residues of Aroclor 1016 accumulated more slowly and to a signi ficantly lesser extent than those of Aroclor 1242. During the recovery period these PCB residues decreased to lower values for Aroclor 1016. The residue concentrations of MCS 1236 quickly reached a stable level well below the concentration in the feed. The residues did not increase with continued exposure. After feeding of the treated chow was ceased, the MCS 1238 residues were rapidly metabolized and/or excreted. The tissue residue accumulation and depuration profile of MCS 1238 shown in Table 4 is markedly different than those of the Arocloif fluids, especially that of Aroclor 1242. iu fVj-M v-dtJ C HONS 0^2936 R esidue L e v e l FAT TISSUE RESIDUE LEVEL VERSUS TIME 25 ppm Feed Level For Rate if Toxic iy. Before samples of MCS 1238 could be evaluated in the capacitor industry and within Monsanto, acute toxicity data was gathered. 1. Rat - Acute single oral dose LD 50 - 3B00 mgs./kg. 2. Rsbbit - Dermal LD 50 5.0-8.0 gms. per kg. Rabbit - Potential eye irritation - A slight degree of irritation resulted when 0.1 ml. of undiluted MCS 1238 was placed in the conjuctival sac of the rabbit eye. Thje average maximum score recorded at one and again at 24: hours after treatment was 12.0 on a scale of 110.0. All eyeB had regained normal appearance 72 hours after dosing. M0NS 047938 4. Rabbit - Potential skin irritation - When undiluted, MCE 1238 was held in continuous 24-hour contact with intact rabbit skin, a moderate degree of irritation resulted. The maximum average score was 3.6 on a scale of 8.0. Further programs are in process, or scheduled, to study the following: a) Vapor Inhalation b) Ultimate Degradation c) 90-Day Pilot Feeding Study d) Long-Term (2-Year) Feeding Studies e) Fish Tissue Residues. To summarize Monsanto research activities: large number of single compounds and mixtures have en evaluated in terms of physical property data, environi^ntal compatability, fire resistance, and model capacitor fe testing. ese have led us to conclude: a) Aroclor 1016 may be sufficiently degradable to remain | in controlled use. b) MCS 1043, a modification of current practice is available longer-term if lower chlorinated materials are more environmentally compatible. cj MCS 1238 is a potentially acceptable replacement with the qualification it is not fire resistant. Further programs must be completed with MCS 1238 in order a I Deepen our knowledge of its environmental compatibility. bi Permit complete evaluation by the capacitor industry across their range of applications. ci Enable utilities, capacitor users, and agencies to evaluate the significance of decreased fire resistance. MOMS 047939 As a closing thought to this section, I would like to comment that since 1929 when Aroclor was first developed as a capacitor dielectric, normal commercial pressures have spurred efforts to find superior replacements. The awareness of environmental accumulation of chlorinated biphenyls from other applications added further impetus for jB more intensive research in the chemical and electrical industries. Aroclor has resisted 45 years of search for a superior replacement. HONS 047940 5. Substi!tute Transformer Fluids Neither Monsanto nor any other company, to our knowledge, has developed a transformer dielectric with equivalent fire resistance to that of Aroclor. The difficulties that we facie in common with other workers in this field are two fold: Aroclor has become the subjective standard for fire resistance in transformers because it works and has worked for 45 years,*Jfo establish standards to guide research effort( Sphere is a need for objective evaluation of the fire hazard associated with the major sectors of transformer use..