Document K6LBzJRrr80X2xJDRxmm9GvLN
PCB-GONE
000-321-9580 216-929-2847
Acts 4 12 P O Box 3575 Akron. Ohio 44310-0575
PCB-GONETM
An exclusive chemical process for the destruction of
Polychlorinated Biphenyls (PCBs).
Presented for public and commercial approval as regulated bv the United States Environmental Protection Agency.
HONS 0X4776
PCB-GONE"
The mobile teat laboratory is equipped with the electron capture gas chromatograph, supplies, and spill prevention and clean-up materials. The laboratory has complete climate control.
Inside the PCB-Gone" processor, the dripproof skids with decking, insulated piping, and reactor can be seen. This unit is operated from a centralized control panel in the Iron! of the trailer.
S. D. Myers, Inc. has developed their own system of chemically dechlorinating transformer oils con --- laminated with Polychlorinated Biphenyls (PCBs) and thereby destroying them. The process is housed in a mobile 40' semi-trailer specially designed to prevent expoeure to humans and the environment and safely hancRe theee liquids utilizing drip-proof skids, dikes, and a sophisticated automatic control system. The process has demonstrated its ability to destroy PCBs in con taminated oils at an efficiency of 99 9+ percent.
S, D. Myers, Inc., the pioneer in reclamation of oils in energized transformers, has been the leader in this Reid lor the past seventeen years. In addition to ser vicing 30,000 energized transformers, S. D. Myers, Inc. has designed and manufactured over eighty pieces ofoil handling equipment presently in service nationwide and abroad. Our continuous or batch treatment processing enables PCB-Gone" to operate on either energized or deenergized transformers. PCB-Gone" hes been
proven to be reliable, efficient, and safe to the environ ment.
S. D. Myers, Inc. with its central laboratory in Akron. Ohio, was the originator of "on-site" transformer oil testing with mobile laboratories that travel to the loca tion (all of continental U S ). The corporation has also established the criteria for evaluating "in-service" transformer oils that has gained nearly worldwide acceptance. Our laboratory is the leader in testing of PCBs in transformer oils as well as gas-in-oil analysis using gas chromatographic techniques.
The PCB-Gone" process results in a finished product (transformer oil free of PCBs) that has "like new" characteristics and is suitable for reuse as a dielectric in sulating fluid in transformers and/or other electrical ap paratus. Our in-house testing facilities as well as ap proved independent and EPA laboratories have con firmed that the PCB-Gone" process is effective in destroying PCBs in oil while yielding by-products that are environmentally safe and not harmful fn humanirivwt.
2
HONS 01.4777
BRIEF DESCRIPTION OF FLOW AND OPERATION
Oil contaminated with PCS Is drawn from a storage tank or transformer. The initial PCB contamination level (sample #1) is verified on-site using the por table electron capture gas chromatograph in the mobile support vehicle laboratory.
The oil then passes through a special inlet filter to protect the Inlet pump
Reagent is drawn from storage and injected into the oil on the suction side on the inlet pump. A flow meter gives the operator control over the predeter mined mix ratio (sample *7) that is based mainly on contamination level.
The inlet pump is a positive displacement rotary gear pump with pressure regulation, flow control, and recirculation for total variable flow.
The reagent and oil are then heated in an oil fired heeler. This heater is monitored by thermostatic control, flame sensor, differential pressure, and a flow switch.
The oM/reagenl mixture is then injected into the 300 gallon specially designed chemical reactor where the PCB Is destroyed. Here the oil is checked lor the pre-discharge PCB count (sample *6). Both mechanical and electrical overpressure and temperature devices monitor the reactor.
Next, the dechlorinated oil and reagent are separated Into pure streams by a centrifuge. A solid. Innocuous by-product is periodically discharged (sample *3) that was proven to be environmentally sale. Vent gases from the centrifuge were extensive ly tested (sample #9) and also found to be sale (both gases and condensables).
The used reagent is automatically returned to the storage tank lor reuse, or tested (sample #4) and dis posed of according to the scope ofourapproval. The reagent la PCB free and is not dangerous to handle.
The dechlorinated oil Is then cooled In a heat ex changer that provides both acceptable reclamation temperatures (~200*F) and heat to the reagent storage tank.
The oil Is then reclaimed in a S.D. Myers. Inc. oil purifier consisting of dual fullers earth filtering tanks (sample *5); a vacuum dehydrator (vent gas 410); and a final % micron filter with disposable paper car tridges (sample 46).
The discharge pump, which returns the oil to the desired location, is also a variable flow positive dis placement rotary gear pump with pressure regula tion.
The final oil sample (sample 42) is drawn for verifica tion of performance. The PCB-GooeTM process has
. been demonstrated to perform as follows:
i
SIMPLIFIED DESCRIPTION OF FLOW
PCS destruction -- 2100 to 0.5 ppm Dielectric breakdown vottage ...................... 40 KV Particle filtration .................................... 0.5 micron Acidity .......".........................0.03 mgKOH/gram Water content ............................................. 10 ppm EPA REGULATIONS AND QUALITY ASSURANCE PROCEDURES The waste volumes of the PCB-GonaTM process are all free of PCB. It is important to remember that all materials that have a limited life and must be eventually disposed, encounter the oil alter the dechlorination process. The operators of the PCB-GoneTM process are all experienc ed in oil handling. Our records and on-site analysts along with detailed quality control sheets will verily the PCB levels in the ten sample locations. S.D. Myers, Inc. is welt aware that the written con ditions of the U.S. E P A. approval require that PCB laden materials above the prescribed E.P.A level must be disposed of in an Annex It landfill. The PCB GoneTM reagent is also non-flammable and not water senotWvo to minimize problems. The spill prevention and countermeasure procedures spelled out in the Federal Register are strictly adhered to with the clean-up equip ment housed in the support vehicle laboratory.
RONS 014778
PCB-GONETM
The FCt-Qom' research program was an In-house program by the Chemists and Engineers at S.O. Myers, Inc. with the following goals in mind: V Develop t chemical destruction process tor PCBs In
transformer oW and later for pure askarel itself. 2. Have this process as safe as possible, l.e. no danger
to our operators or the environment. 3. Destroy the PCBs, yet yield a reusable mineral oil for
electrical apparatus. 4. Theprocessmustbemobilelnordertooperateatthe
transformer site, rather than transport the fluid to the PCB-GcneTM equipment. The success we have witnessed on all lour counts in deed make our process very unique.
The PCB-Qone" process utilizes a sodium-based reagent that when reacted with PCBs In transformer oil, yields by-products that have been determined sale. S.D. Myers, Inc. the U S. E.P.A., and Independent testing
sow s/u
laboratories have confirmed these resultswith testingas follows: Extensive PCB testing in oils, by-products, air
samples, and filter media. PCDF and PCDD testing on by-products. Skin Sensitization test on guinea pigs by TSCA
Topical Patch method on by-products. Oil integrity testing by Doble Engineering Co. and
S. D. Myers, Inc. Environmental Pollution Toxicity test.
The destruction process was demonstrated at a 99.96% efficiency on 2100 ppm.
The S.D. Myers, Inc. Manufacturing Division buitt and tested its first full scale unit with other units ready lor production. We present this practical, effective, cost ef ficient, and environmentally safe method for Polychlorinated Biphenyl destruction in contaminated transformer oil.
MOMS 014779