American Society of Heating and Ventilating Engineers Guide, 1931 :
PROBLEMS INVOLVING AIR VOLUME AND HEAT REQUIREMENTS'
The following cases arise in practice:
1. The heating of the building is done entirely by means of a fan steam system, all of the air being drawn from the outside.
2. Similar to (1), except that all of the air is recirculated.
3. A portion of the air is recirculated, and the remainder is drawn in from the outside
4. Air at the same temperature to be delivered to all the rooms. A constant relative
humidity is maintained in the building and all of the air circulated is drawn from outside
the building. (Not applicable to the heating of various rooms where individual control
of each room is desired).
1
5. Arrangement similar to (4), except that a portion of the air is recirculated.
6. Arrangement of apparatus where individual control of the temperature for each room is required in conjunction with air washer equipment to maintain a constant relative humidity in the rooms. The air washer is provided with a water heater for the spray water, capable of fully saturating the air. It is impossible to maintain the same
room temperature throughout the building with a uniform temperature of the air enter ing the rooms owing to the fact that the weight of air to be delivered to each room is determined and fixed by the ventilating requirements.
In analyzing these six cases, the following symbols will be used:
H = heat loss of the room or building, Btu per hour. H\ = heat to be supplied to the heater, Btu per hour.. H% = heat supplied tempering coil, Btu per hour. Hi == heat supplied air washer, Btu per hour. M = weight of air to be introduced into the room or building, pounds per hour. Mi = weight of recirculated air, pounds per hour.
Mo ~ weight of air drawn in from outside, pounds per hour. /p.~ mean temperature of outside air, degrees Fahrenheit.
. / -- mean air temperature to be maintained in the room or building, degrees ' Fahrenheit. J fi ,= mean temperature of the air entering the heater.
ti = mean- temperature of the air leaving the heater. t.= assumed temperature loss in the duct system.
' ^ temperature f the air leaving the duct outlets. 0.24 = specific heat of air at constant pressure.
ty T tz -- tl or ty -- ti -- tz
Cksdff. (Fig. 3). All' of'the air circulated to be drawn from outside the building, in
which cas^(ii -- to).
'-r;vy:
"
0.24 (ty --t)
Hx = 0.24 '(it- tx)M
Example'. The heat loss if for a certain factory buildingis 700,000 Btu per hour. The mean: inside temperature'1 to be maintained. is 65 F. The assumed outside air tem
perature f0 is O.deg; tz =0and.fy -- it and is assumed to be 140 F. Required, M and ifi.
700,000 0.24 (140 - 65)
38,889 lb per hour
Hi = 0.24 (140 - 0) 38,889 - 1,305,000 Btu per hour.
- ^See Mechanical-Equipment of-Buildings, by Harding and Willard, V'ol. I, second edition,. 1029.
128
Chapter 8--Fan Steam Heating (Fig- 4) AU of the air is to be recirculated, in which case h = t. Caset the data from the preceding example, M = 38,889 and from Formula 2 Using
= 0.24 (140 -- 65) X 38,889 = 700,000 Btu per hour
Fig. 4. Arrangement for Recirculation (Case 2) '
Fig. 5. Combination of Recirculated and Outside Air (Case 3)
This example illustrates the saving in fuel consumption by the recir
culation of the air. The heat to be supplied the apparatus is the same as
that required for a direct system of heating and is equal to the heat loss
of the building (Hi - IT).
.
129