^ t e chemistry which imparts fire resistance tends also produce stable molecules. Monsanto seek replacement products that will provide protection against: a^ Fire from transformer faults under the liquid surface: b) . Fire from secondary ignition of gaseous arc decomposition products; c) , Spread of fire if the transformer is involved in an externally initiated fire. W<* have to accomplish this and produce an environmentally Clcompatible product. We ha\Je four candidates which we are currently introducing to-th^ transformer industry. These materials are in a suffi ciently early stage of development that it would be premature to give detailed property data at this meeting. MONS 047941 APPENDIX A OFFICIAL GAZETTE OF THE REPUBLIC OF FRANCE MINISTRY OF INDUSTRY AND RESEARCH Entries in the Registers of Poisonous Substances (Section I) The Minister of Agriculture, Minister of Health and Minister of Industry and Research, Considering the code of public health, and In particular arti cles L.6?6, R.51*19 and R.5150; The Order of 15th November 1951 as amended and supplemented by subsequent orders, specifying the composition of section I of poisonous substances; and the opinions expressed by the French Supreme Council of Health, Order : Art. I -) the following products are entered In section I of regl8tej C of poisonous substances PolychldrobiphenyIs (P.C.B.): PolychicroterphenyIs (P.C.T., with th exception of those which are contained In the closed systems specified below in conformity with the requirements for make-up, presentation and use laid down by an order made under article R.516B of the Code of Public Health: Transformers and Industrial electrical equipment such as recti fiers, rheostats, resistances and Induction colls: Condensers; Heat-carrying systems; Hydraul:.c systems. Art. 2 ' the Director of Chemical, Textile and Miscellaneous Industr:.es at the Ministry of Industry and Research, the Director General of Administration and Finance at the Ministry of Agriculture, the Head of the Central Department of Pharmacy and Medicaments at the MlnlBtry of Health are Instructed, each for the matters concerning him, to implement this order which will be published in the Official Gazette of the Republic of France. MQNS 047942 -2Made at Paris, 8th July 1975 The Minister of Industry and Research for and on behalf of the Minister: Head of Department, Jacques Darmon. The Minister of Agriculture for and on behalf of the Minister, Head of Department Gabriel Vught The Minister of Health for and on behalf of the Minister, Head of Department Dominique le vert HONS 047943 The Minister of Agriculture, Minister of the Quality of Life, the Minister of Health and Minister of Industry and Research, considering the Code of Public Health, and in particular ar ticles L.626, R.519, R.5150 and R.5168; The Order of 8th July 1975 supplementing register C (Section I) of poljsonous substances; The opinion of the French Supreme Council of Public Health; The communication dated 23rd July 1974 to the Commission of the European Communities, ORDER: I Art.l - the marketing and use of polychlorobiphenyls or mix tures containing polychlorobiphenyls and polychloroterphenyIs are subject to the restrictions of the present order. In the following articles the above-mentioned substances are called "7.C.B." for abbreviation. C Art.2 - ;he use of PCBs is authorized under the conditions laid 2 down in articles 6 to 8 below in closed systems permitting con- | trol of ihe product and described with restrictive effect below: 1. Transformers and industrial electrical appliances such as rectifiers, rheostats, resistances and induction colls; provi ded that' these systems are planned to permit the recovery of more than 95# of the PCBs contained in them. 2. Condensers not specified in article 3. 3. Heatj-carrying systems, save in installations for the treat ment of [foodstuffs for human or animal food or for the prepara tion of pharmaceutical or veterinary products, provided that all measures are taken for any escapes which may occur to be fully recovered and not to be dispersed in any way in the environment. 4. Hyditaullo systems used in mining plant, excluding those used for any other purpose. For the systems specified in 3 and 4 above, the provisions laid down wll 1 only come into force, so far as installations in opera tlb]n are concerned, on the expiry of a period of 1 year after e date of publication of this order in the case of heat-ca frying circuits and two years after this date of publi- oatlon the case of hydraulic systems. HUNS 047944 -2- Art.3 - the use of PCB In condensers containing less than 1 kE thereof Is authorized, provided that: The average number of chlorine atoms In the molecule Is not more tharjthree; The total content of pentachlorobiphenyls and more strongly chlorinated homologs Is not more than 3.5^ In weight. Waste or manufacturing rejects must be destroyed and any risk of dispersal In the environment must be avoided. Art.^l - the use of PCBs In Installations or for purposes con nected Wl) th scientific and technical research Is authorized provided that no risk results to the environment. Any new uses which arise from this must be the subject of a new ordeif. Art.5 - All other uses of PCBs are prohibited, in particular certain applications such as paints for swimming pools, water plant and materials normally In contact with foodstuffs. Art.6 - the emptying and recovering of PCBs used or contained In unused equipment specified in article 2 is obligatory. When equipment is no longer used It Is the duty of users of PCB or owners of systems specified In article 2 containing It to contact either a manufacturer or Importer of PCB of their choice, or the builder, fitter or importer of the system In question or a body for the treatment of chemical waste which Is approved for the treatment of PCBs. As soon as they are Informed of the request and if they do not collect the material themselves, the manufacturer or Importer of PCB, the builder, fitter or importer of equipment or the body forTthe treatment of waste must remind the user or owner of the PCB of the measures to be taken for emptying If possible, package and despatch, and the user or owner must comply with these measures. Condensers will be despatched as they stand. Manufacturers or importers of PCB, builders, fitters or import ers of s/stems and bodies for the treatment of chemical waste which ars approved for the treatment of PCBs, must treat or procure the treatment of the PCBs which they receive with a view to their regeneration or destruction under conditions which must avoid any risk of dispersal in the environment. MQNS 047945 -3- The provl slons laid down In the third paragraph of this artl- fole and l[he treatment required In the fourth paragraph are subject approval by the authorities. Art.7 - the approval of a waste-treatment body for the destruc tion or regeneration of PCBs Is given by a Joint order of the Minister in Charge of Industry and the Minister In Charge of the Environment, on sight of an application which Is shown to be a proper one with regard to technical and economic factors. The authorities have a period of three months commencing with the receipt of a file which is Judged to be sufficiently com plete, ip order to decide applications for obtaining approval. In the absence of any reply after the expiry of this period approvaljIs deemed to have been given. Approval|may be partial or subject to any conditions deemed necessary by the authorities. It may not be given for a period of more than five years. Art.8 - ior all uses in closed systems specified in article 2, the importer, builder or fitter must place on the equipment, in a visible location, an Indelible inscription on a yellow background of dimensions not less than 50 x 75mm bearing the following statement which may be accompanied by the brand name of the product: "This eqiUlpment contains PCBs which could contaminate the envlronmenfc1 and the elimination of which is subject to regulations, If the eqiulpment does not operate properly or Is no longer used, you must conform with the provisions of the order of ..." Art.9 - nanufacturers and Importers of PCB and the manufacturers, importer} or sellers of equipment specified in article 2 must be In a position-to supply the authorities with a list of their customers and to facilitate controls to see that articles 6 to 8 are'carried out. Manufacturers and Importers of PCB must be in a position to supply oS request statistics of the quantities of PCB manufac tured, nJarketed, used or treated. Art. 10 - the Director of Chemical, Textile and Miscellaneous Industries at the Ministry of Industry and Research, the General Direotorl of Administration and Finance (Department for the Prevention of Fraud and Control of the Quality of Life) at the Ministry of Agriculture the Director for the Prevention of Pollution and Nuisances at the Ministry of the Quality of Life and the Head of the General Department of Pharmacy and Medica ments at the Ministry of Health are Instructed, each for the matters concerning him, to carry out the present order which will be published In the Offloial Gazette of the Republic of France HUNS 047946 Made at Paris, 8th July 1975. The Minister of Industry and Research, for and on behalf of the Minister: Head of Department, Jacques Darmon The Mini ster of Agriculture, for and ion behalf of the Minister: Head of Department, Gabriel Vucht The Minister of the Quality of Life, for and on behalf of the Minister: Head of Department, Georges Badault The Minister of Health, for and on behalf of the Minister: Head of Department, Dominique Levert. HONS 047947 APPENDIX B Biodagradation Method Since activated sludge is one of the most important agents for Jewage treatment, test procedures evaluating its action are cf great importance. The temi-continuous activated sludge (SCAS) method has been extersively utilized in the development of biodegradable deteigents. in our SCAS procedure, patterned after the Soap and Detergents Associations standard method ' mixecl liquor (activated sludge and supernatant) from a local domestic sewage treatment plant is charged to magnetically- stirred glass vessels of 1.5 liter capacity. Means for aeration and sampling are provided. The SCAS unit is generally operated using a retention or aeration time cycle of 24 to 72 hours. At the beginning of each cycle, synthetic sewage (300 mg glucose, 200 mg. nutrient broth, and 130 mg K^HPO,]) and the appropriate test material in ethanol solution are added to the mixed liquor (2500 mg/liter suspended solids concentration) . Aeration is maintained until the end of the ' cycle, at which time the sludge is settled and one liter of supernatant drummed. The cycle is then re-initiated by the addition of tap water, synthetic sewage, and test material. Operntion of the units can be continued for an indefinite period of time until consistent degradation rates are observed. SampLe Analysis Biodegradation of the test material was determined during one cycle each week by analyzing 20 to 50 ml mixed liquor samples withdrawn after feeding and at the end of the aeration cycle. The mixed liquor analytical procedure involved extraction with three successive 25 ml portions of hexane, and drying combined extracts with anhydrous sodium sulfate. Extracts were| concentrated in a Kuderna-Danish evaporative concentra tor equipped with a 3-ball Snyder condenser, and measured by electron,, capture, or flame ionization ,gas chromatography. Calibration curves for each product were prepared by plotting detector response (total peak area) versus nanograms of standard injected. MOMS 047948 TheJ percent biodegradation was calculated from the following equation: % Biodegradation (C0 - cn^/co x 100 where CQ and Cn use the initial and final concentration of test material, respectively, on the mixed liquor. References 1. J. Am. Oil Chem Soc. 42, 986 (1965). 2. J. Am. Oil Chem.Soc. 46, 432 (1969). MONS 047949 APPENDIX C Methodology for Feeding Study Feeding and Sampling Rat chew containing 25 ppm Aroclor 1242, Aroclor 1016, or MCS 1238 wi s prepared by mixing the products into Ralston Purina rat chew. The treated chow was fed ad libitum to adult albino rats for an exposure period of 30 days. Following the 30-day exposure period, all remaining rats were placed on the basal laboratory diet. At predetermined intervals during the ex posure and recovery periods, five rats from each exposed set and a control set were sacrificed. Fat tissue was excised for analysis and composited for each group. Samples were quick-frozen and stored in glass containers with aluminum foillined caps to minimize risk of contamination. Isolation The dii lectric fluid residues were isolated from the fat by solven extraction. A weighed amount of fat was placed in an Erlenmt yer flask and homogenized three times with 25 ml of pestic de grade hexanes and anhydrous sodium sulfate using an ultp asonic homogenizer. The combined supernatants and washiings were filtered through anhydrous sodium sulfate and dilute^ to 100 ml with hexane. Lipid weight Determination A 5 mil aliquot of the extract solution was pipetted into a tared 50 ml beaker. After evaporation of the solvent under a stream of nitrogen, the beaker and residue were reweighed to obtain the lipid weight of the aliquot. All residue levels are reported as ppm on a lipid weight basis. PCB Clean-Up and Measurement Sample clean-up for the extracts containing Aroclor 1242 and Aroclojr 1016 residues was accomplished by pipetting an aliquot of the extract onto a 554 deactivated alumina column and eluting with ll25.ml of hexanes. The column eluate was collected in a Kuderna-Danish evaporative concentrator, a 3-ball Snyder conden ser wa|s attached, and the solution was concentrated to 5 ml. The residue levels in the extracts were measured by gas chromatography UBing an electron capture detector. M0NS 047950 Won-Pi Clean-Up and Measurement Sample clean-up for the extracts containing MCS 1238 residues required separation of the residues from the lipid by pre parative scale gel permeation chromatography. Following the GPC separation, the extracts were further cleaned up on an alumina column, collected, and concentrated as above. The residue levels in these extracts were measured by gas chro matography using a flame ionization detector. Calculations Calibration curves for each product were prepared by plotting detector response (total peak area) versus nanograms of standard injected. Residue levels in the samples were determined by summation of the total area of peaks corresponding to peaks in the standard and use of the appropriate calibration curve. The calculations were done as follows: where (j (N)(Vf) Residue (ppm) * (VjJ(W). amount of product from calibration curve (ng) volume of final concentrate (ml) volume injected (ul) lipid weight of original sample (g). MONS 047951 IN 1972 MONSANTO VOLUNTARILY DISCONTINUED SALE OF PCB-CONTAINING PRODUCTS TO THE FOLLOWING MAJOR APPLICATION AREAS: -CARBONLESS PAPER ' -FIRE RESISTANT HYDRAULIC FLUIDS -HEAT TRANSFER -PLASTICIZER HONS 047952 OTHER MISCELLANEOUS MINOR APPLICATIONS DISCONTINUED AT THE SAME TIME. HONS 047953 SALES IN THESE AREAS PELL FROM 32.5H LBS. IN 1970 TO 0 IN 1973. MOWS 047954 IN 1975 WE CONTINUE TO SELL TO THE ELECTRICAL INDUSTRY FOR INCLUSION IN CAPACITORS, TRANSFORMERS AND ASSOCIATED CLOSED ELECTRICAL EQUIPMENT BECAUSE - MONS 047955 1. UTILITY - THE AROCLOR FLUIDS PERFORM AN ESSENTIAL ROLE IN ELECTRICAL DISTRIBUTION. 2. LACK OF EFFECTIVE PROVEN REPLACEMENT. 3. OUR BELIEF THAT USE IN CLOSED SYSTEMS IS CONTROLLABLE. HONS 047956 c. MONSANTO CURRENT MARKETING POLICY - PCB 1. SUPPLY ONLY MANUFACTURERS OF SEALED ELECTRICAL EQUIPMENT SUCH AS CAPACITORS/TRANSFORMERS. 2. SUPPLY LOWER CHLORINATED HOMOLOGS FOR CAPACITOR APPLICATIONS, E.G., AROCLOR 1016. 3. ])0 NOT RECLAIM ELECTRICAL FLUIDS. A. OFFER INCINERATION SERVICE FOR LIQUID PCB WASTES. 5. 30NTINUE RESEARCH PROGRAM (STARTED 1969) TO DEVELOP ' EFFECTIVE REPLACEMENTS. 6. ENSURE THAT SIGNIFICANT DIFFERENCES BETWEEN AROCLOR DIELECTRICS AND REPLACEMENT CANDIDATES ARE FULLY REVIEWED. MOWS 04 795 7 UTILITY IN CAPACITORS PROPERTY FIRE RESISTANCE THERMA L STABILITY CHHMldAL STABILITY HYDRO!)/YTIC STABILITY POWER FACTOR FUNCTION CONSUMER/PLANT SAFETY RELIABILITY DIELECTRIC CONSTANT DIELECTRIC STRENGTH AVAILABILITY OF OTHER > SYSTEM COMPONENTS CAPACITOR SIZE ECONOMY MONS 047958 UTILITY IN TRANSFORMERS FIRE RESISTANCE SAFETY THERMAL/CHEMICAL STABILITY RELIABILITY MONS 047959 TRANSFORMER APPLICATIONS 1. Railroad transformers - rapid transit systems. 2. URBAN SUBSTATIONS. 3. INDUSTRIAL LOAD CENTERS. 1). EtECTROSTATIC PRECIPITATORS - POLLUTION CONTROL IN POWER PLANTS. MONS 041960 FIRE RESISTANCE OF ASKAREL TRANSFORMERS 1. FIRE INITIATION. 2. ARC FORMED GASES. 3. FIRE PROPAGATION. MONS 047961 // POTENTIAL SUBSTITUTES CAPACITORS RESEARCH OBJECTIVES 1 MATCH OR EXCEED AROCLOR 10l6 CAPABILITY. A DIELECTRIC CONSTANT DIELECTRIC STRENGTH - AVAILABILITY CONVERTABILITY B) STABILITY POWER FACTOR - RELIABILITY Cj SAFETY FIRE RESISTANCE 2. GOOD ENVIRONMENTAL COMPATIBILITY. 3. A) SPAN EXISTING APPLICATIONS - COMPLETE SOLUTION. B) INTERNATIONALLY AVAILABLE - NOT SOLELY USA SITUATION. HONS 047962 MCS 10^3 DICHLOROBIPHENYL TYPE. COULD BE-SUBSTITUTED FOR AROCLOR 1016. SLIORTLY LESS FIRE RESISTANT. FURTHER DEVELOPMENT CONTINGENT ON INDUSTRY/GOVERNMENT/PUBLIC/MONSANTO CONCLUSIONS ON DIFFERENCE IN PCB HOMOLOGUES. MONS 047963 NON-PCB THE CAPACITOR INDUSTRY IS CURRENTLY EXAMINING MCS 1238 MCS 1588 L. THESE CONTAIN NO CHLORINATED BIPHENYL. >. THEY REPRESENT A SINGLE CONCEPT. 3. NEITHER PRODUCT IS CHLORINATED. MONS 047964 THE ADDITION OF A LIMITED QUANTITY OF VERY HIGH DIELECTRIC CONSTANT FLUID TO A GOOD DIELECTRIC BASE LIQUID TO GIVE A DIELECTRIC MIXTURE "EQUIVALENT'' ELECTRICALLY TO AROCLOR IOl6. MOWS 047965 1. MCS 1238 HYDROCARBON + HIGH DK COMPONENT 2. MCS 1588 HYDROCARBON + HIGH DK COMPONENT MONS 047966 V PROPERTY DK 25C 100C CORONA IV/EV HYDROLYSIS STABILITY* (NEUTRALIZATION NUMBER) DISSIPATION FACTOR FLUID TANg 60 HZ. 100C ^'.DISSIPATION FACTOR MODEL CAPACITOR AT 90C AROCLOR 1016 5-9 4-85 INDUSTRY 0.00 0.0025 0.0032 KCS 1238 6.0 5.1 INDUSTRY 0.00 0.05 0.0039 KCS 1588 6.1 5.i INDUSTRY S 0.00 0.05 0.0035 HONS 0 4 7 9 6 7 MONSANTO CANDIDATES ARE NOT FIRE RESISTANT. HONS 047968 ENVIRONMENTAL CONSIDERATIONS EXPOSURE DEGRADATION ACCUMULATION TOXICITY --^OCCUPATIONAL SAFETY ----- -ENVIRONMENTAL COMPABILITY MONS 0<r7969 O lbt*> 0 SNOW Material Aroclor 1254 Aroclor 1016 MCS 1238 BIODEGRADATION OF DIELECTRIC FLUIDS % Biodegradation 15 33 70 Exposure Time 48 48 48 Aroclor 1242 Aroclot 1016 MCS 1238 MONS 047971 . TOXICITY STUDIES - MCS 1238 IN-PLANT HANDLING RATE - ACUTE SINGLE ORAL DOSE LD 50 - 3800 MGS/KO. RABBIT - DERMAL LD 50 - 5.0 - 8.0 QMS PER KILOGRAM. RABBIT - POTENTIAL EYE IRRITATION - 12.0/110.0 NORMAL AFTER 72 HOURS. RABBIT - POTENTIAL SKIN IRRITATION (2k HR. CONTACT) - 3.6/8.0. ' MONS 047972 MCS 1238 - FURTHER PROGRAMS IN PROCESS OR SCHEDULED 1. VAPOR INHALATION. 2. ULTIMATE DEGRADATION. 3. ARC GASES. 4. PILOT FEEDING STUDY (90 DAY). 5. LONG-TERM (2 YEAR) FEEDING STUDIES. 6. FISH TISSUE RESIDUES. MONS 047973 STAGE T CAPACITOR REPLACEMENT 23 MOWSAUTO SCREEN (ELEC) A. SELECT MULTIPLE FLUID-^ B.SCREEN(TOX.) PRELIM. BROADEN ENVIRONMENTAL SCREEN INDUSTRY AGENCIES xo ziA o J I \ MULTIPLE APPLICATION r SCREEN 1 v CONSIDER SAFETY * ASPECTS TRANSFORMERS NEITHER WE NOR ANY OTHER COMPANY TO OUR KNOWLEDGE HAS DEVELOPED A TRANSFORMER INSULANT WITH EQUIVALENT FIRE RESISTANCE TO AROCLOR. ,1. PROTECTION UNDER TRANSFORMER FAULT CONDITIONS. 9. ARC FORM GASES. C. POTENTIAL SPREAD OF EXTERNAL FIRE. HONS 047975 WE DO HAVE CANDIDATES WITH INTERMEDIATE FIRE RESISTANCE OUR MAJOR OBSTACLE ABSENCE OF OBJECTIVE STANDARDS TO GUIDE POTENTIAL FLUID SUPPLIER ' TRANSFORMER PRODUCERS TRANSFORMER USERS INSURANCE GROUPS SAFETY ORGANIZATIONS GOVERNMENT AGENCIES ON REQUIRED LEVEL OF FIRE RESISTANCE. MQNS 047977